MANUAL ON TECHNICAL GUIDELINES FOR HOSPITAL PLANNING AND DESIGN 250-BED HOSPITAL (LEVEL 3)

List of Volumes

Volume 1 – INTRODUCTION AND INSTRUCTIONS FOR USE Volume 2 – STANDARD PLANS OF A 250-BED HOSPITAL (LEVEL 3) Volume 3 – DEPARTMENTAL PLANS AND TECHNICAL REQUIREMENTS OF A 250-BED HOSPTAL (LEVEL 3) Volume 4 – APPENDICES

First Edition DEPARTMENT OF HEALTH Manila 2017


MANUAL ON TECHNICAL GUIDELINES FOR HOSPITAL PLANNING AND DESIGN 250-BED HOSPITAL (LEVEL 3)

VOLUMES

Volume 1 – INTRODUCTION AND INSTRUCTIONS FOR USE Volume 2 – STANDARD PLANS OF A 250-BED HOSPITAL (LEVEL 3) Volume 3 – DEPARTMENTAL PLANS AND TECHNICAL REQUIREMENTS OF A 250-BED HOSPTAL (LEVEL 3) Volume 4 – APPENDICES

First Edition DEPARTMENT OF HEALTH Manila 2017


MANUAL on TECHNICAL GUIDELINES for HOSPITAL PLANNING and DESIGN 250-BED HOSPITAL
(LEVEL 3)

VOLUME 1 INTRODUCTION and INSTRUCTIONS FOR USE

First Edition DEPARTMENT OF HEALTH Manila 2017


VOLUME 1 INTRODUCTION and INSTRUCTIONS FOR USE

TABLE OF CONTENTS

PAGE 1.0 INTRODUCTION

1.1. Purpose of the Manual on Technical Guidelines 1

1.2. Format of the Technical Guidelines 1

1.3. Functions of the Technical Guidelines 1

1.4. Updating of the Technical Guidelines 1

1.5. Need for Technical Guidelines 2

1.6. Limitation of the Manual on Technical Guidelines 2

2.0 INSTRUCTIONS FOR USE

2.1. Room Data Sheet A : 5

FUNCTIONAL DESIGN REQUIREMENTS

2.2. Room Data Sheet B : 6

TECHNICAL DESIGN DATA

2.3. Room Data Sheet C : 12

TECHNICAL DESIGN DATA and LAYOUT OF

ROOM and SPACE REQUIREMENTS


1

1.0 INTRODUCTION It is the policy of the Department of Health (DOH) to provide both preventing and curative healthcare that are available, accessible, acceptable, and affordable to the people. Such policy determines to a large extent the provisions of hospitals and other healthcare facilities.
The provision of hospitals and other healthcare facilities involves a significant amount of capital investment and operational expenditure. It is then imperative to give utmost attention and concern to hospital planning and design, considering the country’s socio-economic, cultural, political, and technological conditions; the rapid advance in medical and design technology; and the country’s limited resources.
1.1 Purpose of the Guidelines The primary objective of the technical guidelines is to serve as a tool for hospital planning and design. 1.2 Format of the Technical Guidelines The technical guidelines are presented on a per room basis. Every room is discussed in three (3) different types of Room Data Sheet (RDS). The Room Data Sheet A: FUNCTIONAL DESIGN REQUIREMENTS provides information on functional design requirements, stating the facilities (equipment, furniture, engineering terminals, etc.) needed to support the activities of the room user. The Room Data Sheet B: TECHNICAL DESIGN DATA states the ideal environmental conditions that must be maintained in a room. The Room Data Sheet C: TECHNICAL DESIGN DATA and LAYOUT OF ROOM AND SPACE COMPONENTS gives additional technical design data specifying direct services provided in the room and direct demand on floor and wall, that shall help designers identify appropriate finishing materials. Further, a room layout and area requirement is also provided.
1.3 Function of the Technical Guidelines These technical guidelines and prototypes shall serve as tools and reference guide for hospital planning and design and not as dogmatic documents to be used for specific projects.
It is the intention of the guidelines to provide users with basic information on the functional and technical requirements for the planning and design of a 250-Bed Hospital, Level 3 Classification.
Along with this technical guidelines manual is a catalogue of operational and management manuals, also prepared by the Health Facility Development Bureau (DOH-HFDB), which should be used as cross-references for this Technical Manual. (See List of Manuals under Cross-References) 1.4 Updating the Technical Guidelines It is envisioned that the further improvement of the technical guidelines shall emanate from the result of its continued use and cross-referencing against any hospital design brief.


2

Comments and results from test-case application of the technical guidelines shall be evaluated. The final outcome of the evaluation will determine the corresponding revisions to be made in the guidelines. These shall be the inputs used in the updating the guidelines.
1.5 Need for Technical Guidelines In writing about using a selection of existing techniques and tools for planning health facilities, Dr. Montoya Aguilar of the SHA/WHO Headquarters says, “Subject to an understandable range of nuances, people agree that rigid standards are to be excluded and that typical plans and modules are useful, but only as references or examples of approaches. Indeed, along with alternative reference plans designed for typical situations, planners should also formulate guidelines on how to adapt them for more specific circumstances. Certain technical norms are, of course, necessary and statutory. But, even these must be revised from time to time.” Truly, there are a lot of these guidelines and typical plans but these are however scattered and not thoroughly explained nor set in the proper context of our environment. There is therefore a need for selecting and if possible formulating a set of tools for health facility planning design appropriate for our milieu.
It is generally perceived that the licensing requirements set by the Health Facilities and Services Regulatory Bureau (DOH-BHFS) is a large effort to readily meet the “norms and standards which are necessary and statutory.” What this technical guideline manual seeks to achieve is to address the challenge of hospital planning and go beyond what is required by the BHFS. Because in the final analysis, each hospital project will and shall remain novel and unique in its adaption of the socio-cultural, physical and other characteristics of the community it seeks to serve.
1.6 Limitation of the Technical Guidelines This Manual of Technical Guidelines is limited to a 250-Bed Hospital, Level 3 Classification only. Typical, Redundant and Special Rooms/Spaces In the use of these Technical Guidelines, there will be some rooms/spaces/areas shown on the floor plans that do not have Room Data Sheets --- this is due to several reasons: 1) they are “typical” in nature and thus can be referenced through other Room Data Sheets (i.e. Office, Clinic, etc.); 2) they are redundant, meaning previous Room Data Sheets have already been presented (i.e. Conference/Meeting Room, Storage Room, Pantry, etc.); or 3) they are specialty layouts which are beyond the scope of this Manual (i.e. Auditorium, etc.).
For all cases, it is recommended that the users of this Manual perform due diligence in executing their work: hospital administrators to properly brief designers, and designers to consult hospital end-users regarding the specific and unique requirements of their rooms/spaces/areas.
Refer to the tabulation below for rooms/spaces/areas shown on the floor plans that do not have Room Data Sheets: Room / Space Remarks  Administrative (Executive)


3

 Infection Control Office Refer to Typical Office; shown in Manual as ADMINISTRATIVE – Office (Typical): 250B-AD-RDS-22

 Legal Office

 Public Health Office

Room / Space Remarks  Auditorium
The Auditorium is shown on the floor plan to indicate requirements of space and location. The size of the space shown also indicates scale and proportion for a Level 3 Hospital. The Auditorium design, however, depends on several end-user requirements (e.g. seating form and type, acoustics, lighting, sound, etc.) which fall under the scope of a specialty designer/architect.
 Emergency Service

 Waste Holding Room May be cross-referenced with NUTRITION AND DIETETICS – Waste Holding Area: 250B-DIET-RDS-13

 Supply Room Room/space is an open plan; cabinets and/or shelving to depend on end-user requirements

 Equipment Storage Room Room/space is an open plan; cabinets and/or shelving to depend on end-user requirements

 Affiliates’ Room Room/space is an open plan; seating, desks and/or tables to depend on end-user requirements

 Conference Room May be cross-referenced with ADMINISTRATIVE – Conference Room: 250B-AD-RDS-12

 Electrical Room Room/space is an open plan; electrical equipment/components (e.g. UPS, transformers, panel boards, etc.) to depend on electrical designer’s requirements
 Outpatient Service

 Affiliates’ Room Please see above (ER-Affiliates’ Room)

 Psychiatric Clinic Refer to Typical Office; shown in Manual as OUTPATIENT – Clinic (Typical): 250B- OPD-RDS-16

 Animal Bite Clinic

 STD/HIV Clinic

 Various OPD Clinic

 Lactation Room May be cross-referenced with NEONATAL INTENSIVE CARE UNIT – Breastfeeding Room: 250B-NICU-RDS-03

 Electrical Room Please see previous  Ambulatory Surgery Clinic

 Sub-Waiting Area Room/space is an open plan ; type of seating to depend on end-user requirements

 Staff Dress Area Room/space is an open plan
 Laboratory


4

 Storage Room Room/space is an open plan; cabinets and/or shelving to depend on end-user requirements

 CMT Office Please see previous (Admin-Typical Office)

 Affiliates’ Room
Please see previous (ER-Affiliates’ Room)

 Records Room
May be cross-referenced with ADMINISTRATIVE – Records Room: 250B-HIMS-RDS-06

Room / Space Remarks  Blood Station

 Blood Issuance Area Room/space is an open plan

 Records Room May be cross-referenced with ADMINISTRATIVE – Records Room: 250B-HIMS-RDS-06  Radiology

 Supply Room Please see above (ER-Supply Room)

 Ultrasound 1 & 2 Typical with Ultrasound 3; shown in Manual as Ultrasound Room; please refer to RADIOLOGY – Ultrasound Room: 250B- RAD-RDS-07

 Patient Dress Area
Please see previous (Ambulatory Surgery Clinic-Staff Dress Area)  Nursing Service

 Visitors’/Caretakers’ Pantry May be cross-referenced with ADMINISTRATIVE – Pantry: 250B-HIMS- RDS-08

 Affiliates’ Room
Please see previous (ER-Affiliates’ Room)

 Storage Room Please see previous (Laboratory-Storage)  Operating Room Complex

 Affiliates’ Room
Please see previous (ER-Affiliates’ Room)

 Conference Room/Library Please see previous (ER-Conference Room)  Intensive Care Unit (ICU) and similar

 Equipment Storage
Please see previous (ER-Equipment Storage
Room)

 Medical Intensive Care Unit Typical; shown in Manual as Intensive Care Unit – Patient Bay: 250B-ICU-RDS-02

 Surgical Intensive Care Unit Typical; shown in Manual as Intensive Care Unit – Patient Bay: 250B-ICU-RDS-02  Delivery Room and Nursery Complex

 Septic Labor Room Room/space same as Labor Room, with septic cases physically separated from regular cases to avoid infection

 Septic Delivery Room Room/space same as Delivery Room, with septic cases physically separated from regular cases to avoid infection


5

 Isolation Room May be cross-referenced with NURSING WARDS – Isolation Room: 250B-NU-RDS- 07

 Releasing Area
Room/space is an open plan  Neo-Natal Intensive Care Unit (NICU)

 On-Call Room May be cross-referenced with ER – On-Call
Room: 250B-ER-RDS-18

 Receiving Area
Room/space is an open plan  Linen and Laundry

 Pantry
May be cross-referenced with ADMINISTRATIVE – Pantry: 250B-HIMS- RDS-08

Room / Space Remarks  Property and Supply

 Issuing Area Room/space is an open plan

 Hazardous Items Storage
Room/space same as typical Storage Room, with special storage, cabinets, shelving, etc. to depend on end-user requirements

 Temp-controlled Storage
Room/space same as typical Storage Room, with special storage, cabinets, shelving, etc., including necessary temperature and other related considerations to depend on end-user requirements

 Meeting Room May be cross-referenced with ADMINISTRATIVE – Conference Room: 250B-AD-RDS-12

2.0 INSTRUCTIONS FOR USE The Technical Guidelines is presented in the following Room Data Sheet format:
2.1 Room Data Sheet A: FUNCTIONAL DESIGN REQUIREMENTS This pertains to the essential design considerations which include listing of facilities required and user-related data involved to support and achieve the intended function of the room. These essential design considerations are the following: 2.1.1 Activities Involved: a listing that provides a clearer understanding of the activities performed within the designated area. The specific description of the activities involved gives information on the type and number of furniture and equipment needed to support the listed activities. As these essential information are converted into spatial dimensions, area quantification can now be derived.
2.1.2 People Involved: a listing that provides the number of occupants or users of the room at any time. This refers to the specific regular office period/hour or any other


6

work period or shift. Through anthropometrics, space quantification can be done to identify the size of work areas to be provided to support the activities of the room occupants. This shall also help in determining the number of particular furniture and equipment needed.
This listing varies in accordance with existing official and projected plantilla or organizational set-up in any particular hospital.
2.1.3 Planning Relationship: indicates the areas and services that are to be located adjacent/close to one another, and easily accessible to the room being discussed or referred to in the manual.
2.1.4 Equipment and Accessory Checklist: indicates any of the following: tools, implements, apparatus, appliances, devices, accessories, attachments, and gadgets.
2.1.5 Furniture and Fixture Checklist: indicates either movable or non-movable articles and fixtures found in a room that may or may not significantly occupy floor areas.
2.1.6 Additional Equipment and Engineering Terminals: indicates other accessories and fixtures that do not necessarily occupy a particular floor area within the room but must be recognized for their functional importance. These fixtures are usually wall- or ceiling-mounted.
2.2 Room Data Sheet B: TECHNICAL DESIGN DATA This pertains to the essential technical data that must be considered in establishing and maintaining quality and the ideal environment for any hospital in relation to the following four (4) conditions: 2.2.1 Air 2.2.1.1 Outdoor Air Temperature (deg. C) – the average prevailing atmosphere temperature of a locality in degrees Centigrade. As the outdoor temperature increases, the desirable room temperature in an air- conditioned space increases.
Temperature Ranges: Cold

  • below 10 deg. C Cool
  • 10 deg. C to 15 deg. C Temperate - 15 deg. C to 27 deg. C Hot
  • 27 deg. C to 38 deg. C Very Hot
  • above 38 deg. C 2.2.1.2 Room Temperature (deg. C) – the ideal temperature of an air- conditioned space for employees or hospital staff to work with ease or for a patient to be comfortable. This is sometimes referred to as the effective temperature. Effective temperature is an empirically determined index which combines into a single value the effect of temperature, humidity, and air movement on the sensation of warmth or coolness felt by the human body. The numerical value is that of the temperature of still

7

saturated air which could induce an identical sensation. The wide range of effective temperature is indicated in graphical representation of comfort zone.
2.2.1.3 Mechanical Ventilation – the process of supplying air or removing air by mechanical means for or from any space. Such air may or may not have been conditioned. To minimize odors and to maintain freshness of the air, a quantity of outdoor air should be required to control body odors. Odors satisfactorily decreases as the volume space per occupant increase.
2.2.1.3.1 Volume (cu.m./hr.-person) – the quantity of outside air ventilation requirement in cubic meter per hour per person 2.2.1.3.2 Velocity (m./min.) – the speed of outside air ventilation requirement in meter per minute
2.2.1.4 Pressure Differential – in all infectious rooms, bacteriology laboratory and rooms using toxic chemicals, the following are required:
2.2.1.4.1 Negative Pressure (Pa) – amount of pressure required for an exhaust fan to force the contaminated air out of the room
2.2.1.4.2 Positive Pressure (Pa) – amount of pressure required for an equivalent inlet fan to normalize the room air pressure
2.2.1.5 % Dust Filtration – the quality of indoor air should be clean and dust free. Dust and other heavily contaminated tiny particles of pollutants should be removed from the air to prevent respiratory ailments and other diseases.
2.2.1.6 Humidity (% RH) – unless otherwise stated will mean the relative humidity in percent (%RH). This is the ratio of the actual (measured) partial pressure of the water vapour in the air mixture to its saturation pressure at the same dry bulb temperature. This is also the ratio of the actual weight of moisture per cubic meter of mixture to the weight of the saturated water vapour per cubic meter of mixture at the same dry bulb temperature.
Relative Humidity Ranges (%RH) Very Dry

  • 0-25% Dry

  • 25-50% Humid

  • 50-75% Very Humid

  • 75-100% 2.2.1.7 Cooling Load (TR) – the total calculated heat and moisture of a room in Tons of Refrigeration (TR) equivalent to 12,660 KJ/Hr.
    The following are the major sources of cooling load: a. Product load in cooling and maintaining low temperature of a product; b. Solar transmission through walls, ceilings, floors, doors, ducts, and pipes --- a process of conduction;


8

c. Radiation and conduction through windows; d. Occupants - sensible heat given-off by people; e. Electrical equipment - heat from lights, motors, and other appliances; f. Infiltration - exchange of conditioned air with outdoor air through door openings and cracks; g. Ventilation - the controlled replacement of conditioned air with outdoor air; and h. Latent load - condensation by the air-conditioner or moisture from such sources as people, cooking appliances, and outdoor air.
2.2.2 Sound 2.2.2.1 Acceptable Sound Level (db) – the level that must be observed in a particular area to achieve the acoustical requirements in order that the activities involved may proceed unhampered.
The following tables provide information on the acceptable sound level (db) for a particular area:
2.2.2.1.1 Table I – Recommended Category Classification for Background Noise Levels

Type of Space

Acoustical
Requirements
Acceptable Equivalent Noise Level Range in decibels (db)  Intensive care areas, recovery areas  Quiet surrounding must be maintained
 For listening to faint musical sound 20 - 30  Large meeting and conference rooms, executive offices and conference rooms for 50 people  For good listening
35 - 40  Bedrooms, sleeping quarters  For sleeping, resting, and relaxing
35 – 45  Private and semi- private offices, small conference rooms, classrooms, libraries
 For good listening conditions
40 – 45  Lounging areas and similar spaces  For conversing or listening to radio or TV
45 – 55  Large office, reception areas, waiting areas, dining areas, cafeterias
 For moderately good listening conditions
45 – 60  Lobbies, laboratory work spaces, general secretarial areas  For fair listening conditions
50 – 55  Light maintenance shops, offices, and computer equipment  For moderately fair listening conditions
55 – 70


9

rooms, kitchen and laundry areas
 Shops, garages, power plant control rooms  For acceptable speech and telephone communications
70 – 110

2.2.2.1.2 Table II – Common Noise Levels

Type of Sound

Subjective Impression
Sound
Level (db)  Siren at 30,480mm  Deafening, threshold of pain
120  Wood working shop, accelerating motorcycle  Threshold of discomfort
110  Loud street noise  Power lawn mower
 Car/truck unmuffled  Kitchen blender  Very loud
90  Noisy office
 Loud, intolerable
80  Average street noise  Quiet typewriter  Average radio  For phone use
70  Average office  Normal conversation
 General office
 Quiet radio  Quiet street  Usual background
60  Private office
 Quiet bedroom  Quiet conversation  Noticeably quiet
40 30  Whisper  Human breathing
 Very quiet 20 10  Complete silence
 Intolerably quiet threshold of audibility
0

2.2.2.1.3 Table III – Average Ambient Noise Levels of Interior Spaces Area Average Ambient Noise Level (db)  Television or radio station, church, synagogue 20-34  Office, residence, night school 26-30  Library, reception or reading room, school study hall 31-36  Noisy office, doctor’s or dentist’s office, classroom 37-42  Store and factory
43-49

2.2.2.2 Speech Privacy – levels that indicate extent of acoustical limits and identify areas where application of acoustical provisions is necessary


10

2.2.2.3 Quality Which Cannot be Tolerated – the presence of noise characterized as tonal impacts which are incompatible with the required acceptable sound/noise level and may also hinder achieving and performing the desired activities involved in a particular area 2.2.3 Lighting and Visual 2.2.3.1 General Illumination (lux) – is a method of illumination that provides an approximately uniform level of illumination on the work plane over the entire area. The luminaries are usually arranged in a symmetrical plan fitted into the physical characteristics of the area and blend well with the room architecture. They are relatively simple to install and does not require coordination with furniture or machinery that may not be in place at the time of the installation. Perhaps the greatest advantage of using this system of illumination is that it permits complete flexibility in task location. In this system of illumination, lighting units are supported fairly close to the ceiling or at least at a considerable distance above the working plane. They are spaced uniformly throughout the area without special regard to the location of equipment, machinery, furniture, etc., and at such a distance from one another as to give nearly uniform illumination.
2.2.3.2 Night Illumination (lux) – reduced lighting levels for period of low or minimal activity usually observed during night time 2.2.3.3 Task Illumination (lux) – provides lighting only over a relatively small area occupied by the task and its immediate surrounding. The illumination may be from lamps mounted near the task or from remote spotlights. This system is also called local lighting. It is an economical means of providing higher illumination levels over a small area, and it usually permits some adjustment of the lighting to suit the requirements of the individual. Improper adjustment may, however, cause annoying glare for nearby workers. Local lighting by itself, is seldom desirable. To prevent excessive changes in adaptation, it should be used in conjunction with general lighting or illumination that is at least 20% of the local lighting level; it then becomes supplementary lighting.
2.2.3.4 Color Rendering – is a general expression for the effect of a light source on the color appearance of objects in conscious or subconscious comparison with their color appearance under a reference light source. For example, a case of the fish looking red or fresh under pink light. It is defined as the degree to which perceived colors of objects as illuminated by a test source conform to the colors of the same objects as illuminated by a standard source. The standard is always daylight as that color temperature. Therefore, the color rendering index of a light is really a measure of how closely it approximates daylight of the same color temperature.


11

2.2.3.5 Standby Light – the installed reserve lighting equipment in excess of that required which is a reliable support or source to carry peak load 2.2.3.6 Emergency Light – lighting designed to supply illumination essential to the safety of life and property in the event of failure of the normal supply. It is required when the normal source is interrupted for any of the following reasons: a. Interruption of current flow through operation of a circuit disconnect. For example, inadvertent de-energizing of a circuit at a panel or switchboard; b. Failure of the building’s electrical system; or c. General power failure. 2.2.3.7 Daylight – the cheapest (insofar as energy is concerned), most abundant and in many ways, most desirable form of lighting available. The presence of daylight in interior spaces is made possible by windows and other similar openings. When daylight enters through windows (side lighting, as opposed to top lighting), its horizontal directivity provides good modelling shadows, minimal veiling reflections and excellent vertical surface illumination. Further, the continual variation of daylight, which is one of its prominent characteristics, provides a constantly changing pattern of space illumination; that is unattainable with artificial light. Since these changes are gradual, the eyes adapt easily and the effect is one of visual restfulness and interest.
On the other hand, no ill effects have conclusively been demonstrated to have been caused by lack of daylight; that is by working in an artificially lighted space. An artificial lighting system must be installed in any event, to furnish interior illumination during periods when daylight is insufficient.
Since daylight is variable, it creates special problems of glare control, direct sunlight control and heat gain limitation in large measure. The science and art of daylighting is not so much how to provide daylight but how to do so without the attendant undesirable effects. It is thus imperative to adopt the technique of permanent supplementary artificial lighting in interiors. This design approach/technique views artificial lighting as supplementary to daylight and not vice versa. For structures that are extracted to be in use at night, artificial lighting must be designed to furnish all of the required lighting.
2.2.3.8 View Out – the provision of openings, like windows, in interior spaces that will create visual contact with the outside and the resultant effect providing a bright, pleasant and airy ambiance to the room 2.2.3.9 Privacy – as opposed to being public, not exposed; not open; seclusion; isolation; separateness


12

2.2.3.10 Black Out – deliberated exclusion of unwanted light necessary in the performance of specific activities involving special procedures that may require special low level lighting or the complete absence of some specific type of lighting
2.2.4 Safety 2.2.4.1 Accessible Hot Surface – identifies heat generating equipment whose surfaces may reach temperatures of dangerous levels that users may possibly come in contact with
2.2.4.2 Accessible Hot Water – identifies the sources and location of accessible hot water with its allowable maximum temperature for safe use 2.2.4.3 Access Limit – identifies the authorized room or facility users in order to identify the proper security measures to be adopted
2.2.4.4 Fire Risk – identifies the level (quantity and quality) of fire hazards present in the space being discussed in order that proper fire prevention measures may be applied 2.2.4.5 Other Risks – identifies other health hazards that may be present in the room other than what it previously listed that may pose as some danger to room users 2.3 Room Data Sheet C: TECHNICAL DESIGN DATA ON DIRECT SERVICES AND DEMANDS ON FLOOR AND WALL and LAYOUT OF ROOM AND SPACE COMPONENTS 2.3.1 Direct Services – this refers to the required basic utilities and other convenient necessities that must be provided in a specific area 2.3.1.1 Disposal – identifies the type of waste generated in an area, treatment of which must conform with the approved operational programs for solid waste management as established by the Department of Health (DOH)
2.3.1.2 Hot Water – identifies fixture source and location of this particular utility 2.3.1.3 Cold Water – identifies fixture source and location of this particular utility 2.3.1.4 Drainage – identifies fixtures and areas to be provided with this utility. Treatment of sewage material must also conform with the approved operational programs for liquid waste management as established by the Department of Health (DOH)
2.3.1.5 Gas – identifies areas to be provided with this utility (may either refer to medical or non-medical); the types of which, whether supplied in portable cylinders or through wall outlets, must be determined according to the capacity to supply and to safely maintain such as system 2.3.1.6 Compressed Air – see 2.3.1.5


13

2.3.1.7 Steam – identifies location where required 2.3.1.8 Others – indicates other necessary utilities not previously listed
2.3.2 Direct Demands on Floor and Wall – the extent of usage and other factors, such as the activities involved, affecting the performance of materials to be used as finishing for floors and walls
2.3.2.1 Loading – type of loads, whether light moving loads or heavy stationary loads that will be taken into consideration so that ample structural support can be provided
2.3.2.2 Spillage – the type and frequency of accidental or unintentional falling or throwing of items and materials in the area, that the floor and finishing materials must conform with
2.3.2.3 Foot Traffic – the expected maximum level of the traffic that can be observed in a particular area that the floor finishing materials must be able to support. The finishing material must be durable enough to withstand the movement with the least need for maintenance and upkeep 2.3.2.4 Wheel Traffic – see 2.3.2.3
2.3.2.5 Impact – the force or collision where either floor or wall is subjected to when equipment or other bulky items are being moved or transported 2.3.2.6 Abrasion – scraping or wearing away by friction in either floor or wall brought about by foot and wheel traffic and the movement and transportation of equipment and other load-bearing items 2.3.2.7 Easy Maintenance – where the practice and observance of cleanliness or sanitation can be carried out with a minimum involvement of work and effort 2.3.2.8 Vibration Free – maintaining the constant absence of quivering or trembling disturbances both physical and auditory, that may originate from machines, equipment, and other obvious sources. The absence of these disturbances may be necessary to maintain a safe and secure room atmosphere 2.3.2.9 Door Sets – identifies the type of door, its size and material finish, so that equipment and other listed items may be provided easy access, smooth transfer and movement from one area to another
2.3.2.10 Windows – determine the type, size, and material finish of the windows in order to meet the quality of the interior atmosphere that must be maintained in a room 2.3.2.11 Internal Glazing – identifies the type of glass finishes to be used, whether clear, opaque, etc.


14

2.3.3 Layout of Room and Space Components – indicative rooms plans showing the space components, dimensions, and the required equipment and furnishings to be installed in the room
2.3.4 Space Demands – the quantity or the number of each space component and its standard minimum area requirement that shall comprise the total minimum area requirements of the room (To be filled out by the Designer, in most cases; since this is based on End-Users’ specific needs; in addition to licensing and minimum requirements) 2.3.5 Regulations and Notes – special rules, regulations, and directives that must be applied during the design process to improve and standardize the hospital design and plan (To be filled out by the Designer, in most cases; for local laws and ordinances in addition to national rules and regulations)


MANUAL on TECHNICAL GUIDELINES for HOSPITAL PLANNING and DESIGN 250-BED HOSPITAL
(LEVEL 3)

VOLUME 2 STANDARD PLANS and TECHNICAL REQUIREMENTS of a 250-BED HOSPITAL (LEVEL 3)

First Edition DEPARTMENT OF HEALTH Manila 2017


VOLUME 2 STANDARD PLANS and TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

TABLE OF CONTENTS

PAGE 2.A 250-BED HOSPITAL (LEVEL 3)

FOUR-STOREY MODEL

Site Development Plan 15

Ground Floor Plan 16

Second Floor Plan 17

Third and Fourth Floor Plans 18

Ground Floor Zonal Plan 19

Second Floor Zonal Plan 20

Third and Fourth Floor Zonal Plans 21

Perspectives 22

17 19 20 21 22 23 24 25 26


GRAPHICAL SCALE (METERS) 0 5 10 20 1 2 3 4 5 SITE DEVELOPMENT PLAN SCALE 1:1200M MORGUE ENGINEERING MAINTENANCE SECURITY HOUSEKEEPING HEALTH INFORMATION MANAGEMENT SYSTEM CENTRAL WASTE STORAGE DIETETICS LAUNDRY & LINEN PROPERTY SUPPLY & MANAGEMENT 250-BED HOSPITAL 250-BED HOSPITAL 19


UP UP UP RAMP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP RAMP UP UP RAMP UP RAMP UP RAMP UP RAMP UP RAMP UP UP RAMP UP GRAPHICAL SCALE (METERS) 0 5 10 20 1 2 3 4 5 GROUND FLOOR PLAN SCALE 1:1000M PROPERTY SUPPLY & MANAGEMENT OFFICE LAUNDRY & LINEN DIETETICS DEPARTMENT IMAGING DEPARTMENT LABORATORY DEPARTMENT OPD LOBBY PHYSICAL REHABILITATION DEPARTMENT OPD TB DOTS CLINIC HEMODIALYSIS BLOOD STATION MAIN HOSPITAL LOBBY EMERGENCY DEPARTMENT ENGINEERING, MAINTENANCE, HOUSEKEEPING & SECURITY PRAYER ROOM MRI HEALTH INFORMATION MANAGEMENT SYSTEMS CENTRAL WASTE STORAGE MORGUE 250-BED HOSPITAL OPEN COURT OPEN COURT OPEN COURT OPEN COURT SERVICE YARD OPEN COURT OPEN COURT OPEN COURT 20


RAMP DN RAMP DN UP DN UP UP DN DN DN UP DN DN DN DN DN DN DN DN DN DN DN DN DN DN DN DN RAMP DN RAMP UP DN UP GRAPHICAL SCALE (METERS) 0 5 10 20 1 2 3 4 5 SECOND FLOOR PLAN SCALE 1:1000M 250-BED HOSPITAL HEALTH INFORMATION MANAGEMENT SYSTEMS SURGERY WARD OBSTETRICS WARD CENTRAL STERILE SUPPLY ROOM PICU BURN UNIT SICU OR COMPLEX DR COMPLEX NICU OPD OFFICES AUDITORIUM OPEN BELOW OPEN BELOW OPEN BELOW SOLARIUM OPEN BELOW OPEN BELOW OPEN BELOW OPEN BELOW MICU OPEN BELOW 21


DN UP DN DN UP UP UP DN RAMP DN RAMP UP RAMP DN DN DN DN DN GRAPHICAL SCALE (METERS) 0 5 10 20 1 2 3 4 5 GRAPHICAL SCALE (METERS) 0 5 10 20 1 2 3 4 5 FOURTH FLOOR PLAN SCALE 1:1000M THIRD FLOOR PLAN SCALE 1:1000M 250-BED HOSPITAL 250-BED HOSPITAL MEDICINE WARD PEDIATRIC WARD PRIVATE ROOMS PRIVATE ROOMS SOLARIUM SOLARIUM 22


OPEN COURT CENTRAL WASTE STORAGE ELEVATOR LOBBY E E EE ROOM HEALTH INFORMATION MANAGEMENT SYSTEMS UNASSIGNED E E E EE ROOM ELEVATOR LOBBY G A R D E N G A R D E N G A R D E N MAIN HOSPITAL ENTRANCE EMERGENCY ENTRANCE OPD ENTRANCE PROPERTY SUPPLY and MANAGEMENT OFFICE M A I N H O S P I T A L L O B B Y HEMODIALYSIS OPD PHYSICAL REHABILITATION DEPARTMENT UP UP UP RAMP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP RAMP UP RAMP UP RAMP UP RAMP UP RAMP UP RAMP UP UP BLOOD STATION IMAGING DEPARTMENT TB DOTS CLINIC EMERGENCY DEPARTMENT DIETETICS DEPARTMENT DINING HALL LINEN & LAUNDRY DEPARTMENT MORGUE ENGINEERING, MAINTENANCE, HOUSEKEEPING & SECURITY WATER PUMP ROOM POWER HOUSE CANTEEN TOILETS EE ROOM RAMP UP TOILETS TOILETS TOILETS TOILETS MRI OPD TOILETS ADMINISTRATIVE OFFICES TOILETS PHARMACY DEPARTMENT DRUG TESTING PRAYER ROOM TOILETS EMERGENCY DEPARTMENT OPEN COURT OPEN COURT OPEN COURT TOILETS GRAPHICAL SCALE (METERS) 0 5 10 20 1 2 3 4 5 GROUND FLOOR ZONAL PLAN SCALE 1:1000M 250-BED HOSPITAL 23


O P E N B E L O W R O O F G A R D E N O P E N B E L O W O P E N B E L O W O P E N B E L O W O P E N B E L O W O P E N B E L O W RAMP DN E E EE ROOM E E EE ROOM ELEVATOR LOBBY ELEVATOR LOBBY O P E N B E L O W RAMP DN UP DN UP UP DN DN DN UP DN DN DN DN DN DN DN DN DN DN DN DN DN DN DN DN UP HEALTH INFORMATION MANAGEMENT SYSTEM SURGERY WARD RAMP DN RAMP UP OB-GYNE WARD AMBULATORY SURGERY OPD CLINICS OPD CLINICS OPD CLINICS OFFICES OFFICES AUDITORIUM EXECUTIVE OFFICES DELIVERY ROOM COMPLEX OPERATING ROOM COMPLEX MEDICAL ICU NICU CENTRAL STERILE SUPPLY ROOM PEDIA ICU SURGICAL ICU BURN UNIT COUNSELING ROOMS GRAPHICAL SCALE (METERS) 0 5 10 20 1 2 3 4 5 SECOND FLOOR ZONAL PLAN SCALE 1:1000M 250-BED HOSPITAL 24


E E EE ROOM ELEVATOR LOBBY DN UP DN DN UP UP UP DN RAMP DN RAMP UP MEDICINE WARD PEDIATRIC WARD RAMP DN E E EE ROOM ELEVATOR LOBBY DN DN DN DN SOLARIUM PRIVATE ROOMS PRIVATE ROOMS SOLARIUM GRAPHICAL SCALE (METERS) 0 5 10 20 1 2 3 4 5 GRAPHICAL SCALE (METERS) 0 5 10 20 1 2 3 4 5 FOURTH FLOOR ZONAL PLAN SCALE 1:1000M THIRD FLOOR ZONAL PLAN SCALE 1:1000M 250-BED HOSPITAL 250-BED HOSPITAL 25


AERIAL PERSPECTIVE 250-BED HOSPITAL 26


250-BED HOSPITAL MAIN ENTRANCE PERSPECTIVE 250-BED HOSPITAL SITE ENTRANCE PERSPECTIVE 27


MANUAL on TECHNICAL GUIDELINES for HOSPITAL PLANNING and DESIGN 250-BED HOSPITAL
(LEVEL 3)

VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

First Edition DEPARTMENT OF HEALTH Manila 2017


VOLUME 3 DEPARTMENTAL PLANS and TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

TABLE OF CONTENTS

PAGE 3.1 ADMINISTRATIVE SERVICE FACILITIES

3.2 EMERGENCY SERVICE FACILITIES

3.3 OUTPATIENT SERVICE FACILITIES

3.3.1 OUTPATIENT CLINICS

3.3.2 AMBULATORY SURGERY CLINIC

3.3.3 PHYSICAL REHABILITATION

3.3.4 DIALYSIS

3.4 ANCILLARY SERVICE FACILITIES

3.4.1 PHARMACY

3.4.2 LABORATORY

3.4.3 BLOOD STATION

3.4.4 RADIOLOGY

3.5 NURSING SERVICE FACILITIES

3.7 OPERATING ROOM & ICU SERVICE FACILITIES

3.7.1 OR & ICU

3.7.2 CSSR

3.8 DELIVERY and NICU SERVICE FACILITIES

3.9 NUTRITION and DIETETICS SERVICE FACILITIES

3.10 ENGINEERING, MAINTENANCE and HOUSEKEEPING FACILITIES

3.11 SUPPORT SERVICE FACILITIES

3.10.1 LINEN and LAUNDRY

3.10.2 PROPERTY and SUPPLY

3.10.3 MORGUE

3.10.4 CENTRAL WASTE STORAGE

3.6 BURN UNIT SERVICE FACILITIES 31 33 131 195 199 249 279 292 315 319 344 396 418 473 499 513 516 590 603 675 731 781 784 803 819 829


VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.1 ADMINISTRATIVE SERVICE FACILITIES

First Edition DEPARTMENT OF HEALTH Manila 2017 33


Hospital: 250-Bed (Level 3) Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER ADMINISTRATIVE 1,086.00 ADMINISTRATIVE (FRONTLINE) 422.00 250B-AD-DDS-01A Main Lobby 180.00 250B-AD-RDS-01 Info/ Reception & Communication Area
250B-AD-RDS-02 Admitting Office 27.00 250B-AD-RDS-03 Billing & Claims Office 36.00 250B-AD-RDS-04 Cashier's Office 250B-AD-RDS-05 Medical Social Work Office 43.00 250B-AD-RDS-06 Public/ PWD Toilets 45.00 250B-AD-RDS-07 Staff Toilets 36.00 250B-AD-RDS-08 ADMINISTRATIVE (EXECUTIVE) 664.00 250B-AD-DDS-01B Budget & Accounting Offices/ 108.00 250B-AD-RDS-09 Finance Manager's Office Office of the Chief of Hospital 250B-AD-RDS-10 IHOMP (Integrated Hospital Operations 36.00 250B-AD-RDS-11 & Management Program) Conference Room 22.00 250B-AD-RDS-12 Office of the Administrative Officer 30.00 250B-AD-RDS-13 Office of the Chief of Clinics 42.00 250B-AD-RDS-14 Human Resource Development Head 90.00 250B-AD-RDS-15 & Staff Offices Office of the Chief Nurse & Nursing Office 90.00 250B-AD-RDS-16 Auditing Office 36.00 250B-AD-RDS-17 Library 48.00 250B-AD-RDS-18 Staff Lounge 18.00 250B-AD-RDS-19 Public Toilets 36.00 250B-AD-RDS-20 18.00 250B-AD-RDS-21 24.00 250B-AD-RDS-22 Reference Sheet Number: ADMINISTRATIVE 250B-AD-SFSI-01 ROOM TITLE PAGE SERVICE FACILITY SHEET INDEX Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU Service Facility Title: Office (Typical) Procurement Department/ BAC Office

19.00 36.00 66.00 35 37 38 41 44 47 50 53 56 59 62 63 66 69 72 75 78 81 84 87 90 93 96 99 102


Hospital: 250-Bed (Level 3) Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER HEALTH INFORMATION MANAGEMENT 785.00 MANAGEMENT SYSTEMS Waiting Area 90.00 250B-HIMS-RDS-01 Staff Office and Releasing/Receiving 54.00 250B-HIMS-RDS-02 Completion Room 250B-HIMS-RDS-03 Head's Office 11.00 250B-HIMS-RDS-04 Admin Records 45.00 250B-HIMS-RDS-05 Records Room 250B-HIMS-RDS-06 Files Storage Area 486.00 250B-HIMS-RDS-07 Staff Pantry, Lockers and Toilets 36.00 250B-HIMS-RDS-08 Reference Sheet Number: ADMINISTRATIVE 250B-AD-SFSI-02 ROOM TITLE PAGE SERVICE FACILITY SHEET INDEX Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU Service Facility Title:

36

Ϯ 36.00 106 109 112 250B-HIMS-DDS-01 105 115 118 121 124 127 27.00


24000 WAITING AREA INFORMATION PABX ROOM CASHIER BILLING & CLAIMS ADMITTING OFFICE MEDICAL SOCIAL SERVICE FEMALE T MALE T TO OPD TO ER 3000 6000 3000 3000 6000 6000 6000 PHILHEALTH OFFICE PWD T JAN CLO WAITING AREA MALE STAFF T FEMALE STAFF T FEMALE STAFF LOCKERS MALE STAFF LOCKERS 3050 MAIN ENTRANCE 12000 15000 M A I N L O B B Y SCALE 1:300 M 9000 15000 12000 6000 36000 37


Department: Room Title: ADMINISTRATIVE MAIN LOBBY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Reception/ Waiting area for patients, relatives Glass board w/ directory 1 and visitors Waste bin w/ black or colorless 1 lining People Involved: Patients, Relatives and Visitors FURNITURE AND FIXTURE CHECKLIST 2- Seater Sofa 4 Center Table, 900mmX900mm 1 Side Table 400mmX400mm 4 Planning Relationships: a. Within the frontline service building ADDITIONAL EQUIPMENT & QUANTITY REMARKS ENGINEERING TERMINALS Window curtain rail 4 Outlet, 10A, 2P, 240V, duplex 8 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 emergency light Outlet, DATA 1 wall-mounted Outlet, Telephone 1 Smoke Detector 4 ROOM DATA SHEET 250B-AD-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: 38


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE MAIN LOBBY 250B-AD-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
150 Room temperature (°C) ambient Night illumination (LUX) 50 Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit general public Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 39 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:200 M 1 Table, center, 900 x 900mm 2 Table, side, 400 x 400mm 3 2-Seater sofa 4 Hospital directory 5 Waste bin 1 4 5 2 3 SD T D 2 2 2 3 3 3 3 SD SD SD 12000 15000 40


Department: Room Title: ADMINISTRATIVE INFORMATION/ RECEPTION & COMMUNICATIONS ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Receives queries from clients, patients and guests Computer w/ internet connection 1 b. Gives direction to hospital clients Waste bin w/ black or 2 colorless lining People Involved: FURNITURE AND 2 x Computer Operators FIXTURE CHECKLIST Patients and Guests Counter, 2-Level 1 Computer Table 1 Swivel Chair 5 Work Counter 1 File Cabinet 2 Communication System Console 2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Lobby Outlet, 10A, 2P, 240V, duplex 9 grounding type universal Outlet, 10A, 2P, 40V, single 1 emergency light Outlet, DATA 2 Outlet, Telephone 2 Smoke Detector 2 QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-AD-RDS-02A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 41


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE INFORMATION/ RECEPTION & COMMUNICATIONS ROOM 250B-AD-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit general public Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 42


KEY SCALE 1:100 M 1 INFORMATION 2 Counter, 2-level 3 Table, computer 4 Chair, swivel, with casters 5 Waste bin 2 3 4 1 6 PABX ROOM 7 Counter, work 8 Cabinet, file 9 Communication system console SD SD 4 4 4 4 5 5 6 7 8 8 9 9 CH CH T D CH CH D T 2100 4000 3000 43


Department: Room Title: ADMINISTRATIVE ADMITTING OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Admitting of patients Computer w/ internet connection 1 b. Conduct interviews with clients to determine service Printer 1 needed Waste bin w/ black or 3 c. Assignment of room/bed where patient is to be colorless lining admitted (private, pay medicare or service) d. Encoding of demographic data of inpatient records People Involved: FURNITURE AND 1 x Administrative Officer I FIXTURE CHECKLIST 4 x Computer Operator II Desk, 600mmX1200mm 1 Patients and Companion/s Desk extension, 400mmX900mm 4 Swivel Chair 3 Counter w/ low partitions 2 Cabinet, 500mmX700mm 3 Steel Filing Cabinet 6 Visitor's chair 6 Chair, gang-type 2 Wheelchair park 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Lobby Window curtain rail 4 Outlet, 10A, 2P, 240V, duplex 11 grounding type universal Outlet, 10A, 2P, 240V, single 2 emergency light Outlet, DATA 3 wall-mounted Outlet, Telephone 3 desktop Smoke Detector 2 Airconditioning Unit 1 split type 250B-AD-RDS-03A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 44


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE ADMITTING OFFICE 250B-AD-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit general public Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 45


3000 KEY SCALE 1:100 M 1 Counter, with low partition 2 Desk, 600 x 1200mm 3 Cabinet, 450 x 1200mm 4 Cabinet, filing, 500 x 700mm 5 Chair, swivel, with casters 1 SD T 5 2 6 Chair, visitor 7 Chair, gang-type 8 Waste bin 9 Wheelchair park 1 3 4 4 4 4 5 5 6 6 6 6 6 6 7 7 8 8 8 9 D T D T D SD 2000 7000 9000 46


Department: Room Title: ADMINISTRATIVE BILLING AND CLAIMS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Chief Billing Officer and Clerks read, write and use Computer 7 telephone in their work stations Printer 7 b. Chief Billing Officer and Clerks compute billing charges ACU 1 c. Chief Billing Officer and Clerks sort charge slips, store Telephone 3 file and retrieve billing records Waste bin w/ black or 2 colorless lining People Involved: FURNITURE AND 1 x Chief Billing Officer FIXTURE CHECKLIST 6 x Clerks Transaction counter 1 w/ glass panel Desk, 750mmX1200mm 1 Desk, 600mmX1200mm 6 Swivel Chair 7 Desk extension, 400mmX900mm 7 Steel Filing Cabinet 5 Visitor's chair 2 Stool, adjustable height 2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Accessible to the Office of the Administrative Officer b. Accessible to Business and Accounting Office Outlet, 10A, 2P, 240V, duplex 13 grounding type universal Outlet, 10A, 2P, 240V, single 1 emergency light Outlet, DATA 7 wall-mounted Outlet, Telephone 3 desktop Smoke Detector 1 QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-AD-RDS-04A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 47


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE BILLING AND CLAIMS 250B-AD-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering ESSENTIAL:desirable:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit PhilHealth staff/ patient/ visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 48


KEY SCALE 1:100 M 1 Counter, transaction, with glass front panel 2 Desk, 750 x 1200mm 3 Desk, 600 x 1200mm 4 Desk, extension, 400 x 900mm 5 Cabinet, filing, 500 x 700mm 6 Chair, swivel, with casters 7 Chair, visitor 8 Stool, adjustable height 9 Waste bin 10 Waiting area SD 1 3 2 4 6 8 8 9 9 D 3 4 6 3 4 6 9 9 4 6 7 7 9 3 6 3 6 3 6 4 4 4 5 5 5 5 5 10 D D T D T D D D T CH CH 6000 6000 49


Department: Room Title: ADMINISTRATIVE CASHIER'S OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Prepares checks and statement of collection Computer 7 and disbursement Printer 3 b. Maintains record of collection and deposit CCTV 2 if funds are available c. Collects payments Check Writer 1 d. Issues check to suppliers and other claimants Money Verifier (Scanner) 1 e. Prepares Monthly Report of Collection and Deposit Typewriter 1 and other Reports Waste bin w/ black or 4 colorless lining People Involved: FURNITURE AND 1 x Chief Cashier Officer FIXTURE CHECKLIST 4 x Collecting and Disbursement Clerks Desk, 600mmX1200mm 4 Swivel Chair 4 Desk extension, 300mmX500mm 3 Desk extension, 400mmX900mm 4 Transaction Counter 1 w/ glass panel Cork/ White board 1 Safe/ Cash box 1 Stool, adjustable height 3 Filing cabinet 2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Billing and PhilHealth Section b. Adjacent to Medical Social Worker Outlet, 10A, 2P, 240V, duplex 14 grounding type universal Outlet, 10A, 2P, 240V, single 2 emergency light Outlet, DATA 5 wall-mounted Outlet, Telephone 1 desktop Smoke Detector 2 QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-AD-RDS-05A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 50


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE CASHIER'S OFFICE 250B-AD-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Chief Cashier, Clerks Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 51


KEY SCALE 1:100 M 5 1 Counter, transaction, with glass front panel 2 Desk, 600 x 1200mm 3 Desk, extension, 400 x 900mm 4 Desk, extension, 300 x 500mm 5 Cabinet, filing, 500 x 700mm 6 Vault 7 Safe/cash box 8 Chair, swivel, with casters 9 Stool, adjustable height 10 Waste bin T D 1 2 2 2 2 3 4 4 4 3 3 3 5 6 8 8 8 8 7 9 9 9 10 10 10 10 D D D D SD SD CH CH CH 2900 3100 6000 2100 3900 6000 52


Department: Room Title: ADMINISTRATIVE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. MSW conducts psychosocial assessment to determine Computer W/ internet 6 financial capacity of patient to defray expenses and Telefax 1 diagnose psychosocial condition as it interacts with Queuing System 1 physical condition and treatment. This involves Copying machine 1 interviewing the patient, family and significant others. Safety Alarm 1 b. MSW has referral system and maintains coordination Local Telephone 6 with medical team, other stakeholders, patient, Waste bin w/ black or 2 family and significant others colorless lining c. MSW provides case management and therapeutic services that includes pre-admission and discharge planning group therapy d. MSW documents, maintains reports, conducts research and studies. e. Clerk receives visitors, requests communication, documents and maintains reports and filing system f. MSW validates PhilHealth membership and NHTS listing FURNITURE AND of indigent patients from computer program provided FIXTURE CHECKLIST g. Provide supervisory service for both administrative and Desk 600mmX1200mm 6 room should be clinical services of the MSWD staff Upright chair 6 sound proof to h. Attend to the reference patients with special needs such Visitor's Chair 7 afford privacy as pay patients requesting for transfer to service ward Steel filing cabinet 1 but with glass or political reference Cabinet 1 windows for security i. Conducts resource development and networking Chair, gang-type 2 purpose and with j. Develop plans and policies for the unit emergency buzzer People Involved: 1 x Head Medical Social Worker 5 x Clerks Patient, family and significant others Medical team NGO's, GO's, other stakeholders ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Admitting Office Window curtain rail 5 b. Accessible to Emergency Room and Outpatient Dept. Outlet, 10A, 2P, 240V, duplex 12 grounding type c. Accessible to the Office of the Administrative Officer universal d. Close to Business and Finance Office Outlet, 10A, 2P, 240V, single 3 emergency light Outlet, DATA 6 wall-mounted Outlet, Telephone 6 desktop Smoke Detector 4 250B-AD-RDS-06A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 53 MEDICAL SOCIAL WORK OFFICE


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE MEDICAL SOCIAL WORK OFFICE 250B-AD-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Medical Social Service Staff, patients & visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 54


KEY SCALE 1:200 M 1 Desk, 600 x 1200mm 2 Cabinet, steel, filing 3 Chair, upright 4 Chair, visitor 5 Chair, gang-type 6 Cabinet 7 Waste bin SD SD SD 1 2 3 4 5 5 7 7 1 3 4 1 3 4 1 3 4 1 3 4 1 3 4 4 6 D T D T D T D T D T D T SD 3000 2000 2000 2000 2000 2000 2000 3000 15000 55


Department: Room Title: ADMINISTRATIVE PUBLIC/ PWD TOILETS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Hospital patients, relatives and visitors make use of Exhaust Fan 3 public/PWD toilet facilities Waste bin w/ black or 3 b. Janitorial services do clean-up activities colorless lining People Involved: FURNITURE AND Patients, relatives and visitors FIXTURE CHECKLIST Water closet w/ spray hose 10 Lavatory 7 Urinal 4 Slop Sink 1 Shelf, open 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to the Main Lobby Outlet, 10A, 2P, 240V, single 1 emergency light QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-AD-RDS-07A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 56


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE PUBLIC/ PWD TOILETS 250B-AD-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) 50 Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 85 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) required Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privac ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit: Visitors/Patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 57


KEY SCALE 1:150 M 1 FEMALE TOILET 2 MALE TOILET 3 Waste bin 4 PWD TOILET 5 JANITOR'S CLOSET 6 Slop sink, with faucet 7 Shelf, open 1 2 3 3 3 4 6 5 7 2200 3000 6000 3000 3000 58


Department: Room Title: ADMINISTRATIVE STAFF TOILETS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Hospital administrative staff make use of personnel Exhaust Fan 2 toilet facilities Waste bin w/ black or 4 b. Janitorial services do clean-up activities colorless lining People Involved: FURNITURE AND Male and Female Employees FIXTURE CHECKLIST Water closet w/ spray hose 4 Lavatory 4 Urinal 2 Steel Lockers, 300 x 500mm
18 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Billing and Claims Office Outlet, 10A, 2P, 240V, duplex 4 Outlet, 10A, 2P, 240V, single 2 emergency light Smoke Detector 2 250B-AD-RDS-08A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 59


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE STAFF TOILETS 250B-AD-RDS-08B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) 50 Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 85 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) applicable Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit:
Administrative Staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 60


KEY SCALE 1:150 M 1 MALE TOILET 2 FEMALE TOILET 3 Waste bin 3000 3000 3000 1 2 3 3000 3000 4 LOCKER ROOM (MALE & FEMALE) 5 Locker, steel, 300 x 500mm SD SD 3 3 3 4 5 4 5 12000 61


3000 A U D I T O R I U M 3000 3000 4100 1900 9000 ELECTRICAL ROOM MALE PUBLIC TOILET CHIEF NURSE OFFICE PANTRY NURSING SERVICES OFFICE PROCUREMENT DEPT. / BAC OFFICE INFECTION CONTROL LIBRARY COA OFFICE LEGAL OFFICE AO OFFICE OPET CPMT OFFICE SEC CHIEF OF CLINICS OFFICE 5502 4100 3000 4000 3000 4000 6000 3000 6000 6000 3000 6000 5100 3000 3500 LOUNGE O P E N B E L O W O P E N B E L O W ROOF GARDEN FINANCE MANAGER'S OFFICE PANTRY BUDGET & ACCOUNTING DEPARTMENT BUDGET & ACCOUNTING HEADS' OFFICE CONFERENCE ROOM INT. HOSPITAL OPERATIONS & MGT. PROGRAM SECRETARY PANTRY CHIEF OF HOSPITAL HRD HEAD'S OFFICE PANTRY HRD STAFF OFFICE PUBLIC HEALTH OFFICE FEMALE STAFF TOILET MALE STAFF TOILET FEMALE PUBLIC TOILET SCALE 1:300 M 1600 45000 19400 45000 1900 1900 62


Department: Room Title: ADMINISTRATIVE BUDGET AND ACCOUNTING/ FINANCE MANAGER'S OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Processes funding & payments of vouchers, payroll, Computer 13 contract and other financial transactions of the hospital Printer with scanner 1 b. Maintains and ensures that the financial transaction Printer for payroll 1 is in accordance with the generally accepted Tape recorder 1 accounting and auditing rules and regulations Waste bin w/ black or 9 c. Prepares and submits accurate and timely financial colorless lining statements and reports d. Maintains book of accounts, equipment and supplies, and accounts receivables e. Provides periodic financial analysis FURNITURE AND FIXTURE CHECKLIST Transaction counter 1 Desk, 750mmX1200mm 3 Desk, 600mmX1200mm 10 Desk Extensions, 400mmX900mm 3 People Involved: Counter w/ cabinets above & below 1 Chief Accountant Sink, stainless steel 1 Chief Budget Officer Steel filing cabinet 20 Bookkeeper Stool, adjustable height 1 Budget Clerk Visitor's chair 5 Accounting Clerk Junior Executive chair 3 Swivel chair 10 Chair, gang-type 1 2-Seater Sofa 3 Water closet 1 Urinal 1 Lavatory 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Office of the Chief of Hospital Window curtain rail 1 b. Close to Office of the Administrative Officer Outlet, 10A,2P,240V, duplex 28 grounding type universal Outlet, 10A, 2P, 240V, single 2 emergency light Outlet, DATA 13 Outlet, Telephone 6 Smoke Detector 6 QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 250B-AD-RDS-09A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 63


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE BUDGET AND ACCOUNTING/ FINANCE MANAGER'S OFFICE 250B-AD-RDS-09B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Accounting & Administrative staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 64


6000 5500 KEY SCALE 1:200 M 1 Counter, transaction 2 Desk, 750 x 1200mm 3 Desk, 600 x 1200mm 4 Desk, extension, 400 x 900mm 5 Counter, with cabinets above and below 6 Sink, stainless steel 7 Cabinet, filing, 500 x 700mm 8 Chair, junior executive 9 Chair, swivel, with casters 10 Chair, visitor 11 Chair, gang-type 12 Stool, adjustable height 13 Sofa, 2-seater 14 Waste bin 4100 3500 1900 3000 1 2 3 9 7 14 11 12 7 7 14 4 5 CH 6 8 7 7 7 7 7 7 10 10 13 2 2 10 8 4 10 8 4 13 13 14 14 14 14 13 3 9 7 3 9 7 3 9 7 14 3 9 3 9 7 3 9 7 3 9 7 3 9 7 3 9 10 7 7 7 14 14 SD SD SD SD SD SD D D D T D D D D D D 7 T T D T D T D T D 18000 65


Department: Room Title: ADMINISTRATIVE OFFICE OF THE CHIEF OF HOSPITAL FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Chief of Hospital reads, writes and uses telephone in Computer and printer 2 his desk Fax Machine 1 b. Chief of Hospital receives visitors Telephone 1 c. Chief of Hospital stores, files and retrieves records Intercom/ PABX 1 d. COH's secretary reads, writes and uses telephone in Waste bin w/ black or 3 non-biodegradable her desk colorless lining e. COH's secretary receives visitors Waste bin w/ green lining 1 biodegradable f. COH's secretary stores, files and retrieves records g. Use of toilet facilities FURNITURE AND FIXTURE CHECKLIST Executive desk, 900mmX1800mm 1 Desk extension, 400mmX1200mm 1 Desk, 600mmX1200mm 1 Desk extension, 400mmX900mm 1 Executive chair 1 People Involved: Swivel chair 1 1 x Chief of Hospital Visitor's chair 6 1 x Secretary Sofa, two-seater 2 2 x Visitors Side table, 400mmX400mm 3 Cabinet, 400mmX800mm 1 Conference table 1 Conference chair 5 Counter, w/ cabinets above & below 1 Sink, stainless steel 1 Steel filing cabinet 4 Water closet 1 Urinal 1 Lavatory 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to the Office of the Administrative Officer Window curtain rail 4 b. Close to Conference Room Outlet, 10A,2P,240V, duplex 13 grounding type c. Close to Business and Accounting universal Outlet, 10A, 2P, 240V, single 3 emergency light Outlet, DATA 2 wall-mounted Outlet, Telephone 2 desktop Smoke Detector 4 Airconditioning Unit 1 window/ split type Water heater, 6kw 1 QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 250B-AD-RDS-10A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 66


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE OFFICE OF THE CHIEF OF HOSPITAL 250B-AD-RDS-10B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 3.6 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit COH, Hospital & Visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 67


KEY SCALE 1:150 M 6000 3000 2000 11000 2100 1 Desk, executive, 900 x 1800mm 2 Desk, extension, 400 x 1200mm 3 Desk, 600 x 1200mm 4 Desk, extension, 400 x 900mm 5 Chair, executive 6 Chair, swivel, with casters 7 Chair, visitor 8 Sofa, two-seater 9 Table, side, 400 x 400mm 10 Table, conference 11 Chair, conference 12 Cabinet, 400 x 1800mm 13 Cabinet, filing 500 x 700mm 14 Counter, with cabinets above and below 15 Sink, stainless steel 16 Waste bin 6000 2200 1700 T D 3 4 1 5 2 6 7 7 7 7 7 7 8 8 9 9 9 10 11 11 11 11 11 12 13 13 13 13 14 15 16 16 16 SD SD SD SD T D CH 68


Department: Room Title: ADMINISTRATIVE INTEGRATED HOSPITAL OPERATIONS & MANAGEMENT PROGRAM (IHOMP) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. System Administrator prepares program, enhances system,Database Server 2 builds libraries of diseases, drugs and medicines Computers 2 hospital staff, personnel directories of doctors and UPS (Uninterrupted Power Supply) 3 specialists AVR (Automatic Voltage Regulator) 2 Printers 1 Airconditioning Unit 1 hp stand-by ACU Electric fan 1 Hub 1 Waste bin w/ black or 3 colorless lining FURNITURE AND FIXTURE CHECKLIST Desk, 600mmX1200mm 5 People Involved: Desk Extensions, 400mmX900mm 5 Information Technologist Clerical Chair 5 Computer Engineer Visitor's Chair 2 Systems Administrator Cabinet 450mmX1500mm 2 Server Cabinet, 1000mmX1000mm 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Near or adjacent to the Chief of Hospital's Office Window curtain rail 2 b. Close to other Executive Offices (Administrative Service) Outlet, 10A,2P,240V, duplex 10 grounding type universal Outlet, 10A, 2P, 240V, single 1 emergency light Outlet, DATA 1 wall-mounted Outlet, Telephone 1 desktop Smoke Detector 1 Airconditioning Unit 1 window/ split type QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 250B-AD-RDS-11A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 69


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE IHOMP 250B-AD-RDS-11B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.8 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Systems Administrator Maximum temperature (°C) NA Access limit IHOMP Staff/ Visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 70


KEY SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Desk extension, 400 x 900mm 3 Chair, clerical 4 Chair, visitor 6000 6000 SD 1 3 4 4 5 5 2 1 3 2 1 3 2 1 3 2 1 3 2 6 7 7 7 5 Cabinet, with shelves, 450 x 1500mm 6 Server, 1000 x 1000mm 7 Waste bin SD 1 3 4 4 5 5 2 1 3 2 1 3 2 1 3 2 1 3 2 6 7 7 7 T D 71


Department: Room Title: ADMINISTRATIVE CONFERENCE ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Hospital staff/ Hospital Services Personnel & Visitors White board 1 hold meetings and special lectures Glass board 1 LCD Screen 1 Opaque Projector 1 Microphone 1 Sound System 1 set Voice Recorder 1 Waste bin w/ black or 1 colorless lining People Involved: FURNITURE AND QUANTITY REMARKS Hospital Staff FIXTURE CHECKLIST Hospital Services Personnel Conference table, 500mmX1500mm 6 Visitors Cabinet, 400mmX1800mm 1 Conference chair 12 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to the Office of the Administrative Officer Outlet, 10A,2P,240V, duplex 6 grounding type b. Close to Office of the Chief of Hospital universal c. Close to Office of the Chief Nurse Outlet, 10A, 2P, 240V, single 1 emergency light d. Close to the Office of the Chief of Clinics Outlet, Laptop 1 floor type Smoke Detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 250B-AD-RDS-12A April 2016 72


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE CONFERENCE ROOM 250B-AD-RDS-12B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 70 Black out essential:desirable:UNNECESSARY Cooling load (TR) 5 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Hospital Staff, clients & visiotrs Fire risk low: medium:HIGH Other risks NA ROOM DATA SHEET 73


KEY SCALE 1:100 M 3600 6000 1 Table, conference, 500 x 1500mm 2 Cabinet, 400 x 1800mm 3 Chair, conference 4 Whiteboard 5 Waste bin 1 1 1 1 1 1 2 2 5 3 3 3 3 3 3 3 3 3 3 3 3 4 SD FO 74


Department: Room Title: ADMINISTRATIVE OFFICE OF THE ADMINISTRATIVE OFFICER FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Administrative Officer reads, writes and uses telephone in Computer and printer 1 his desk Printer w/ scanner 1 b. Administrative Officer receives visitors Calculating machine 1 c. Administrative Officer plans, directs, controls and Telephone 1 organizers workplace system Intercom/ PABX 1 d. Clerk acts as secretary, prepares plans and schedule Waste bin w/ black or 2 of CAO colorless lining e. Clerk stores, files and retrieves records Airconditioning unit 1 f. Clerk updates records Electric fan 1 g. Use toilet facilities FURNITURE AND FIXTURE CHECKLIST Desk, 750mmx1200mm 1 Desk extension, 400mmX1800mm 1 People Involved: Junior executive chair 1 1 x Hospital Administrative Officer Visitor's chair 2 1 x Clerk Sofa, two-seater 1 Visitor/s Steel filing cabinet 3 Cabinet, 400mmX1200mm 1 Counter w/ cabinets above & below 1 Sink, stainless steel 1 Water Closet 1 Urinal 1 Lavatory 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Budget and Accounting office Window curtain rail 2 b. Close to Office of the Chief of Hospital Outlet, 10A,2P,240V, duplex 8 grounding type c. Close to Human Resource Development & universal Property and Supply Outlet, 10A, 2P, 240V, single 1 emergency light Outlet, DATA 1 wall-mounted Outlet, Telephone 1 desktop Smoke Detector 2 Airconditioning Unit 1 window/ split type QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 250B-AD-RDS-13A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 75


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE OFFICE OF THE ADMINISTRATIVE OFFICER 250B-AD-RDS-13B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit Administrative Officer, Hospital staff and visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 76


KEY SCALE 1:100 M 1 AO OFFICE 2 Desk, 750 x 1200mm 3 Desk, extension, 400 x 1800mm 4 Chair, junior executive 5 Chair, visitor 6 Sofa, two-seater 7 Cabinet, filing, 500 x 700mm 8 Cabinet, with shelves, 400 x 1200mm 9 PANTRY 10 Counter, with cabinet above and below 11 Sink, stainless steel 12 Waste bin 13 TOILET 2 3 5 5 4 6 10 12 7 12 7 7 SD SD CH T D 3900 2100 6000 1 9 8 11 1900 3000 4900 77


Department: Room Title: ADMINISTRATIVE OFFICE OF THE CHIEF OF CLINICS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Chief of Clinics reads and writes in his work station Computer 2 b. Chief of Clinics receives visitors Printer w/ scanner 1 c. Chief of Clinics stores, files and retrieves records Airconditioning unit 1 d. Clerk receives visitors Telephone/ Intercom 1 e. Clerk stores, files and retrieves records Waste bin w/ black or 2 f. Clerk updates records colorless lining g. Use of toilet facilities FURNITURE AND FIXTURE CHECKLIST Desk, 900mmX1500mm 1 Desk, 600mmX1200mm 1 Desk extension, 400mmX900mm 1 Junior executive chair 1 Clerical chair 1 People Involved: Visitor's chair 4 1 x Chief of Clinics Single-seater sofa 1 1 x Clerk Two-seater sofa 2 Visitors Side table, 400mmX400mm 2 Cabinet, 400mmX900mm 1 Steel filing cabinet 3 Lavatory 1 Water Closet 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to the Office of the Chief of Hospital Window curtain rail 2 Outlet, 10A,2P,240V, duplex 11 grounding type universal Outlet, 10A, 2P, 240V, single 1 emergency light Outlet, DATA 2 Outlet, Telephone 2 Smoke Detector 2 250B-AD-RDS-14A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 78


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE OFFICE OF THE CHIEF OF CLINICS 250B-AD-RDS-14B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit COC, Hospital & Visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 79


1900 7000 KEY SCALE 1:100 M 1 Desk, 900 x 1500mm 2 Desk, 600 x 1200mm 3 Desk, extension, 400 x 900mm 4 Chair, junior executive 5 Chair, clerical 6 Chair, visitor 7 Sofa, single-seater 8 Sofa, two-seater 9 Table, side, 400 x 400mm 10 Cabinet, with shelves, 400 x 900mm 11 Cabinet, filing, 500 x 700mm 12 Waste bin 3000 2500 4100 6000 1500 SD SD 1 T D 2 4 5 6 6 6 6 3 8 8 7 9 9 10 11 11 11 12 12 T D 80


Department: Room Title: ADMINISTRATIVE HUMAN RESOURCE DEVELOPMENT OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Prepares comprehensive manpower development Computer 3 program from selection to separation Printer with scanner 1 b. Maintains and ensures the confidentiality of personnel Printer for payroll 1 records Telephone 1 c. Prepares payroll and other personnel records per Intercom/ PABX 1 employee Copier 1 d. Acts on personnel actions and transactions Waste bin w/ black or 4 e. Acts as secretary of the hospital training committee, PSB colorless lining and Accreditation committee FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST Transaction Counter 1 Desk, 750mmX1200mm 1 Desk, 600mmX1200mm 11 Desk Extensions, 400mmX900mm 1 Shelves, wall-mounted 1 People Involved: Steel filing cabinet 15 Personnel Officer Side table 1 10 x Administrative Clerks Visitor's chair 5 Applicants/ Employees Junior Executive chair 1 Swivel chair 11 Chair, Visitor 2 Chair, gang-type 1 2-Seater Sofa 1 Counter, w/ cabinets above & below 1 Sink, stainless steel 1 Stool, adjustable height 1 Water closet 1 Lavatory 1 Urinal 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Lobby within the Administrative Window curtain rail 1 Service Office Outlet, 10A,2P,240V, duplex 25 grounding type universal Outlet, 10A, 240V, single 2 emergency light Outlet, DATA 11 wall-mounted Outlet, Telephone 2 desktop Smoke Detector 5 Airconditioning Unit 1 window/ split type 250B-AD-RDS-15A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 81


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE HUMAN RESOURCE DEVELOPMENT OFFICE 250B-AD-RDS-15B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Personnel Staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 82


KEY SCALE 1:200 M 2100 3900 6000 3600 2400 T D 2 SD 4 14 7 8 10 13 15 7 7 10 1 SD 5 CH 7 7 15 11 15 3 9 7 D 9 3 3 9 7 T D 3 9 7 D 3 9 7 D 3 9 7 D 3 9 7 D 15 3 9 7 D T 3 9 7 D 3 9 D 3 9 D 15 15 7 7 12 1 Counter, transaction 2 Desk, 750 x 1200mm 3 Desk, 600 x 1200mm 4 Desk, extension, 400 x 900mm 5 Counter, with cabinets above and below 6 Sink, stainless steel 7 Cabinet, filing, 500 x 700mm 8 Chair, junior executive 9 Chair, swivel, with casters 10 Chair, visitor 11 Chair, gang-type 12 Stool, adjustable height 13 Sofa, 2-seater 14 Shelf, open 15 Waste bin SD SD SD SD 6 3000 1900 10100 15000 83


Department: Room Title: ADMINISTRATIVE OFFICE OF THE CHIEF NURSE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Chief Nurse reads, writes and uses telephone in his desk Computer 1 b. Chief Nurse receives visitors Calculating Machine 1 c. Chief Nurse stores, files and retrieves records Whiteboard/Glassboard 1 d. Clerk receives visitors Waste bin w/ black or 5 e. Clerk stores, files and retrieves records colorless lining f. Clerk updates records g. Use of toilet facilities FURNITURE AND FIXTURE CHECKLIST Desk, 750mmX1200mm 1 Desk, 600mmX1200mm 8 Desk Extensions, 400mmX900mm 1 Counter w/ cabinets above and below 1 Sink, Stainless steel 1 People Involved: Steel filing cabinet 11 1 x Chief Nurse Side table 1 8 x Clerks Visitor's chair 4 Visitors Junior Executive chair 1 Swivel chair 8 Cabinet, 300mmX900mm 1 2-Seater Sofa 1 Water Closet 1 Urinal 1 Lavatory 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to the Office of the Chief of Hospital Window curtain rail 5 Outlet, 10A,2P,240V, duplex 17 grounding type universal Outlet, 10A, 2P, 240V, single 2 emergency light Outlet, DATA 9 wall-mounted Outlet, Telephone 3 desktop Smoke Detector 4 Airconditioning Unit 1 Window/ Split type 250B-AD-RDS-16A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 84


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE OFFICE OF THE CHIEF NURSE 250B-AD-RDS-16B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.8 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit CN, Hospital & Visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 85


4100 1900 9000 15000 2100 3900 6000 KEY SCALE 1:200 M 1 Desk, 750 x 1200mm 2 Desk, 600 x 1200mm 3 Desk, extension, 400 x 900mm 4 Counter, with cabinets above and below 5 Sink, stainless steel 6 Table, side, 400 x 400mm 7 Cabinet, filing, 500 x 700mm 8 Cabinet, with shelves, 300 x 900mm 9 Chair, junior executive 10 Chair, swivel, with casters 11 Chair, visitor 12 Sofa, 2-seater 13 Waste bin SD SD SD SD 1 2 3 4 6 7 7 7 7 9 10 11 12 5 13 8 8 13 13 13 13 11 11 11 1111 1111 2 10 2 10 2 10 13 2 10 7 2 10 7 2 10 7 2 10 CH T D T D D7 D D 7 7 T D D D 7 D 13 86


Department: Room Title: ADMINISTRATIVE AUDITING OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Commission on Audit personnel reads, writes and Computer 5 uses telephone in his work Printer 1 b. Commision on Audit personnel receives visitors Calculating machine 1 c. Commission on Audit personnel stores, and retrieves Waste bin w/ black or 3 records colorless lining

People Involved: FURNITURE AND 1 x COA Auditor FIXTURE CHECKLIST 1 x Clerk Desk, 750mmX1200mm 1 10 x Visitors Desk, 600mmX1200mm 4 Desk Extensions, 400mmX900mm 2 Conference table 1 Steel filing cabinet 4 Chair, upright, stacking 5 Visitor's chair 5 Conference chair 6 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Budget and Accounting Office Window curtain rail 2 b. Close to Office of the Administrative Officer Outlet, 10A,2P,240V, duplex 12 grounding type universal Outlet, 10A, 2P, 240V, single 2 emergency light Outlet, DATA 5 Outlet, Telephone 2 Smoke Detector 3 250B-AD-RDS-17A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 87


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE AUDITING OFFICE 250B-AD-RDS-17B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.8 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit COA staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 88


SCALE 1:100 M 1 Desk, 750 x 1200mm 2 Desk, 600 x 1200mm 3 Desk extension, 400 x 900mm 4 Table, conference 5 Cabinet, steel, filing 2500 3500 2300 6000 3700 6000 6 Chair, upright, stacking 7 Chair, visitor 8 Chair, conference 9 Waste bin KEY 2 3 4 5 1 6 2 7 9 5 5 7 7 7 7 8 8 8 8 3 6 6 6 T D T D D D SD SD SD 8 8 2 6 D 2 5 89


Department: Room Title: ADMINISTRATIVE LIBRARY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Hospital staff and affiliates make use of the Computer 4 library and its amenities Printer 1

People Involved: FURNITURE AND QUANTITY REMARKS Hospital staff FIXTURE CHECKLIST Medical staff Counter 1 Affiliates Desk 2 Cart, book 1 Cart, for computer & printer 1 Shelf, for books 10 Rack, for magazines etc. 2 Chair, swivel 2 Chair, upright 4 Stool, adjustable 2 Study desk/carrel 4 Waste bin 3 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Near offices (not public) Outlet, 10A,2P,240V, duplex 12 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light 250B-AD-RDS-18A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 90


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE LIBRARY 250B-AD-RDS-18B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.5 - 3 SOUND SAFETY Acceptable sound level (db) 30 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit none Fire risk low: MEDIUM : high Other risks NA ROOM DATA SHEET 91


KEY SCALE 1:100 M 1 3 2 SD 1 Counter, 1000mm high 2 Desk, 600 x 1200mm 3 Cabinet, filing, 500 x 700mm 4 Shelf, 400 x 1600mm, open 5 Shelf, 300mm deep, overhead 6 Cart, book 7 Table, with computer and printer 8 Study desk/carrel 9 Periodical/magazine rack 10 Chair, swivel, with casters 11 Chair, upright, stacking 12 Stool, adjustable height 13 Waste bin 4 5 6 7 8 9 9 10 10 12 12 11 8 11 8 11 8 11 13 13 13 4 4 4 4 4 4 4 4 4 8000 6000 92


Department: Room Title: ADMINISTRATIVE STAFF LOUNGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Hospital Administrative Staff makes use of the pantry Refrigerator 1 b. Hospital Administrative Staff do clean-up activities Water Dispenser 1 Waste bin w/ black or 2 colorless lining People Involved: FURNITURE AND Male and Female Employees FIXTURE CHECKLIST Dining table, 6-seater 1 Dining chairs 6 Sofa, two-seater 1 Counter w/cabinets above & below 1 Sink, stainless steel 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Accessible to Administrative Offices Window curtain rail 1 Outlet, 10A, 2P, 240V, duplex 7 grounding type universal Outlet, 10A, 2P, 240V, single 1 emergency light Smoke Detector 1 250B-AD-RDS-19A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 93


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE STAFF LOUNGE 250B-AD-RDS-19B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit Administrative Staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 94


SCALE 1:100 M 1 Table, dining, 6-seater 2 Chair, dining 3 Sofa, two-seater 4 Counter, with cabinets above and below 5 Sink, stainless steel 6 Refrigerator 7 Water dispenser, hot and cold 8 Waste bin 9 Concealed floor drain KEY SD 1 2 4 5 3 6 8 7 9 2 2 2 2 2 CH 3000 6000 95


Department: Room Title: ADMINISTRATIVE PUBLIC TOILETS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Hospital patients, relatives and visitors make use of Exhaust Fan 2 public/PWD toilet facilities Waste bin w/ black or 2 b. Janitorial services do clean-up activities colorless lining People Involved: FURNITURE AND Patients, relatives and visitors FIXTURE CHECKLIST Water closet w/ spray hose 5 Lavatory 4 Urinal 2 Slop sink w/ faucet 2 Floor strainer 2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Accesible to all Administrative Offices Outlet, 10A, 240V, single 1 emergency light Smoke Detector 2 QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-AD-RDS-20A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 96


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ADMINISTRATIVE PUBLIC TOILETS 250B-AD-RDS-20B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 85 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit:
Visitors/ Patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 97


KEY SCALE 1:100 M 1 FEMALE TOILET 2 Slop sink 3 Waste bin 4 MALE TOILET 1 2 3 4 3 2 3000 3000 6000 98


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Hospital office workers read, write and use Computer 3-5 telephone and/or computer in their work stations Printer 2-3 b. Performance of clerical, filing and office work ACU 1 c. Use of office equipment Telephone 1-3 d. Office worker attends to visitor/client , patient Waste bin 2 with black lining and/or other hospital office worker/medical staff Note:

  1. provide other equipment and accessories necessary to

  2. number of equipment and accessories depend on requirement FURNITURE AND FIXTURE CHECKLIST Desk, 600 x 1200mm 5 Chair, swivel 5 Chair, visitor 2 Cabinet, steel, filing 2 People Involved: Note: 5 x Hospital office workers

  3. provide other furniture and fixture necessary to 2 x Visitors

  4. number of furniture and fixture depend on requirement

ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 7 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Outlet, data 7 Planning Relationships: Outlet, telephone 4

a. May be close to or adjacent to hospital area being Smoke detector 1 served Cubicle curtain rail 1 b. May be grouped with other administrative offices Note:

  1. provide additional equipment and engineering terminals
  2. number of additional equipment and engineering terminals
    depend on requirement and not necessarily 1:1 ratio per staff specific office type and not necessarily 1:1 ratio per staff specific office type and not necessarily 1:1 ratio per staff QUANTITY REMARKS Reference Sheet Number: QUANTITY REMARKS April 2016 250B-AD-RDS-21A QUANTITY REMARKS Updated Reference: Hospital: OFFICE (TYPICAL) 250-Bed (Level 3) necessary to specific office type ROOM DATA SHEET ADMINISTRATIVE Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 99

Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.75 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit office staff, patients, visitors Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET April 2016 250B-AD-RDS-21B ADMINISTRATIVE OFFICE (TYPICAL) 100


KEY 1 Desk, 600 x 1200mm 2 Cabinet, filing; 500 x 700mm 3 Chair, swivel; with casters 4 Chair, visitor 5 Waste bin 3000 6000 SD 1 2 3 4 5 5 4 1 1 1 1 3 3 3 3 2 D T D T D T D T D 101


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Procurement Department - Bids and Awards Computer 3-5 Committee (BAC) office workers read, write and use Printer 2-3 telephone and/or computer in their work stations ACU 1 b. Performance of clerical, filing and office work Telephone 1-3 c. Use of office equipment Waste bin 2 with black lining d. Office worker attends to bidder/visitor/client Note: and/or other hospital office worker/medical staff

  1. provide other equipment and accessories as required by

  2. number of equipment and accessories depend on requirement FURNITURE AND FIXTURE CHECKLIST Desk, 600 x 1200mm 5 Chair, swivel 5 Chair, visitor 2 Cabinet, steel, filing 2 People Involved: Note: 5 x BAC office workers

  3. provide other furniture and fixture as required by 5 x Visitors

  4. number of furniture and fixture depend on requirement

ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 7 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Outlet, data 7 Planning Relationships: Outlet, telephone 4

a. May be grouped with other administrative offices Smoke detector 1

Cubicle curtain rail 1 Note:

  1. provide additional equipment and engineering terminals
  2. number of additional equipment and engineering terminals
    depend on requirement and not necessarily 1:1 ratio per staff BAC end-user and not necessarily 1:1 ratio per staff BAC end-user and not necessarily 1:1 ratio per staff QUANTITY REMARKS Reference Sheet Number: QUANTITY REMARKS April 2016 250B-AD-RDS-22A QUANTITY REMARKS Updated Reference: Hospital: BAC OFFICE 250-Bed (Level 3) as required by BAC end-user ROOM DATA SHEET ADMINISTRATIVE Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 102

Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.75 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit office staff, visitors Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET April 2016 250B-AD-RDS-22B ADMINISTRATIVE BAC OFFICE 103


KEY 1 Counter, transaction, with glass front panel 2 Desk, 600 x 1200mm 3 Cabinet, filing; 500 x 700mm 4 Chair, swivel; with casters 5 Chair, 5-seater gang style 6 Stool, adjustable height 4000 6000 2 1 SD SD 4 5 6 3 3 7 7 9 8 2 2 2 4 4 4 4 7 Waste bin 8 Door, glass; with full windows 9 Window, glass 10 Waiting area 10 D D T D T D 2 D 104


DN UP STAFF OFFICE COMPLETION ROOM RECEIVING/ RELEASING SCALE 1:300 M HEAD'S OFFICE WAITING AREA STAFF PANTRY LOCKERS JAN CLO FT MT DUMB WAITER ADMIN RECORDS 6000 3000 3800 3000 2300 3700 4900 4100 6000 6000 21000 15800 2100 4400 2500 F I L E S S T O R A G E

A R E A RECORDS ROOM DUMB WAITER 15000 36000 6000 3000 27000 15000 6000 9000 105


Department: Room Title: HEALTH INFORMATION MANAGEMENT SYSTEMS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Visitors wait for receiving and issuance of medical/ Emergency light 1 medico-legal certificates, birth and death certificates Queuing numbering system 1

Waste bin - black or colorless 1

lining

FURNITURE AND FIXTURE CHECKLIST

Chair, gang-type, waiting 3 4-seater People Involved: 3 5-seater Client / Visitor 3 7-seater

Planning Relationships:

a. Adjacent to Administrative Department b. Accessible to Out Patient Department ADDITIONAL EQUIPMENT & c. Accessible to Receiving/Releasing Area ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 2

Hospital: 250-Bed (Level 3) REMARKS ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY WAITING AREA April 2016 250B-HIMS-RDS-01A REMARKS QUANTITY Reference Sheet Number: QUANTITY REMARKS QUANTITY Updated Reference: 106


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: HEALTH INFORMATION MANAGEMENT SYSTEMS TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 25 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 70 Black out essential:desirable:UNNECESSARY Cooling load (TR) 5 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit HIMS staff, clients, and visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 250-HIMS-RDS-01B WAITING AREA Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary 107


KEY SCALE 1: 200 M 1 Chair, gang-type, 4-seater 2 Chair, gang-type, 5-seater 3 Chair, gang-type, 7-seater 2 2 2 1 1 1 3 3 3 15000 6000 SD SD 108


Department: Room Title: HEALTH INFORMATION STAFF OFFICE & MANAGEMENT SYSTEMS RELEASING/ RECEIVING FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. HIMS staff and other authorized users conduct Computer 1 w/ printer & scanner medical studies, read, write, and retrieve Calculator 1 records Photocopier machine 1 b. Processing and filing of OPD, ER, and OR records Risograph machine 1 c. Transcription of birth and death certificates Emergency light 1 d. HIMS staff assemble/input inpatient charts Facsimile machine 1 and updated death registry UPS and AVR 1 e. Receiving and issuance of medical/medico- Waste bin - black or colorless 1 legal certificates, birth and death certificates lining

PA & BGM system 1 Airconditioning unit 1 window/split type LCD

optional

Electric typewriter 1 People Involved: Paper shredder 1 1 x Statistician 1 x Data Controller 2 x HIMS Clerks FURNITURE AND Researchers / Doctors FIXTURE CHECKLIST Desk, 600 x 1200mm 12 Chair, clerical 12 Counter, transaction 1 Cabinet, steel, filing 5 Stool, adjustable 3

Planning Relationships: ADDITIONAL EQUIPMENT & REMARKS a. Accessible to Filing Area ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 15 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, telephone outlet 1 Smoke detector 1 Outlet, airconditioning unit
window/split type Window curtain rail 1 Hospital: 250-Bed (Level 3) April 2016 250B-HIMS-RDS-02A Reference Sheet Number: QUANTITY REMARKS Updated Reference: ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY QUANTITY QUANTITY REMARKS 109


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: HEALTH INFORMATION STAFF OFFICE & MANAGEMENT SYSTEMS RELEASING/ RECEIVING TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 70 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit researchers/doctors, HIMS staff Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET April 2016 250-HIMS-RDS-02B 110 Negative Pressure (Pa) NA
Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:150 M 1 Counter, transaction 2 Desk, 600 x 1200mm 3 Chair, clerical 4 Stool, adjustable 5 Cabinet, filing, 500 x 700mm T 2 3 2 3 2 3 2 3 4 1 6 7 5 5 5 5 5 6 Photocopier machine 7 Risograph machine 8 Paper shredder 9 Waste bin 8 9 2 3 2 3 2 3 2 3 2 3 2 3 2 3 2 3 4 4 6000 9000 SD SD CH CH FO FO FO FO FO FO FO FO 111


Department: Room Title: HEALTH INFORMATION MANAGEMENT SYSTEMS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Researchers / Doctors and other authorized users Computer 1 w/ printer & scanner discuss and finalize pertinent papers/documents Whiteboard, 1200 x 2400mm 1 related to medical records as requested by Airconditioning unit 1 window type patients/relatives Waste bin - black or colorless 1 b. HIMS officer assists researchers/doctors by lining

providing data on specific research topics

c. Researchers/Doctors protect confidentiality of

medical records

People Involved: FURNITURE AND 1 x HIMS Officer (Administrative Officer V) FIXTURE CHECKLIST 1 x Clinical Coder (Administrative Officer IV) Table, conference 1 Researchers / Doctors Chair, conference 6 Counter, 900mm high 2

w/ shelves below

Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Staff Office ENGINEERING TERMINALS

Outlet, 10A,2P,240V, duplex 6 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, telephone outlet 1 Outlet, data 1 Smoke detector 1 Outlet, airconditioning unit 1 window/split type Window curtain rail 2 QUANTITY REMARKS QUANTITY REMARKS Hospital: 250-Bed (Level 3) April 2016 250B-HIMS-RDS-03A Reference Sheet Number: QUANTITY REMARKS Updated Reference: COMPLETION AREA ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 112


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: HEALTH INFORMATION MANAGEMENT SYSTEMS TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.6 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit researchers/doctors, medical records staff & authorized users Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET April 2016 250-HIMS-RDS-03B COMPLETION AREA 113 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 1 Table, conference 2 Chair, conference 3 Counter, 900mm high, with shelves below 4 White board, 1200 x 2400mm 5 Waste bin SD 1 T D CH 2 2 2 2 2 2 3 3 4 5 4100 4400 114


Department: Room Title: HEALTH INFORMATION MANAGEMENT SYSTEMS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Health Information Management (HIM) Officer reads, Computer 1 w/ printer & scanner transcribes, and updates disease and operation Calculating machine 1 coding and indexing Airconditioning unit 1 window type b. HIM Officer prepares communications and other Telephone 1 pertinent papers related to medical records as Intercom 1 requested by patients Whiteboard 1 c. HIM Officer protects confidentiality of medical records Waste bin - black or colorless 1 d. HIM Officer performs statistical and other reports lining

required by DOH and other institutions

e. HIM Officer performs qualitative and quantitative

analysis of hospital health records

FURNITURE AND People Involved: FIXTURE CHECKLIST 1 x HIMS Officer (Administrative Officer V) Desk, 750 x 1200mm 1 Researchers Desk extension, 400 x 850mm 1 Clients/Visitors Cabinet, filing, 500 x 700mm 2

Chair, junior executive 1 Chair, visitor 2 Sofa, two-seater 1

Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Staff Office ENGINEERING TERMINALS b. Accessible to Receiving/Releasing Area Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, telephone outlet 1 Outlet, data 1 Smoke detector 1 Outlet, airconditioning unit 1 window/split type Window curtain rail 1 Hospital: 250-Bed (Level 3) April 2016 250B-HIMS-RDS-04A Reference Sheet Number: QUANTITY REMARKS Updated Reference: HEAD'S OFFICE ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY QUANTITY REMARKS QUANTITY REMARKS 115


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: HEALTH INFORMATION MANAGEMENT SYSTEMS TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.6 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical records staff & authorized users Fire risk low: medium: HIGH Other risks possible termite infestation ROOM DATA SHEET April 2016 250-HIMS-RDS-04B HEAD'S OFFICE 116 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 1 1 Desk, 750 x 1200mm 2 Desk, extension, 400 x 850mm 3 Cabinet, filing, 500 x 700mm 4 Chair, junior executive 5 Chair, visitor 6 Sofa, two-seater 7 White board 8 Waste bin T D 4100 2500 2 3 3 6 4 5 8 7 SD 117


Department: Room Title: HEALTH INFORMATION MANAGEMENT SYSTEMS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. HIMS staff stores/files administative records Calculator 1

for easy access PA & BGM system 1 b. HIMS staff retrieves records on file Exhaust fan 2

FURNITURE AND

FIXTURE CHECKLIST People Involved: Shelving, steel, open 8 HIMS staff Cabinet, with shelves 2 Researchers / Doctors Ladder, aluminum or wooden 1

Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Staff Office ENGINEERING TERMINALS

Outlet, 10A,2P,240V, duplex 6 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 2 Water sprinkler system

Window curtain rail 3

Hospital: 250-Bed (Level 3) April 2016 250B-HIMS-RDS-05A Reference Sheet Number: QUANTITY REMARKS Updated Reference: ADMIN RECORDS ROOM DATA SHEET QUANTITY REMARKS QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 118


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: HEALTH INFORMATION MANAGEMENT SYSTEMS TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit authorized HIMS staff Fire risk low: medium: HIGH Other risks possible termite infestation ROOM DATA SHEET April 2016 250-HIMS-RDS-05B ADMIN RECORDS 119 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa)
NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:150 M 1 Shelving, steel, open 2 Cabinet, with shelves 3 Ladder, movable Note : provide 1000mm clear distance from

ceiling to topmost shelf SD 4900 13500 1 1 1 1 1 1 1 1 SD 2 3 2 120


Department: Room Title: HEALTH INFORMATION MANAGEMENT SYSTEMS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. HIMS staff stores/files OPD, ER, and OR/DR records, Calculator 1

birth and death certificates for easy access PA & BGM system 1 b. HIMS staff retrieves records on file for request/ Exhaust fan 2 follow-up of patients/relatives and researchers/ doctors and refiles them c. HIMS staff records individual charts by patient's data for complete inventory control FURNITURE AND

FIXTURE CHECKLIST People Involved: Shelving, steel, open 4 HIMS staff Cabinet, with shelves 2 Researchers / Doctors Ladder, aluminum or wooden 1

Planning Relationships: ADDITIONAL EQUIPMENT & a. Accessible to Staff Office ENGINEERING TERMINALS

Outlet, 10A,2P,240V, duplex 8 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1 Water sprinkler system

Window curtain rail 1

QUANTITY REMARKS QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 250B-HIMS-RDS-06A Reference Sheet Number: QUANTITY REMARKS Updated Reference: RECORDS ROOM ROOM DATA SHEET 121


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: HEALTH INFORMATION MANAGEMENT SYSTEMS TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit authorized HIMS staff Fire risk low: medium: HIGH Other risks possible termite infestation ROOM DATA SHEET April 2016 250-HIMS-RDS-06B RECORDS ROOM 122 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa)
NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 1 Shelving, steel, open 2 Cabinet, with shelves 3 Ladder, movable Note : provide 1000mm clear distance from

ceiling to topmost shelf 6000 6000 SD 1 1 1 1 2 2 3 123


Department: Room Title: HEALTH INFORMATION MANAGEMENT SYSTEMS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of inactive files that have passed the

ten- to thirty-year filing period PA & BGM system 1 b. Storage of files to ensure protection from fire, Exhaust fan 3 flood and theft c. Periodic evaluation of inactive health records/files d. To keep medical records accessible as many years as possible FURNITURE AND

FIXTURE CHECKLIST People Involved: Shelving, steel, open 102 HIMS staff Ladder, aluminum or wooden 5

Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to HIMS Department ENGINEERING TERMINALS

Outlet, 10A,2P,240V, duplex 14 grounding type,

universal slots Outlet, 10A,2P,240V, single 3 emergency light Smoke detector 7 Water sprinkler system

QUANTITY REMARKS QUANTITY REMARKS Updated Reference: FILES STORAGE AREA QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 250B-HIMS-RDS-07A Reference Sheet Number: ROOM DATA SHEET 124


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: HEALTH INFORMATION MANAGEMENT SYSTEMS TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit authorized HIMS staff Fire risk low: medium: HIGH Other risks possible rodents and termite

infestation; moisture ROOM DATA SHEET April 2016 250-HIMS-RDS-07B FILES STORAGE AREA 125 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa)
NA View out essential:desirable:UNNECESSARY


DN KEY SCALE 1:400 M 1 Shelving, steel, open 2 Ladder, movable Note : provide 1000mm clear distance from

ceiling to topmost shelf 1 1 1 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 SD SD SD SD SD SD SD 27000 15000 36000 6000 126


Department: Room Title: HEALTH INFORMATION MANAGEMENT SYSTEMS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Lounging area for HIMS staff Refrigerator 1

b. HIMS staff stores personal belongings Water dispenser 1 c. HIMS staff uses toilet facilities Waste bin 1 FURNITURE AND FIXTURE CHECKLIST Table, dining 1 Chair, dining 4 Counter, with cabinets above 1

and below

People Involved: Sink, stainless steel 1 HIMS staff Concealed floor drain 1

Locker, steel, 300 x 500 mm 7

Slop sink with faucet 1

Shelf, open 1

Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to HIMS Department ENGINEERING TERMINALS

Outlet, 10A,2P,240V, duplex 6 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 3 Water sprinkler system

Reference Sheet Number: ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) QUANTITY REMARKS QUANTITY REMARKS Updated Reference: STAFF PANTRY, LOCKERS AND TOILETS QUANTITY REMARKS April 2016 250B-HIMS-RDS-08A 127


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: HEALTH INFORMATION MANAGEMENT SYSTEMS TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Cooling load (TR) NA Black out essential:desirable:UNNECESSARY SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Emergency Staff Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET April 2016 250-HIMS-RDS-08B 128 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa)
NA View out essential:desirable:UNNECESSARY STAFF PANTRY, LOCKERS AND TOILETS


KEY SCALE 1:100 M 1 STAFF PANTRY 2 Table, dining 3 Chair, dining 4 Counter, with cabinets above and below 5 Sink, stainless steel 6 Refrigerator 7 Water dispenser 8 Concealed floor drain 9 Waste bin 1500 1500 3800 2300 2100 1600 6000 6800 4750 10 LOCKERS 11 Locker, steel, 300 x 500 mm 12 JANITOR'S CLOSET 13 Slop sink with faucet 14 Shelf, open 15 FEMALE TOILET 16 MALE TOILET 1 10 12 15 16 2 SD SD 3 3 3 3 4 5 6 7 8 11 13 14 SD CH 9 9 9 129


VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.2 EMERGENCY SERVICE FACILITIES

First Edition DEPARTMENT OF HEALTH Manila 2017 131


Hospital: 250-Bed (Level 3) Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER 566.00 138.00 19.00 41.00 16.00 38.00 20.00 23.00 10.00 10.00 10.00 10.00 21.00 24.00 9.00 31.00 44.00 28.00 36.00 29.00

Resuscitation Bay Treatment Cubicle (OB-GYNE) Treatment Cubicle (SURGERY)

Minor Operating Room HEM Office and Supply Room Ambulatory Care

Service Facility Title: ROOM TITLE Waiting Area & Triage Decontamination Room Isolation Room Scrub-Up / Sub-Sterile VAWC Room ER Head Office Doctors' On Call Room Treatment Cubicle (PEDIA) Treatment Cubicle (MEDICAL) 250B-ER-SFSI-01 EMERGENCY Nurse Station Delivery Room Respiratory Unit Staff Pantry/Lockers, T&B PAGE Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU EMERGENCY Reference Sheet Number: SERVICE FACILITY SHEET INDEX 250B-ER-RDS-19 189 250B-ER-RDS-18 186 250B-ER-RDS-17 183 250B-ER-RDS-16 180 250B-ER-RDS-15 177 250B-ER-RDS-14 174 250B-ER-RDS-13 171 250B-ER-RDS-12 168 250B-ER-RDS-11 165 250B-ER-RDS-10 162 250B-ER-RDS-09 159 250B-ER-RDS-08 156 250B-ER-RDS-07 153 250B-ER-RDS-06 150 250B-ER-RDS-05 147 250B-ER-RDS-04 144 250B-ER-RDS-03 141 250B-ER-RDS-02 138 250B-ER-RDS-01 135 250B-ER-DDS-01 134 133 Observation Bay 250B-ER-RDS-20 192 9.00


UP UP UP UP UP UP OBSERVATION BAY NURSE STATION CLEAN LINEN ROOM MT FT ELECTRICAL ROOM STAFF T DIRTY LINEN JAN CLO DIRTY LINEN ROOM WASTE HOLDING ROOM AFFILIATES' ROOM CONF ROOM DOCTORS' ON-CALL ROOM AMBULATORY CARE ER HEAD OFFICE HEMS OFFICE HEMS OPCEN / SUPPLY ROOM STAFF PANTRY OPERATING ROOM NURSE STATION SURGICAL OB-GYNE DELIVERY ROOM ISOLATION ROOM VAWC ROOM EQPT STORAGE ROOM RESPIRATORY UNIT RESCUSCITATION BAY SUPPLY ROOM RECORDS ROOM TRIAGE WAITING AREA DECONTAMINATION ROOM EQPT STO ROOM SUP RM 3000 2100 18900 3000 2600 2100 2100 4000 4300 5900 3000 51000 3800 3300 13900 3000 6000 3000 3000 12000 4300 3000 4500 3200 5000 2000 5900 2100 6000 36000 6000 3000 6000 6000 6000 3000 6000 6000 3100 5100 4100 4100 7500 3100 3000 8100 12800 3100 O P E N C O U R T O P E N C O U R T MEDICINE PEDIA 33000 SCALE 1:400 M 134


Department: Room Title: EMERGENCY WAITING AREA & TRIAGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient may arrive on foot Sphygmomanometer/ Stethoscope 1 b. Patient may arrive in a wheelchair/ stretcher for Pedia/ Adult c. Patients arriving at ER are evaluated at the counter Computer 1 d. Patients await their turns to be interviewed and Adult/ Pediatric Scale 1 their cases to be assessed at the triage Spine board 1 e. Transfer of patient to/ from stretcher trolley or Printer 1 wheelchair to examining table Fire Extinguisher 1 Whiteboard 1 Thermometer, digital 1 Wheelchair & stretcher park 1 Waste bin w/ black lining 3 FURNITURE AND QUANTITY REMARKS People Involved: FIXTURE CHECKLIST 1 x Medical Doctor Counter, 2-level 1 1 x Nurse Counter, 1200mm high; with 1 1 x Nursing Attendant window 2 x Clerks Desk, 500mm x 300mm 1 Chair, swivel 5 Stool, adjustable 1

Chair, gang-type, 3-, 4- & 5-seater 20 ADDITIONAL EQUIPMENT & a. Adjacent to OPD Waiting Area ENGINEERING TERMINALS b. Close to entrance to OPD Outlet, 10A,2P,240V, duplex 10 grounding type, c. Close to the Office of the OPD chief

universal slots d. Close to Consultation Rooms Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 2 Outlet, DATA 1 Outlet, Telephone 1

Window Curtain Rail 2 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-ER-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: Planning Relationships QUANTITY REMARKS REMARKS QUANTITY 135


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY WAITING AREA & TRIAGE 250B-ER-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
500 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ER staff, patients, and visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 136 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


SCALE 1:200 M 1 Counter, 2-level 2 Counter, 1200mm high; with window 3 Desk, with computer and printer 4 Chair, swivel 5 Stool, adjustable 6 Chair, gang-type, 3-, 4- & 5-seater KEY 9000 12000 1 2 SD 3 4 5300 7500 SD SD 7 Whiteboard 8 Waste bin 9 Wheelchair & stretcher park 4 4 5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 7 8 8 9 T D 137


Department: Room Title: EMERGENCY DECONTAMINATION ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Ambulatory patient may arrive Exhaust fan 1 b. Patient may arrive on wheelchair/ stretcher Electric fan 1 c. Patient is decontaminated with chemical solutions Airconditioning unit 1 d. Patient undergoes screening for possible or suspected Thermometer 1 with any biological or chemical contamintion Sphygmomanometer 1 Weighing scale 1 Stethoscope 1 IV stand 1 Suction machine 1 Gooseneck lamp 1 Linen Hamper 1 Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-02A QUANTITY REMARKS Updated Reference: April 2016 People Involved: Stretcher 1 1 x Resident Physician Waste bin 1 Patient FURNITURE AND FIXTURE CHECKLIST Water closet w/ spray hose 1 Lavatory 1 Shower 1 Cubicle curtain and rod 1

Planning Relationships ADDITIONAL EQUIPMENT & a. Close to ambulance or emergency vehicle drop-off ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1

QUANTITY REMARKS QUANTITY REMARKS 138


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY DECONTAMINATION 250B-ER-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 20,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit ER staff and patient Fire risk low:MEDIUM:high Other risks NA ROOM DATA SHEET 139 ROOM Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


SCALE 1:100 M 1 Stretcher 2 DRESS CUBICLE 3 Hamper, soiled linen 4 Cubicle curtain and rod 5 Waste bin 6 TOILET WITH SHOWER KEY 6000 3100 SD 1 2 3 4 5 6 T D 140


Department: Room Title: EMERGENCY RESUSCITATION BAY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient may arrive on foot Defibrillator 1 b. Patient may arrive on wheelchair/ stretcher E-cart w/ complete emergency 1 c. Use of diagnostic equipment medicines ECG or cardiac monitor 1 Pulse oxymeter 1 Sphygmomanometer 1 Stethoscope 1 Thermometer, digital 1 Suction machine 1 Cardiac board 1 IV stand w/ IV fluid 1 People Involved: Laryngoscope w/ endotracheal tube 1 1 x Resident Physician Indwelling poly catheter 1 1 x Patient Bag valve mask or respirator 1 1 x Nurse Nebulizer 1 1 x Nursing Attendant Waste bin 1 FURNITURE AND FIXTURE CHECKLIST Examination table 1 Table, instrument 1 Resuscitating apparatus 1 Counter, with cabinets below 1

Sink, stainless steel 1 Examination light 1 Medical gas console 1 Cubicle curtain and rod 1 Concealed floor drain 1 Portable X-Ray Machine 1 ADDITIONAL EQUIPMENT & a. Close to Emergency suite entrance ENGINEERING TERMINALS b. Adjacent to Nurse Station and Minor Operating room Outlet, 10A,2P,240V, duplex 3 grounding type,

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1

Outlet, Aircon 1 Outlet for various equipment ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-03A QUANTITY REMARKS Updated Reference: April 2016 QUANTITY REMARKS QUANTITY REMARKS Planning Relationships Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) 141


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY RESUSCITATION BAY 250B-ER-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff and patients Fire risk LOW:medium:high Other risks NA ROOM DATA SHEET 142 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 5050 2750 1 Examination table 2 Table, instrument 3 Resuscitating apparatus 4 Counter, with cabinets below 5 Sink, stainless steel 6 Examination light SD 2 3 4 5 1 6 2700 2750 8200 CH CH CH 7 Medical gas console (Air, Oxgyen, Vaccum) 8 Cubicle curtain and rod 9 Concealed floor drain 10 Waste bin 11 Portable X-Ray Machine 7 8 9 10 T D 11 143


Department: Room Title: EMERGENCY RESPIRATORY UNIT FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Ambulatory patient may arrive Waste bin w/ yellow lining 1 b. Patient may arrive on wheelchair/ stretcher Bed 1 c. Patient is triaged and brought to the Respiratory unit Stethoscope 1 d. Holding area of patient prior to admission or referral for Sphygmomanometer 1 laboratory tests Thermometer, non-medical 1 e. Collection of specimen by nasopharyngeal swab Nebulizer 1 IV stand 1 Suction machine 1 Pulse Oxymeter 1 Ventilator 1 Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-04A QUANTITY REMARKS Updated Reference: April 2016 People Involved: FURNITURE AND 1 x Resident Physician FIXTURE CHECKLIST 1 x Patient Examination table 1 1 x Nurse Medical gas console 1 Cubicle curtain and rod 1

Planning Relationships ADDITIONAL EQUIPMENT & a. Close to emergency exit and accessible to the ENGINEERING TERMINALS Nursing wards Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1

QUANTITY REMARKS QUANTITY REMARKS 144


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY RESPIRATORY UNIT 250B-ER-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 20,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.65 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ER staff, patients and companions Fire risk LOW:medium:high Other risks NA ROOM DATA SHEET 145 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 3050 5100 SD 1 2 5 6 7 1 Examination table 2 Suction apparatus 3 Ventilator 4 IV stand 5 Medical gas console (Air, Oxgyen, Vaccum) 6 Cubicle curtain and rod 7 Waste bin 3 4 T D 146


Department: Room Title: EMERGENCY STAFF PANTRY/ LOCKERS, T&B FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Lounging area for Emergency Room staff Waste bin w/ black lining 2 b. Emergency Room staff stores personal belongings c. Emergency Room staff uses toilet facilities People Involved: FURNITURE AND Emergency Room Staff FIXTURE CHECKLIST Table, dining 1 Chair; dining 4 Counter, with cabinets above 1 and below Sink, stainless steel 1 Refrigerator 1 Water dispenser 1 Locker, steel, 300 x 500mm 8 Concealed floor drain 1 Slop sink 1

Shelf, open 1 Water closet 1 Lavatory 1 Urinal 1 Planning Relationships ADDITIONAL EQUIPMENT & a. Accessible from all ER facilities ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 7 grounding type,

universal slots

1 GFCI Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 2 QUANTITY REMARKS QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-05A QUANTITY REMARKS Updated Reference: April 2016 147


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY STAFF PANTRY/ 250B-ER-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Emergency Staff Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET 148 LOCKERS, T&B
Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


SCALE 1:100 M KEY 1700 4700 1300 1 STAFF PANTRY 2 Table, dining 3 Chair; dining 4 Counter, with cabinets above and below 5 Sink, stainless steel 6 Refrigerator 7 Water dispenser 8 Concealed floor drain 9 Waste bin 10 Locker, steel, 300 x 500mm 11 JANITOR'S CLOSET 12 Slop sink with faucet 13 Shelf, open 14 STAFF TOILET & BATH 4500 6200 2100 SD SD 2 3 3 3 3 CH 5 7 6 8 9 1 11 12 13 14 9 4 GFCI 3900 10 6000 149


Department: Room Title: EMERGENCY ISOLATION ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. ER patient is triaged and brought to Isolation Room Exhaust fan 1 b. ER attendant bathes patient Electric fan 1 c. Patient is decontaminated with chemical solutions Airconditioning unit 1 d. Patient undergoes screening for possible or suspected Thermometer 1 biological or chemical contamination
Sphygmomanometer 1 e. Consultation/ examination/ treatment of patients Weighing scale 1 f. Holding area of patients prior to admission or referral Stethoscope 1 to other hospitals IV stand 1 Suction machine 1 Gooseneck lamp 1 Linen Hamper 1 People Involved: Stretcher 1 1 x Medical Doctor Waste bin w/ black lining 1 1 x Nurse Waste bin w/ yellow lining 1 Patient FURNITURE AND FIXTURE CHECKLIST Examination table/bed 1 Table, side, 400 x 400mm 1 Footstool 1 Cabinet, for PPE; with PPE 1 Lavatory, wall-hung 1

Hamper, for soiled linen 1 Concealed floor drain w/ 1 waterless trap ADDITIONAL EQUIPMENT & QUANTITY REMARKS a. Close to Emergency Department exit ENGINEERING TERMINALS b. Adjacent to ambulance entrance Outlet, 10A,2P,240V, duplex 7 grounding type, c. Accessible to Nursing Wards

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1

Reference Sheet Number: 250B-ER-RDS-06A QUANTITY REMARKS Updated Reference: April 2016 Planning Relationships Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: QUANTITY REMARKS 150


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY ISOLATION ROOM 250B-ER-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 20,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 30 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ER staff and patient Fire risk low:MEDIUM:high Other risks NA ROOM DATA SHEET 151 Negative Pressure (Pa) 10
Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 1 ISOLATION ROOM 2 Examination table/bed 3 Table, side, 400 x 400mm 4 Footstool 5 Waste bin, general 6 Waste bin, infectious 1800 2500 3500 SD 1 7 ANTE ROOM 8 Cabinet, for PPE; with PPE 9 Lavatory, wall-hung 10 Hamper, for soiled linen 11 Concealed floor drain 12 TOILET 1500 3300 SD D T 2 4 3 5 6 7 8 9 10 6 11 12 6 6000 152


Department: Room Title: EMERGENCY VAWC ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST Examination table/bed 1 Speculum set 1 a. Patient arrives on foot, wheelchair, or stretcher Examination light 1 b. Social Worker/Family Physician interviews and Waste bin, w/ black or 2 records information from/about patient colorless lining

c. Family Physician examines patient and/or refers patient to diagnostic/laboratory service People Involved: FURNITURE AND 1 x Family Physician FIXTURE CHECKLIST 1 x Nurse Desk, 600 x 1200mm 1 1 x Social Worker Desk, extension 1 Patient Chair, swivel 1 Patient's companion Chair, upright, stacking 4 Table, side 1 Footstool 1 Cart, instrument 1 Cubicle curtain and rod 1

Planning Relationships ADDITIONAL EQUIPMENT & a. Preferably with exterior access ENGINEERING TERMINALS Window curtain rail 1 Outlet, 10A, 2P, 240V, duplex 6 grounding type,

universal slots Outlet, intercom 1 wall-mounted Outlet, Telephone 1 desktop Outlet, Data 1 Smoke Detector 1 Ionization type 250-Bed (Level 3) VAWC - Violence Against Women & Children ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-07A QUANTITY REMARKS Updated Reference: April 2016 REMARKS QUANTITY Department of Health DEVELOPMENT BUREAU HEALTH FACILITY QUANTITY REMARKS 153


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY VAWC ROOM 250B-ER-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.5 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ER staff, patient, companion Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 154 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 1 PATIENT ROOM 2 Examination table/bed 3 Table, side, 400 x 400mm 4 Footstool 5 Instrument cart 6 Chair, upright 7 Waste bin, general 1500 3500 1 8 INTERVIEW AREA 9 Desk, 600 x 1200mm 10 Desk, extension 11 Chair, swivel 12 Cubicle curtain and rod 13 TOILET 2300 3800 SD 2 4 3 5 6 7 8 9 10 12 13 T D 6 6 6 7 7 11 2500 6000 155


Department: Room Title: EMERGENCY TREATMENT CUBICLE (PEDIA) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Ambulatory patient may arrive on foot Laryngoscope w/ endotracheal tube 1 b. Patient may arrive on wheelchair/ stretcher (different sizes) c. Use of diagnostic equipment Examining light 1 d. Patient is treated for minor injuries and illness Nebulizer 1 e. Transfer of patient from examining table to stretcher Sphygmomanometer w/ pediatric cuffs 1 trolley, to go to observation rooms or pediatric wards Weighing scale, infant 1 f. Patient is assisted by Nurse/ Nursing Attendant to Heavy-duty weighing scale 1 move out from examining table and be discharged Stethoscope 1 IV stand 1 Suction machine 1 Gooseneck lamp 1 People Involved: Waste bin w/ black lining 1 1 x Resident Physician Oxygen tank set 1 1 x Patient Bag valve mask 1 1 x Nurse Cervical collar 1 1 x Nursing Attendant FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST Examination table/bed 1 Table, side, 400 x 400mm 1 Footstool 1 Chair, upright 1

Lavatory, wall-hung 1 Cubicle curtain and rod 1 Planning Relationships ADDITIONAL EQUIPMENT & a. Close to Emergency suite entrance ENGINEERING TERMINALS b. Adjacent to Nurse Station and Minor Operating room Outlet, 10A,2P,240V, duplex 3 grounding type,

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 for entire area Cubicle curtain rail 1

Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-08A QUANTITY REMARKS Updated Reference: April 2016 156


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY TREATMENT CUBICLE 250B-ER-RDS-08B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Medical staff and patient Fire risk LOW:medium:high Other risks NA ROOM DATA SHEET 157 (PEDIA) Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary


2350 KEY SCALE 1:100 M 3650 KEY 4 5 6 1 2 3 7 1 Examination table/bed 2 Table, side, 400 x 400mm 3 Footstool 4 Chair, upright 5 Waste bin, general 6 Lavatory, wall-hung 7 Cubicle curtain and rod Note : provide smoke detectors at entire area of pedia treatment 158


Department: Room Title: EMERGENCY TREATMENT CUBICLE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Ambulatory patient may arrive on foot Laryngoscope w/ endotracheal tube 1 b. Patient may arrive on wheelchair/ stretcher Pulse Oxymeter 1 c. Use of diagnostic equipment Examining light 1 d. Patient is treated for minor injuries and illness Nebulizer 1 e. Transfer of patient from examining table to stretcher Sphygmomanometer 1 trolley, to go to observation rooms or medical wards
Weighing scale 1 f. Patient is assisted by Nurse/ Nursing Attendant to Stethoscope 1 move out from examining table and be discharged IV stand w/ IV fluid 1 Suction machine 1 ECG cardiac monitor 1 Waste bin w/ black lining 1 People Involved: Oxygen tank set 1 1 x Resident Physician Bag valve mask 1 1 x Patient Cervical collar 1 1 x Nurse E-cart w/ complete ER meds 1 1 x Nursing Attendant Thermometer, digital 1 Electric fan 1 Glucometer 1 FURNITURE AND FIXTURE CHECKLIST Examination table/bed 1

Table, side, 400 x 400mm 1 Footstool 1 Chair, upright 1 Lavatory, wall-hung 1 Cubicle curtain and rod 1 ADDITIONAL EQUIPMENT & a. Close to Emergency suite entrance ENGINEERING TERMINALS b. Adjacent to Nurse Station and Minor Operating room Cubicle curtain rail 1 c. Accessible to the Nursing Wards Outlet, 10A,2P,240V, duplex 3 grounding type,

universal slots Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 for entire area Updated Reference: April 2016 Planning Relationships Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-09A QUANTITY REMARKS QUANTITY REMARKS QUANTITY REMARKS 159 (MEDICAL)


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY 250B-ER-RDS-09B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 3.6 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Medical staff and patient Fire risk LOW:medium:high Other risks NA ROOM DATA SHEET 160 TREATMENT CUBICLE (MEDICAL) Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


2650 SCALE 1:100 M 3650 1 Examination table/bed 2 Table, side, 400 x 400mm 3 Footstool 4 Chair, upright 5 Waste bin, general 6 Lavatory, wall-hung 7 Cubicle curtain and rod Note : provide smoke detectors at entire area of pedia treatment 1 2 3 4 5 6 7 KEY 161


Department: Room Title: EMERGENCY TREATMENT CUBICLE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Ambulatory patient may arrive on foot IV stand w/ IV fluid 1 b. Patient may arrive on wheelchair/ stretcher Examining light 1 c. Use of diagnostic equipment Oxygen tank set 1 d. Patient is treated for minor injuries and illness Sphygmomanometer 1 e. Transfer of patient from examining table to stretcher Stethoscope 1 trolley, to go to observation rooms or ob-gyne wards Weighing scale 1 f. Patient is assisted by Nurse/ Nursing Attendant to Ortho Set 1 move out from examining table and be discharged Thermometer, digital 1 Suction apparatus 1 EENT diagnostic set 1 Neurological hammer 1 People Involved: Glucometer 1 1 x Resident Physician Pulse Oxymeter 1 1 x Patient Cervical collar 1 1 x Nurse Laryngoscope w/ ET tube 1 1 x Nursing Attendant E-cart w/ complete ER meds 1 set ECG cardiac monitor 1 Bag valve mask 1 Electric fan 1 Waste bin w/ black lining 1 FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST

Examination table/bed 1 Table, side, 400 x 400mm 1 Footstool 1 Chair, upright 1 Lavatory, wall-hung 1 Cubicle curtain and rod 1 ADDITIONAL EQUIPMENT & QUANTITY REMARKS a. Close to Emergency suite entrance ENGINEERING TERMINALS b. Adjacent to Nurse Station and Minor Operating room Cubicle curtain rail 1 Outlet, 10A,2P,240V, duplex 3 grounding type,

universal slots Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 for entire area QUANTITY REMARKS Updated Reference: April 2016 Planning Relationships Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-10A 162 (OB-GYNE)


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY 250B-ER-RDS-10B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Medical staff and patient Fire risk LOW:medium:high Other risks NA ROOM DATA SHEET 163 TREATMENT CUBICLE (OB-GYNE) Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


SCALE 1:100 M 1 Examination table/bed 2 Table, side, 400 x 400mm 3 Footstool 4 Chair, upright 5 Waste bin, general 6 Lavatory, wall-hung 7 Cubicle curtain and rod Note : provide smoke detectors at entire area of pedia treatment 2350 3650 4 5 6 1 2 3 7 KEY 164


Department: Room Title: EMERGENCY TREATMENT CUBICLE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Ambulatory patient may arrive on foot IV stand w/ IV fluid 1 b. Patient may arrive on wheelchair/ stretcher Examining light 1 c. Use of diagnostic equipment Oxygen tank set 1 d. Patient is treated for minor injuries and illness Sphygmomanometer 1 e. Transfer of patient from examining table to stretcher Stethoscope 1 trolley, to go to observation rooms or surgery wards
Weighing scale 1 f. Patient is assisted by Nurse/ Nursing Attendant to Ortho Set 1 move out from examining table and be discharged Thermometer, digital 1 g. Patient is given initial treatment and brought to the Suction apparatus 1 Minor Operating Room EENT diagnostic set 1 Neurological hammer 1 Glucometer 1 Pulse Oxymeter 1 People Involved: Cervical collar 1 1 x Resident Physician Laryngoscope w/ ET tube 1 1 x Patient Surgical set (minor) 1 set 1 x Nurse Waste bin w/ black lining 1 1 x Nursing Attendant FURNITURE AND FIXTURE CHECKLIST Examination table/bed 1 Table, side, 400 x 400mm 1

Footstool 1 Chair, upright 1 Lavatory, wall-hung 1 Cubicle curtain and rod 1 ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS a. Close to Emergency suite entrance Cubicle curtain rail 1 b. Adjacent to Nurse Station and Minor Operating room Outlet, 10A,2P,240V, duplex 3 grounding type,

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 for entire area QUANTITY REMARKS Updated Reference: April 2016 QUANTITY REMARKS QUANTITY REMARKS Planning Relationships Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-11A 165 (SURGERY)


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY 250B-ER-RDS-11B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 3.6 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Medical staff and patient Fire risk LOW:medium:high Other risks NA ROOM DATA SHEET 166 TREATMENT CUBICLE (SURGERY) Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


2650 SCALE 1:100 M 3650 1 Examination table/bed 2 Table, side, 400 x 400mm 3 Footstool 4 Chair, upright 5 Waste bin, general 6 Lavatory, wall-hung 7 Cubicle curtain and rod Note : provide smoke detectors at entire area of pedia treatment 1 2 3 4 5 6 7 KEY 167


Department: Room Title: EMERGENCY NURSE STATION FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Nurse receives patient Instrument sterilizer 1 b. Nurse makes inquiries and records necessary information Waste bin w/ yellow lining 3 from/about patients rushed to ER Cart, supply 1 c. Nurse performs other medical monitoring activities Cart, emergency 1 d. Physician aided by nurses and nursing attendants, Lockers for staff 4 monitor and perform diagnostic activities and administers Filing cabinet 1 proper treatment to patient rushed to ER Cabinet for dangerous medicines 1 Whiteboard 1 Electric fan 1 Exhaust fan 1 GENT diagnostic set 1 People Involved: Weighing scale 1 1 x Nurse Defribrillator 1 1 x Nursing Attendant Ambu bag (Adult/Pedia) 1 Suction machine 1 Puncture-proof container 1 Clock 1 Refrigerator 1 FURNITURE AND FIXTURE CHECKLIST Counter, 2-level 2

Counter, with cabinets above & below 1 Sink, stainless steel 2 Chair, stacking, upright 1 Stool, adjustable 1 Concealed floor drain 1 Shelf, open 2 a. Close to Emergency entrance Water closet w/ spray hose 1 b. Adjacent to Treatment and Minor Operating Room Lavatory 1

ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 15 grounding type,

universal slots Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 2 Outlet, DATA 1 Outlet, Telephone 1

Water heater, 3.5kw 1

Paging System 1 QUANTITY REMARKS QUANTITY REMARKS Reference Sheet Number: 250B-ER-RDS-12A QUANTITY REMARKS Updated Reference: April 2016 Planning Relationships Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: 168


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY NURSE STATION 250B-ER-RDS-12B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering ESSENTIAL:desirable:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit nursing staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 169 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa)
NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 1267 1 NURSE STATION 2 Counter, 2-level 3 Counter, with cabinets above and below 4 Sink, stainless steel 5 Desk 6 Cart, supply 7 Cart, emergency 8 Chair, stacking, upright 9 Stool, adjustable 10 Whiteboard 11 Clock 12 Waste bin 13 MEDICINE PREP. ROOM 14 Concealed floor drain 15 Refrigerator, for medicine 16 SUPPLY ROOM 17 Shelf, open 18 CLEAN LINEN ROOM 19 DIRTY LINEN ROOM 20 STAFF TOILET 2767 4033 1265 2733 3998 1270 1203 SD 1 T SD D D 9 9 8 2 2 3 3 5 6 7 6 10 11 12 12 12 13 14 4 4 15 16 17 17 18 19 20 2008 2473 170


Department: Room Title: EMERGENCY DELIVERY ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a wheelchair or stretcher Delivery table 1 b. Patient is transferred to delivery table Adjustable stool 1 c. Clinical handwashing Shelf 1 d. Administering of anesthesia e. Preparation of patient for childbirth f. Normal delivery of baby by patient People Involved: FURNITURE AND 1 x Resident Physician FIXTURE CHECKLIST 1 x Nurse or Nursing Attendant Delivery table 1 Patient Adjustable stool 1 Shelf 1

Planning Relationships ADDITIONAL EQUIPMENT & a. Adjacent to Sub-Sterilizing Room ENGINEERING TERMINALS b. Adjacent to Scrub-Up Window curtain rail 1 c. Near Ob-Gyne Treatment Area Outlet, 10A, 2P, 240V, duplex 8 grounding type,

universal slots Outlet, intercom 1 wall-mounted Outlet, Telephone 1 desktop Outlet, Data 1 Smoke Detector 1 Ionization type Hospital: QUANTITY REMARKS Reference Sheet Number: 250B-ER-RDS-13A QUANTITY REMARKS REMARKS QUANTITY Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET 171


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY DELIVERY ROOM 250B-ER-RDS-13B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000-20,000 Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Exhaust (Pa) NA Daylight essential:desirable:UNNECESSARY Inlet (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.5-3 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIALl:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ER staff, patient Fire risk low : medium: HIGH Other risks NA ROOM DATA SHEET 172


KEY SCALE 1:100 M 6000 3900 1 9 Kick bucket 10 Heated bassinet/warmer 11 Aspirator 12 Clock 13 Isolation monitor 14 Floor clean-out 15 Shelving; adjustable, 500mm deep 16 Ground terminal 1 Delivery table 2 Obstetrical lamp 3 Mayo table 4 Emergency light, fixed 5 Instrument table 6 Emergency light, portable 7 Single basin stand 8 Adjustable stool 2 3 4 5 6 7 8 7 9 10 11 13 12 14 15 16 T D SD 173


Department: Room Title: EMERGENCY SCRUB-UP/SUB-STERILE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST SCRUB-UP Clock 1 a. Physician and nurses rinse arms and hands with water Soap Dispenser 1 and soap prior to and/or after surgical operation Hand Dryer 1 SUB-STERILE Small instrument sterilizer 1 a. Preparation of packed and surgical instruments from cabinets Waste bin w/ yellow lining 2 b. Storing and retrieving of instruments from cabinets Airconditioning unit 1 c. Minor sterilizing works d. Handwashing and other clean-up activities People Involved: FURNITURE AND 1 x Resident Physician FIXTURE CHECKLIST 1 x Nurse 2-Station Scrub sink, with 1 1 x Nursing Attendant gooseneck spout & foot control, sensor type Shelves, overhead 1 Concealed floor drain 2 Counter, 900mm high 1 Sink, with drainboard 1 Door, with vision panel 1

Planning Relationships ADDITIONAL EQUIPMENT & a. Adjacent to Sub-Sterilizing Room ENGINEERING TERMINALS b. Adjacent to Scrub-Up Outlet, 10A,2P,240V, duplex 5 grounding type, c. Close to Treatment cubicles

universal slots d. Close to Nurse Station Outlet, 15A,2P,240V, single 1 for emergency light e. Adjacent to Minor Operating Room Smoke detector 2 Outlet, Aircon 1

QUANTITY REMARKS ROOM DATA SHEET Hospital: QUANTITY REMARKS Reference Sheet Number: 250B-ER-RDS-14A QUANTITY REMARKS Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) 174


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY SCRUB-UP/SUB-STERILE 250B-ER-RDS-14B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 20,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ER staff Fire risk low:MEDIUM:high Other risks NA ROOM DATA SHEET 175 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


SCALE 1:100 M 1 SCRUB-UP AREA 2 2-Station Scrub sink, with gooseneck spout & foot control, sensor type 3 Soap dispenser 4 Hand dryer 5 Shelves, overhead 6 Waste bin, infectious 7 Clock 8 Concealed floor drain KEY 2300 2000 1500 2600 SD SD 9 1 2 3 4 5 6 7 8 9 SUB-STERILE ROOM 10 Counter, 900mm high 11 Sink, with drainboard 12 Instrument sterilizer, small 13 Door, with vision panel 10 11 12 13 8 6 CH 176


Department: Room Title: EMERGENCY MINOR OPERATING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a stretcher trolley IV Stand 1 b. Patient is transferred from a stretcher trolley to Operating light 1 operating table Oxygen tank set 1 c. Clinical Handwashing Sphygmomanometer 1 d. Anesthesia is administered Stethoscope 1 e. Use of diagnostic equipment Suction apparatus 1 f. Patient is surgically operated EENT diagnostic & surgical set 1 Surgical set 1 Clock 1 Double-film Negatoscope 1 Double X-ray film illuminator 1 UV Light 1 Telephone 1 People Involved: Airconditioning Unit 1 2 x Resident Physician Anesthesia Unit 1 1 x Patient Puncture-proof container 1 1 x Nurse Waste bin w/ yellow lining 1 1 x Nursing Attendant FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST Aspirator 1 Footstool 2 Instrument table 1

Double basin stand 1 Single basin stand 1 Anesthetist's stool 1 Anesthetist's table 1 Kick bucket 1 Concealed floor drain 1 Shelving; adjustable, 500mm deep 1 a. Adjacent to Sub-sterilizing Room Door with vision panel 1 b. Adjacent to Scrub-Up ADDITIONAL EQUIPMENT & c. Close to treatment cubicles ENGINEERING TERMINALS d. Close to Nurse station Outlet, 10A,2P,240V, duplex 9 grounding type,

universal slots Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, Telephone 1 Outlet, DATA 1 Grounding terminal 3 Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: QUANTITY REMARKS Updated Reference: April 2016 QUANTITY REMARKS Planning Relationships Reference Sheet Number: 250B-ER-RDS-15A 177


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY MINOR OPERATING ROOM 250B-ER-RDS-15B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit ER Staff and patient Fire risk low:medium:HIGH Other risks NA ROOM DATA SHEET 178 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY KEY SCALE 1:100 M 5100 6000 10 Kick bucket 11 Clock 12 Double-film negatoscope 13 Concealed floor drain 14 Shelving; adjustable, 500mm deep 15 Door with vision panel 1 Operating table 2 Operating lamp 3 Aspirator 4 Footstool 5 Instrument table 6 Double basin stand 7 Single basin stand 8 Anesthetist's stool 9 Anesthetist's table 1 2 4 4 5 6 7 8 9 10 11 12 3 13 14 15 SD T D 179


Department: Room Title: EMERGENCY HEALTH EMERGENCY MGMT. OFFICE & SUPPLY RM. FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of supplies for public health emergency Personal Protective Equipment (PPE) preparedness and response unit Gloves b. Distribution of said supplies Gown Goggles Facial Guards N95 Respirator or Surgical Mask Waste bin 2 People Involved: FURNITURE AND 1 x Medical Doctor FIXTURE CHECKLIST Desk, 600 x 1200mm 1 Desk, extension 1 Desk, 600 x 1000mm 2 Chair, upright; stacking 5 Cabinet, steel, filing 3 Shelf, open, adjustable, 8 600mm deep Ladder, aluminum 1

Planning Relationships ADDITIONAL EQUIPMENT & a. Within the Emergency Department and near the ENGINEERING TERMINALS exit/ lobby for easier distribution of supplies in cases Outlet, 10A,2P,240V, duplex 11 grounding type, of emergency

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 2 Outlet, Telephone 1 Outlet, DATA 1 QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-16A QUANTITY REMARKS Updated Reference: April 2016 REMARKS QUANTITY Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) 180


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY HEALTH EMERGENCY MGMT. OFFICE & SUPPLY RM. 250B-ER-RDS-16B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Medical Staff Fire risk low:MEDIUM: high Other risks NA ROOM DATA SHEET 181 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 1 HEMS OFFICE 2 Desk, 600 x 1200mm 3 Desk, extension 4 Desk, 600 x 1000mm 5 Chair, upright; stacking 6 Cabinet, steel, filing 7 Waste bin 6000 3200 4000 8 HEMS SUPPLY ROOM 9 Shelf, open, adjustable, 600mm deep 10 Ladder, aluminum SD SD T D 4 5 6 1 2 3 7 4 5 5 5 5 6 6 7 8 9 9 9 9 9 9 9 9 10 182


Department: Room Title: EMERGENCY ER HEAD OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Reads, writes, and uses telephone in his work station Waste bin w/ black lining 3 b. Receives visitors c. Consulted by patients d. Stores, files and retrieves records e. Supervises/ monitors clinical activities f. Use of toilet facilities People Involved: FURNITURE AND 1 x ER Chief FIXTURE CHECKLIST 1 x ER staff Desk, 600 x 1200mm 1 Visitors Desk, extension 1 Desk, 600 x 1000mm 1 Chair, junior executive 1 Chair, upright, stacking 4 Cabinet, steel, filing 3 Table, 4-seater 1 Chair, with armrest 4 Lavatory 1 Urinal 1

Water closet 1 Planning Relationships ADDITIONAL EQUIPMENT & a. Close to ER treatment cubicles ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 6 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 2 Outlet, Telephone 1 Outlet, DATA 1 QUANTITY REMARKS QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-17A QUANTITY REMARKS Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) 183


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY ER HEAD OFFICE 250B-ER-RDS-17B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ER chief, staff and visitors Fire risk LOW:medium:high Other risks NA ROOM DATA SHEET 184 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 1 ER HEAD'S OFFICE 2 Desk, 600 x 1200mm 3 Desk, extension 4 Desk, 600 x 1000mm 5 Chair, junior executive 6 Chair, upright, stacking 4000 7 Cabinet, steel, filing 8 Table, 4-seater 9 Chair, with armrest 10 Waste bin 11 TOILET SD 6000 1700 1900 1 2 3 4 5 6 6 6 6 7 7 7 8 9 9 9 9 10 10 11 T D T 185


Department: Room Title: EMERGENCY DOCTORS ON CALL ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Doctor on duty reads, writes, and uses mobile Waste bin w/ black lining 1 non-bidoegradable phone at his table Waste bin w/ green lining 1 biodegradable b. Doctor on duty rests while awaiting emergency calls c. Doctor on duty uses toilet facilities d. Doctor on duty stores personal belongings FURNITURE AND FIXTURE CHECKLIST Sofa, 2-seater 2 Desk, 600 x 1200mm 1 People Involved: Chair, swivel 1 2 x Resident Physician Cabinet, steel, filing 2 2 x Nurse Table, side, 400 x 400mm 2 2 X Nursing Attendant Table, dining, 4-seater 1 Chair, dining 4 Counter, with cabinets above 1 and below Sink, stainless steel 1 Water dispenser 1 Refrigerator 1 Concealed floor drain 1 Closet 1

Lavatory 1 Urinal 1 Water closet 1 ADDITIONAL EQUIPMENT & a. Close to ER Major Operating Room ENGINEERING TERMINALS b. Close to Nurse Station Outlet, 10A,2P,240V, duplex 8 grounding type, c. Close to Treatment Cubicles

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 2 Outlet, Telephone 1 Outlet, DATA 1 ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-18A QUANTITY REMARKS Updated Reference: April 2016 REMARKS QUANTITY REMARKS QUANTITY Planning Relationships Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) 186


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY DOCTORS ON CALL ROOM 250B-ER-RDS-18B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit ER chief, staff and visitors Fire risk LOW:medium:high Other risks NA ROOM DATA SHEET 187 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


SCALE 1:100 M 1 DOCTORS' ON-CALL RM 2 Sofa, 2-seater 3 Desk, 600 x 1200mm 4 Chair, swivel 5 Cabinet, steel, filing 6 Table, side, 400 x 400mm 7 Table, dining, 4-seater 8 Chair, dining 9 Waste bin KEY SD 1 2 3 4 5 6 D 10 Counter, with cabinets above and below 11 Sink, stainless steel 12 Water dispenser 13 Refrigerator 14 Concealed floor drain 15 Closet 16 TOILET & BATH 5900 4300 1700 4200 1700 6000 2 5 6 7 8 8 8 8 9 9 10 11 12 13 14 15 16 CH T 188


Department: Room Title: EMERGENCY AMBULATORY CARE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is transferred to Ambulatory Care Examination table/bed 2 after physician declares patient fit to be Waste bin, w/ black or 2 moved from Emergency to a patient room colorless lining

b. Patient stays at Ambulatory Care until a patient room is available People Involved: FURNITURE AND 1 x Resident Physician FIXTURE CHECKLIST Patient Table, side 2 Footstool 2 Chair, upright, stacking 2 Cubicle curtain and rod 2

Planning Relationships ADDITIONAL EQUIPMENT & a. Close to Observation Bays ENGINEERING TERMINALS b. Close to Treatment Area Window curtain rail 1 Outlet, 10A, 2P, 240V, duplex 6 grounding type,

universal slots Outlet, intercom 1 wall-mounted Outlet, Telephone 1 desktop Outlet, Data 1 Smoke Detector 1 Ionization type QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ER-RDS-19A QUANTITY REMARKS QUANTITY REMARKS Updated Reference: April 2016 189


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 EMERGENCY AMBULATORY CARE 250B-ER-RDS-19B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR)

SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ER staff, patient, companion Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 190 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


SCALE 1:100 M 1 MALE AMBULATORY CARE 2 Examination table/bed 3 Table, side, 400 x 400mm 4 Footstool 5 Chair, upright 6 Waste bin, general 7 Cubicle curtain and rod KEY 3650 1 2 5 6 7 3 4 T D 1700 2200 3000 1900 3000 8 FEMALE AMBULATORY CARE 9 TOILET SD 9 9 6 6 6 8 2 5 3 4 191


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is transferred to ER Observation from Emergency light 1 other ER areas: either from Rescusitation Bay, Volume respirator 1 Respiratory Unit, Treatment Cubicle, VAWC Room, Pulse oximeter 1 Delivery Room, or Operating Room Nebulizer 1 b. Patient is transferred to bed and vice versa Sphygmomanometer 1 c. Nurses and nursing attendants monitor vital Stethoscope 1 signs of patient at regular intervals IV stand with IV fluid 1 Thermometer, digital 1 Electric fan 1 People Involved: FURNITURE AND QUANTITY REMARKS 1 x Patient FIXTURE CHECKLIST 1 x Resident Physician Hospital bed, adjustable 1 1 x Nurse Table, side 1 1 x Nursing Attendant Footstool 1 Chair, upright 1 Cubicle curtain and rod 1

Planning Relationships: ADDITIONAL EQUIPMENT & QUANTITY REMARKS a. Visible from Observation Area Nurse Station ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 2 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light

Smoke detector 3

Hospital: OBSERVATION BAY 250-Bed (Level 3) ROOM DATA SHEET EMERGENCY Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Reference Sheet Number: QUANTITY REMARKS April 2016 250B-ER-RDS-20A Updated Reference: 192


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 3.6 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit patient and medical staff Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET April 2016 250B-ER-RDS-20B EMERGENCY OBSERVATION BAY 193


KEY SCALE 1:100 M 1 Hospital bed, adjustable 2 Table, side 3 Footstool 4 Chair, upright 5 Cubicle curtain and rod Note :

  • Provide smoke detectors at entire area of Observation bays
  • Provide handwashing sinks at central areas of Observation bays for shared use 2700 3000 1 2 3 4 5 194

VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.3 OUTPATIENT SERVICE FACILITIES

OUTPATIENT CLINICS 3.3.1 AMBULATORY SURGERY 3.3.2 CLINIC 3.3.3 PHYSICAL REHABILITATION UNIT 3.3.4. DIALYSIS UNIT

First Edition DEPARTMENT OF HEALTH Manila 2017 195


Hospital: 250-Bed (Level 3) Hospital Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER 839.00 297.00 250B-OPD-RDS-01 18.00 250B-OPD-RDS-02 OPD Records Room 36.00 250B-OPD-RDS-03 Office of the Family Medicine Chief 30.00 250B-OPD-RDS-04 43.00 250B-OPD-RDS-05 18.00 250B-OPD-RDS-06 Consultation Room (OB-GYNE) 54.00 250B-OPD-RDS-07 Consultation Room (Pedia/ Under Six) 36.00 250B-OPD-RDS-08 Consultation Room (Surgery) 18.00 250B-OPD-RDS-09 Consultation Room (Dental) 55.00 250B-OPD-RDS-10 36.00 250B-OPD-RDS-11 36.00 250B-OPD-RDS-12 Consultation Room (TB-DOTS) 90.00 250B-OPD-RDS-13 18.00 250B-OPD-RDS-14 36.00 250B-OPD-RDS-15 18.00 250B-OPD-RDS-16 200.00 18.00 250B-ASC-RDS-01 36.00 250B-ASC-RDS-02 18.00 250B-ASC-RDS-03 21.00 250B-ASC-RDS-04 7.00 250B-ASC-RDS-05 9.00 250B-ASC-RDS-06 33.00 250B-ASC-RDS-07 36.00 250B-ASC-RDS-08 12.00 250B-ASC-RDS-09 10.00 250B-ASC-RDS-10 Consultation Room (ENT) Public Toilets Staff Pantry & Lounge PAGE Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU OUTPATIENT 250B-OPD-SFSI-01 OUTPATIENT Reference Sheet Number: SERVICE FACILITY SHEET INDEX Treatment Room Consult/ Exam Service Facility Title: ROOM TITLE Lobby & Waiting Area Registration/ Admitting Area Consultation Room (Medicine) Conference Room Consultation Room (Ophtha) Scrub-Up Area Clean-Up Area Sterilization Room AMBULATORY SURGERY CLINIC Reception Clinic (Typical) Patient Dress/ Toilet Recovery Room Operating Room Sterile Instrument Supply & Storage Room

250B-OPD-DDS-01 250B-OPD-DDS-02 197 199 201 204 207 210 213 216 219 222 225 228 231 234 237 240 243 246 200 249 252 255 258 261 264 267 270 273 276


Hospital: 250-Bed (Level 3) Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER PHYSICAL REHABILITATION Waiting & Reception 20.00 250B-PR-RDS-01 Consult/ Exam Room 9.00 250B-PR-RDS-02 Treatment/ Gym Area 250B-PR-RDS-03 Toilets, Dress Cubicles & Soiled Linen Area 21.00 250B-PR-RDS-04 DIALYSIS Information, Admitting & Waiting Area 33.00 250B-DIA-RDS-01 Consultation Room 12.00 250B-DIA-RDS-02 Dialysis Treatment Area 250B-DIA-RDS-03 Isolation Room 12.00 250B-DIA-RDS-04 Janitor's Closet, Soiled Linen & Waste 13.00 250B-DIA-RDS-05 Holding Area Pantry 10.00 250B-DIA-RDS-06 Reprocessing Room 10.00 250B-DIA-RDS-07 Reference Sheet Number: OUTPATIENT 250B-OPD-SFSI-02 ROOM TITLE PAGE SERVICE FACILITY SHEET INDEX Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU Service Facility Title:

94.00 123.00 144.00 213.00 250B-PR-DDS-01 250B-DIA-DDS-01 279 280 283 286 289 292 293 296 299 302 305 308 311 198


UP UP RAMP UP PUBLIC FEMALE TOILET ANIMAL BITE CLINIC STD & HIV CLINIC PSYCH CLINIC FEMALE STAFF TOILET MALE STAFF TOILET PUBLIC MALE OILET TB DOTS CLINIC STAFF/ PANTRY/ LOUNGE OPD REGISTRATION/ ADMITTING COUNTER OPD RECORDS ROOM PUBLIC FEMALE TOILET PUBLIC MALE TOILET O P D L O B B Y W A I T I N G A R E A 3100 8900 3000 3000 3000 3000 14900 3000 6000 3000 3000 6000 18000 15000 SCALE 1:300 M 6000 15000 3100 21000 199


RAMP DN DN DN DN DN DN 6000 6000 ELECTRICAL ROOM 3000 6000 9000 3000 3000 3000 3000 2500 6000 3500 3000 3000 3000 51000 6000 6000 3000 6000 3000 3000 6000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 3000 AFFILIATES' ROOM OB-GYNE CLINIC RECEPTION/ RECORDS/ WAITING AREA SUB- WAITING AREA DRESS CLEAN UP SCRUB UP STERILE INSTRUMENT, SUPPLY, STORAGE FEMALE STAFF TOILET MALE STAFF TOILET STAFF PANTRY/ LOUNGE FAMILY PLANNING CLINIC OB- GYNE CLINIC E CONSULT/ EXAM ROOM TREATMENT DRESS RECOVERY ROOM OR SURGERY/ MEDICINE OPHTHA OPHTHA DENTAL X-RAY FEMALE STAFF TOILET MALE STAFF TOILET FM CHIEF OFFICE CONFERENCE ROOM PEDIA WELLNESS WELLNESS PEDIA DENTAL NURSES' OFFICE FAMILY MEDICINE CLINIC FAMILY MEDICINE CLINIC NEWBORN CLINIC BREAST CLINIC CHEMOTHERAPY CLINIC HEARING CLINIC FEMALE PUBLIC TOILET MALE PUBLIC TOILET ENT CLINIC DERMA CLINIC STAFF PANTRY/ LOCKERS TREATMENT OR STERILIZATION ROOM 3000 SCALE 1:300 M 200


Department: Room Title: OUTPATIENT LOBBY & WAITING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patients await their turns to be interviewed and their Waste bins, foot-controlled 6 General waste cases be assessed at the triage (black & green) b. Patients await their turns to be attended to in any of the treatment rooms c. Patient waits for his/ her number to be called People Involved: FURNITURE AND 72 x Outpatients and Companions FIXTURE CHECKLIST Counter, 2-level 1 Chair, gang 14 4-seater 4 5-seater 19 6-seater Planning Relationships: ADDITIONAL EQUIPMENT & QUANTITY REMARKS a. Close to OPD Consultation Rooms ENGINEERING TERMINALS b. Adjacent to OPD Registration Counter Window curtain rail 4 c. Close to other Ancillary Services Outlet, 10A,2P,240V, duplex 12 grounding type, d. Registration Area to a location near the entrance and

universal accessible to OPD Clinics Outlet, 10A, 2P 240V, single 2 for emergency light Smoke Detector 6 April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) 201


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT LOBBY & WAITING AREA 250B-OPD-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
150 Room temperature (°C) atmospheric Night illumination (LUX) 50 Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit general public Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 202 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:300 M 15000 18000 1 Counter, 2-level 2 Chair, gang 3 Waste bin 1 2 3 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 SD SD SD SD SD SD 3000 9000 203


Department: Room Title: OUTPATIENT FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. OPD Patient Registration Printer 1 b. Data encoding of patient's information to the system Computer 1 c. Issuance of Medical/Legal certificates Telephone handset 1 d. Maintenance of OPD register Intercom handset 1 Electric fan 1 Microphone 1 Waste bin w/ black lining 1 People Involved: FURNITURE AND 1 x Administrative Officer FIXTURE CHECKLIST 2 x Data controller Counter, with transaction window 1 Cabinet, 450 x 2000mm 1 Stool, adjustable 3 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to OPD Waiting Area b. Close to entrance to OPD Outlet, 10A,2P,240V, duplex 6 grounding type, c. Close to the Office of the OPD chief

universal slots d. Close to Consultation Rooms Outlet, 10A, 2P 240V, single 1 e. Adjacent and accessible to OPD Records Room Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 1 Paging System 1 Water Sprinkler 1 Fire extinguisher 1 QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-OPD-RDS-02A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 204 ADMITTING/ REGISTRATION COUNTER


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT ADMITTING/ REGISTRATION COUNTER 250B-OPD-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit OPD staff, patients & visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 205


6000 KEY SCALE 1:100 M 3000 1 Counter, with transaction window 2 Cabinet, 450 x 2000mm 3 Stool, adjustable 4 Waste bin 1 3 SD 2 4 D T 3 3 206


Department: Room Title: OUTPATIENT RECORDS ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. OPD staff reads, writes, files and retrieves records of Steel ladder, 4-step, heavy-duty 2 patients Electric fan 1 Fire extinguisher 1 Waste bin w/ black lining 1 People Involved: FURNITURE AND 1 x Records officer FIXTURE CHECKLIST 1 x Clerk Shelving, open, steel 18 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent and accessible to OPD registration counter Outlet, 10A,2P,240V, single 1 emergency light b. Adjacent to OPD waiting area c. Close to entrance to OPD d. Close to the Office of the OPD chief e. Close to consultation rooms QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-03A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 207


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT RECORDS ROOM 250B-OPD-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit OPD staff & authorized users Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET 208


6000 6000 KEY SCALE 1:100 M 1 Shelving, open, steel 2 Ladder, steel 2 1 2 1 1 1 1 1 209


Department: Room Title: OUTPATIENT FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Reads, writes and uses telephone in his work station Computer/ Laptop 1 b. Receives visitors Printer 1 c. Consulted by patients Waste bin w/ black lining 2 d. Stores, files, and retrieves records e. Supervises/ monitors clinical activities f. Use of toilet facilities People Involved: FURNITURE AND QUANTITY REMARKS 1 x Family Medicine chief FIXTURE CHECKLIST 1 x Family Medicine staff Desk, 750 x 1500mm 1 Visitors Desk, extension, 400 x 900mm 1 Shelf, open 1 Cabinet, steel, filing 3 Chair, junior executive 1 Chair, visitor 2 Sofa, 2-seater 1 Counter, 900mm high, with 1 cabinets above and below Sink, stainless steel 1 Table, side, 400 x 400mm 2 Water closet 1 Lavatory 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to OPD consultation rooms Window curtain rail 2 b. Close to OPD registration counter Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 1 Aircon, window type 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-04A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 210 OFFICE OF THE FAMILY MEDICINE CHIEF


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT OFFICE OF THE FM CHIEF 250B-OPD-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit FM chief, staff & visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 211


KEY SCALE 1:100 M 4300 6000 1 Desk, 750 x 1500mm 2 Desk, extension, 400 x 900mm 3 Shelf, open 4 Cabinet, steel, filing 5 Chair, junior executive 6 Chair, visitor 7 Sofa, 2-seater 1 SD 1700 1900 D T CH 2 3 8 9 5 6 6 7 10 10 11 11 12 4 4 4 8 Counter, 900mm high, with cabinets above and below 9 Sink, stainless steel 10 Table, side, 400 x 400mm 11 Waste bin 12 Concealed floor drain 212


Department: Room Title: OUTPATIENT CONFERENCE ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. OPD staff, physicians and visitors hold meetings LCD projector, built-in 1 and special lectures Negatoscope 1 Aircon 1 Computer/ Printer 1 Whiteboard/ Projection screen 2 Waste bin w/ black lining 2 biodegradable non-biodegradable People Involved: FURNITURE AND OPD doctors FIXTURE CHECKLIST OPD staff Table, 500 x 1500mm 6 Visitors Cabinet, 400 x 2000mm 1 Chair, swivel 12 Counter, 900mm high, with 1 cabinets above and below Sink, stainless steel 1 Water closet 1 Lavatory 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Staff Area Window curtain rail 1 b. Close to the Office of the OPD chief Outlet, 10A,2P,240V, duplex 6 grounding type, c. Close to OPD consultation rooms

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1 QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-05A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 213


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT CONFERENCE ROOM 250B-OPD-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit OPD staff & visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 214


KEY SCALE 1:100 M 1 Table, 500 x 1500mm 2 Cabinet, 400 x 2000mm 3 Chair, swivel 4 Counter, 900mm high, with cabinets above and below 1700 6000 6000 SD CH 1 2 3 3 4 5 6 7 7 6 7 3 3 3 1 1 1 1 1 3 3 3 3 3 3 3 5 Sink, stainless steel 6 Whiteboard/projection screen 7 Waste bin 8 Concealed floor drain 8 215


Department: Room Title: OUTPATIENT CONSULTATION ROOM (MEDICINE) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient may arrive on foot Examination light 1 b. Patient may arrive in wheelchair Sphygmomanometer, non-mercurial 1 c. Transfer patient to/from a wheelchair to examining Examination bed 1 table and vice versa Adult weighing scale 1 d. Clinical handwashing Paper towel dispenser 1 e. Use of monitoring/diagnostic equipment Towel rack 1 f. Medical, surgical, nursing and first aid activities Opthalmoscope 1 Otoscope 1 Neuro hammer 1 2-film Negatoscope 1 Mayo Table 1 Gooseneck lamp 1 Stethoscope 1 IV stand 1 Sharps collector, puncture-proof 1 container Footstool 1 People Involved: Waste bin w/ black lining 1 1 x Resident Physician Waste bin w/ yellow lining 1 2 x Nurse 1 x Nursing Attendant FURNITURE AND 1 x Patient FIXTURE CHECKLIST Desk 1 Chair, upright, stacking 2 Stool, adjustable height 1 Cabinet, steel, filing 1 Table, side; 400 x 500mm 1 Counter, 900mm high, 1 cabinets above and below Sink, with drainboard, with 1 gooseneck spout & foot/ elbow control Concealed floor drain 1 Planning Relationships: a. Close to other Ancillary Services ADDITIONAL EQUIPMENT & b. Close to OPD Minor OR ENGINEERING TERMINALS Window curtain rail 1 This activity space provides facilities needed for Outlet, 10A,2P,240V, duplex 6 grounding type, the delivery of general patient care

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 1 Cubicle curtain rail 1 Department of Health HEALTH FACILITY QUANTITY REMARKS QUANTITY REMARKS Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-06A 216


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT CONSULTATION ROOM (MEDICINE) 250B-OPD-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff and patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 217


3000 6000 KEY SCALE 1:100 M 1 Desk 2 Chair, upright, stacking 3 Stool, adjustable height 4 Adult weighing scale 5 Cabinet, steel, filing 6 Table, side; 400 x 500mm 7 Examination light 8 Examination bed 9 Footstool 10 Trolley 11 Counter, 900mm high, cabinets above and below 12 Sink, with drainboard, with gooseneck spout & foot/ elbow control 13 Negatoscope 14 Rack, towel 15 Cubicle curtain with rod 16 Waste bin 17 Concealed floor drain 2 1 4 D SD 2 5 6 7 8 9 11 12 14 15 17 16 16 CH T 10 13 3 218


Department: Room Title: CONSULTATION ROOM (OB-GYNE) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is ambulatory Examination light 2 b. Patient may arrive in wheelchair Examination bed 2 c. Transfer patient to/from a wheelchair to examining Adult weighing scale 2 table and vice versa Sphygmomanometer, non-mercurial 2 d. Clinical handwashing Paper towel dispenser 1 e. Use of monitoring/diagnostic equipment Speculum set (vaginal) 2 f. Medical, surgical, nursing and first aid activities Histerometer 1 g. Administration of Tetanus Toxoid (TT) immunization Ovum forceps 1 Towel rack 2 Stainless container 3 Trolley 2 Stethoscope 1 Kelly Pad 1 NSD set 1 Waste bin w/ yellow lining 3 Fetal Doppler 1 Line hamper 2 People Involved: Dressing cart w/ acessories 1 2 x Resident Physicians Puncture-proof container 2 2 x Nurses Foot stool 2 2 x Nursing Attendants FURNITURE AND 2 x Patients FIXTURE CHECKLIST Desk, 750mmX1200mm 3 Chair, upright, stacking 7 Side extension, 400 x 900mm 1 Side extension, 400 x 1200mm 2 Bench 1 Water Closet 2 Lavatory 2 Planning Relationships: a. Close to OPD Consultation Room (Pedia/ Under six) ADDITIONAL EQUIPMENT & b. Close to other Ancillary Services ENGINEERING TERMINALS c. Close to toilet facilities Outlet, 10A,2P,240V, duplex 17 grounding type, This activity space provides facilities needed for

universal slots the delviery of general patient care Outlet, 10A,2P,240V, single 1 emergency light Outlet, DATA 2 Outlet, Telephone 2 Smoke detector 4 QUANTITY REMARKS QUANTITY REMARKS April 2016 OUTPATIENT 250B-OPD-RDS-07A REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 219


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT CONSULTATION ROOM (OB-GYNE) 250B-OPD-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff and patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 220


2500 3000 3500 6000 9000 3000 3000 4500 1500 KEY SCALE 1:150 M 1 Desk 2 Side extension, 400 x 900mm 3 Side extension, 400 x 1200mm 4 Chair, upright, stacking 5 Bench 6 Adult weighing scale 7 Examination bed 8 Footstool 9 Linen hamper 10 Waste bin 11 TOILET 1 D T SD 2 3 1 4 5 6 7 8 9 11 10 10 4 10 4 4 4 SD SD D T SD 3 1 4 7 8 9 10 10 4 SD 11 221


Department: Room Title: CONSULTATION ROOM (PEDIA/ UNDER SIX) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is ambulatory Adult weighing scale 1 b. Patient may arrive in wheelchair Infant weighing scale 1 c. Transfer patient to/from a wheelchair to examining Examination bed 2 table and vice versa Footstool 2 d. Use of monitoring/diagnostic equipment Paper towel dispenser 2 e. Medical, surgical, nursing and first aid activities Examination light 2 Trolley 2 Lamp, gooseneck 2 Refrigerator, for meds 1 Negatoscope 2 Rack, for towel 1 Waste bin w/ yellow lining 3 People Involved: FURNITURE AND 2 x Resident Physicians FIXTURE CHECKLIST 2 x Nurse Desk, 750mmX1200mm 1 2 x Nursing Attendants Chair, upright, stacking 3 2 x Patients Table, side, 400 x 500mm 2 Counter, 900mm high, 1 cabinets above and below Sink, with drainboard, with 1 gooseneck spout & foot/ elbow control Stool, adjustable 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to OPD Consultation Rooms ENGINEERING TERMINALS b. Close to other Ancillary Services Window curtain rail 2 Outlet, 10A,2P,240V, duplex 17 grounding type, This activity space provides facilities needed for

universal slots the delivery of general patient care Outlet, 10A,2P,240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 4 Electronic queuing machine, optional 1 April 2016 OUTPATIENT 250B-OPD-RDS-08A Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET QUANTITY REMARKS Department of Health HEALTH FACILITY QUANTITY REMARKS 222


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT CONSULTATION ROOM (PEDIA/ UNDER SIX) 250B-OPD-RDS-08B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff and patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 223


3100 KEY SCALE 1:100 M 6000 3000 3000 2900 SD SD SD SD CH 1 Desk 2 Chair, upright, stacking 3 Adult weighing scale 4 Infant weighing scale 5 Examination bed 6 Table, side, 400 x 500mm 7 Footstool 8 Paper towel dispenser 9 Examination light 10 Trolley 11 Lamp, gooseneck 12 Counter, 900mm high, cabinets above and below 13 Sink, with drainboard, with gooseneck spout & foot/ elbow control 14 Refrigerator, for meds 15 Stool, adjustable 16 Negatoscope 17 Rack, for towel 18 Waste bin 19 Concealed floor drain 1 2 2 2 2 3 4 12 13 15 17 18 19 5 6 7 8 9 10 11 16 18 14 D T 5 6 7 8 9 10 11 16 18 6000 224


Department: Room Title: OUTPATIENT CONSULTATION ROOM (SURGERY) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient may arrive on foot Thermometer, non-mercurial 1 b. Patient may arrive in wheelchair Sphygmomanometer, non-mercurial 1 c. Transfer patient to/from a wheelchair to examining Examination bed 1 table and vice versa Adult weighing scale 1 d. Clinical handwashing Paper towel dispenser 1 e. Use of monitoring/diagnostic equipment Towel rack 1 f. Medical, surgical, nursing and first aid activities Opthalmoscope 1 Otoscope 1 Neuro hammer 1 2-film Negatoscope 1 Mayo Table 1 Examination light 1 Stethoscope 1 IV stand 1 Sharps collector 1 Footstool 1 Cast remover 1 People Involved: Mirror set 1 1 x Resident Physician I and D set 1 1 x Nurse Suture removal set 1 1 x Nursing Attendant Trolley 1 1 x Patient Waste bin w/ black lining 1 Waste bin w/ yellow lining 1 FURNITURE AND FIXTURE CHECKLIST Desk, 750mmX1200mm 1 Chair, upright, stacking 2 Stool, adjustable height 1 Cabinet, steel, filing 1 Side table, 400mmX500mm 1 Counter, 900mm high, 1 cabinets above and below Sink, with drainboard, with 1 Planning Relationships: gooseneck spout & foot/ a. Close to other Ancillary Services elbow control b. Close to OPD Minor OR Concealed floor drain 1 ADDITIONAL EQUIPMENT & This activity space provides facilities needed for ENGINEERING TERMINALS the delivery of general patient care Window curtain rail 1 Outlet, 10A,2P,240V, duplex 6 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 1 Cubicle curtain rail 1 April 2016 Reference Sheet Number: QUANTITY QUANTITY REMARKS REMARKS REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-09A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) 225


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT CONSULTATION ROOM (SURGERY) 250B-OPD-RDS-09B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff and patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 226


2 1 4 D SD 2 5 6 7 8 9 11 12 14 15 17 16 16 CH T 10 13 3 3000 6000 KEY SCALE 1:100 M 1 Desk 2 Chair, upright, stacking 3 Stool, adjustable height 4 Adult weighing scale 5 Cabinet, steel, filing 6 Table, side; 400 x 500mm 7 Examination light 8 Examination bed 9 Footstool 10 Trolley 11 Counter, 900mm high, cabinets above and below 12 Sink, with drainboard, with gooseneck spout & foot/ elbow control 13 Negatoscope 14 Rack, towel 15 Cubicle curtain with rod 16 Waste bin 17 Concealed floor drain 227


Department: Room Title: OUTPATIENT CONSULTATION ROOM (DENTAL) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is ambulatory Dental chair, hydraulic 2 b. Patient may arrive in wheelchair Amalgamator, electric 2 c. Transfer patient to/from a wheelchair to examining Instrument sterilizer 2 table and vice versa Dental unit with monitor 2 d. Use of monitoring/diagnostic equipment Dental unit with hydraulic 2 e. Medical, surgical, nursing and first aid activities Dental x-ray, wall model 1 f. Dentists perform normal and special dental Dental operating light 2 procedures to treat Developing tank 1 Compressor, dental air 1 Towel rack 2 Bane pole, stainless 3 Coton files sow 2 High-speed handpiece w/ burr 1 remover 1 Waste bin w/ yellow lining 2 Puncture-proof container 1 Surgical chisel 1 People Involved: Surgical mallette ronquer 2 2 x Dentists *18 upper molar dental chair unit 1 2 x Dental Aides 2 x Patients FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST Desk 4 Chair, upright, stacking 7 Cabinet, file, steel 3 Counter, 900mm high, cabinets 5 below Sink, with gooseneck spout 2 Sink, elbow-controlled 1 Cabinet, dental instrument 2 Stool, adjustable 2 Concealed floor drain 3 Planning Relationships: a. Close to OPD Consultation Rooms ADDITIONAL EQUIPMENT & QUANTITY REMARKS b. Close to other Ancillary Services ENGINEERING TERMINALS This activity space provides facilities needed for Outlet, 10A,2P,240V, duplex 18 grounding type, the delivery of general patient care

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 4 Outlet: Gas, Air, Electic 1 Electronic queuing machine, optional 1 April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-10A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) 228


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT CONSULTATION ROOM (DENTAL) 250B-OPD-RDS-10B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 5,000-1,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: heat generating instrument Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: at sink and lavatory tolerated Maximum temperature (°C) 70 Access limit medical staff and patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 229


KEY SCALE 1:150 M 3000 2200 3000 6000 9075 3900 21 17 2975 12 13 14 16 15 17 SD 4 9 10 11 12 13 14 16 15 17 SD 4 9 10 11 18 4 5 22 4 5 22 4 6 7 8 22 1 2 2 3 D 2 2 2 2 2 3 3 T CH CH CH 1 Desk 2 Chair, upright, stacking 3 Cabinet, file, steel 4 Counter, 900mm high, cabinets below 5 Sink, with gooseneck spout 6 Sink, elbow-controlled 7 Developing tank 8 Compressor, dental air 9 Instrument sterilizer 10 Amalgamator 11 Cabinet, dental instrument 12 Chair, dental 13 Dental unit with monitor 14 Dental unit, hydraulic 15 Dental operating light 16 Stool, adjustable 17 Waste bin 18 Dental X-ray, wall model 19 Dental Laboratory 20 Outlet : Gas, Air, Eletric 21 Rack, towel 22 Concealed floor drain 20 SD SD SD 230


Department: Room Title: OUTPATIENT CONSULTATION ROOM (ENT) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is ambulatory Compressed air & vacuum apparatus 1 b. Patient may arrive in wheelchair Table, treatment
1 c. Transfer patient to/from a wheelchair to examining Table, with instrument 1 table and vice versa ENT instruments 1 d. Use of monitoring/diagnostic equipment ENT chair-diagnostic 1 e. Medical, surgical, nursing and first aid activities Head mirror 1 Instrument Sterilizer 2 Sharps collector 1 Examination light 1 Indirect laryngoscopy 1 Otoscope 1 Sphygmomanometer 1 Adult weighing scale 1 Stethoscope, non-mercurial 1 Surgical set 1 Alligator forcep 1 ENT endoscopy set 1 People Involved: Thermometer, digital 1 1 x Medical Specialist Whiteboard
1 1 x Nurse Rack, towel 1 1 x Patient Clock 1 Waste bin 2 Footstool 1 FURNITURE AND FIXTURE CHECKLIST Desk, 600 x 1200mm 2 Chair, upright, stacking 3 Chair, gang-type 2 Cabinet, steel; filing 3 Stool, adjustable height 1 Counter, 900mm high, cabinets 1 above and below Sink, with gooseneck spout & 1 Planning Relationships: foot/elbow control a. Close to OPD Consultation Rooms Sink, combination instrument/scrub 1 b. Adjacent to consultation room (Ophtha) w/ gooseneck spout & foot/elbow control This activity space provides facilities needed for Cabinet, supply 1 the delivery of general patient care Concealed floor drain 1 ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Window curtain rail 2 Outlet, 10A,2P,240V, duplex 10 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, DATA 2 Outlet, Telephone 2 Smoke detector 2 Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-11A Department of Health HEALTH FACILITY QUANTITY REMARKS QUANTITY REMARKS 231


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT CONSULTATION ROOM (ENT) 250B-OPD-RDS-11B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 5,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: instrument sterilizer Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff and patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 232


SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Chair, upright, stacking 3 Chair, gang-type 4 Adult weighing scale 5 Cabinet, steel; filing 6 Whiteboard 7 Table, treatment 8 Table, with instrument 9 Compressed air and vacuum apparatus 10 Footstool 11 Stool, adjustable height 12 Examination light 13 ENT Chair 6000 14 Counter, 900mm high, cabinets above and below 15 Sink, with gooseneck spout & foot/elbow control 16 Sink, combination instrument/scrub; w/ gooseneck spout & foot/elbow control 17 Cabinet, supply 18 Rack, towel 19 Clock 20 Waste bin 21 Concealed floor drain 3000 3000 6000 KEY 1 SD D T SD 2 4 3 3 5 5 5 6 1 2 2 7 8 10 12 13 9 11 12 14 15 16 17 18 21 20 20 19 CH D T 233


Department: Room Title: OUTPATIENT CONSULTATION ROOM (OPHTHA) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is ambulatory Examinination light 1 b. Patient may arrive in wheelchair Trial lens case 1 c. Transfer patient to/from a wheelchair to examining Illuminated test card cabinet 1 table and vice versa Clock 1 d. Use of monitoring/diagnostic equipment IV stand 1 e. Medical, surgical, nursing and first aid activities Minor ophthalmic set 1 Trolley 1 Tonometer 1 Opthalmic set 1 Sneller chart 1 Sphygmomanometer, non-mercurial 1 Adult weighing scale 1 Stethoscope, non-mercurial 1 Swivel chair 1 Sharps collector 1 Rack, towel 1 Table, treatment 1 People Involved: Compressed air & vacuum apparatus 1 1 x Resident Physician Waste bin, w/ yellow lining 2 infectious 1 x Medical Specialist 1 x Patient FURNITURE AND 1 x Nurse FIXTURE CHECKLIST 1 x Intern Desk 1 Nursing Affiliates Chair, upright, stacking 10 Clinical Secretary Chair, ENT 1 Stool, adjustable height 2 Cabinet, steel, filing 3 Counter, 900mm high, 1 cabinets above and below Sink, with gooseneck spout & 1 foot/elbow control Sink, combination instrument/ 1 scrub; w/ gooseneck spout Planning Relationships: & foot/elbow control a. Close to OPD Consultation Rooms Cabinet, supply 1 b. Adjacent to consultation room (ENT) Concealed floor drain 1 This activity space provides facilities needed for ADDITIONAL EQUIPMENT & the delivery of general patient care ENGINEERING TERMINALS Window curtain rail 1 Outlet, 10A,2P,240V, duplex 9 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 2 QUANTITY REMARKS QUANTITY REMARKS REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-12A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 234


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT CONSULTATION ROOM (OPHTHA) 250B-OPD-RDS-12B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff and patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 235


6000 6000 KEY SCALE 1:100 M 1 Desk 2 Chair, upright, stacking 3 Chair, ENT 4 Stool, adjustable height 5 Cabinet, steel, filing 6 Adult weighing scale 7 Table, treatment 8 Examination light 9 Compressed air and vacuum apparatus 10 Trolley 11 Counter, 900mm high, cabinets above and below 12 Sink, with gooseneck spout & foot/elbow control 13 Sink, combination instrument/ scrub; w/ gooseneck spout & foot/elbow control 14 Cabinet, supply 15 Rack, towel 16 Waste bin 17 Concealed floor drain SD SD 2 1 2 2 4 4 6 5 5 5 7 8 9 3 10 11 12 14 13 15 17 16 16 D T CH 2 2 2 2 2 2 2 236


Department: Room Title: CONSULTATION ROOM (TB-DOTS) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is ambulatory Stethoscope 2 b. Clinical handwashing Thermometer, non-mercurial 2 c. Recording and reporting of TB data Examination bed 2 d. Sputum microscopy for diagnosis Sphygmomanometer, non-mercurial 2 e. Distribution of anti-TB drugs Footstool 2 Mayo table 2 Gooseneck Lamp 2 Computer 1 Towel rack 2 Printer 3 Waste bin, foot-controlled 4 Puncture-proof container 1 Negatoscope 2 People Involved: FURNITURE AND QUANTITY REMARKS 1 x Resident Physician FIXTURE CHECKLIST 1 x Nursing Attendant Chair, upright, stacking 11 1 x Patient Counter, 900mm high, 2 1 x Patient's companion cabinets above and below

Sink, with drainboard 2 Desk 3 Cabinet, filing 3 Counter, cabinets below 2 Sink 2 Concealed floor drain 4 Water Closet 1 Urinal 1 Lavatory 1 Planning Relationships: a. Close to other Ancillary Services ADDITIONAL EQUIPMENT & QUANTITY REMARKS b. Within the OPD Department but with separate ENGINEERING TERMINALS entrance for patients Window curtain rail 2 Outlet, 10A,2P,240V, duplex 20 grounding type, This activity space provides facilities needed for

universal slots the delivery of general patient care Outlet, 10A,2P,240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 4 Exhaust fan 1 Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET April 2016 OUTPATIENT 250B-OPD-RDS-13A Department of Health HEALTH FACILITY 237


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: CONSULTATION ROOM (TB-DOTS) TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 3 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL: desirable :unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff and patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 OUTPATIENT 250B-OPD-RDS-13B 238


KEY SCALE 1:200 M 1 Receiving Area : 2 Chair, upright, stacking 3 Counter, 900mm high, cabinets above and below 4 Sink, with drainboard 5 Toilet 6 Interview Area : 7 Desk 8 Cabinet, filing 6000 14900 9 Consult/Exam Room : 10 Examination bed 11 Table, Mayo 12 Footstool 13 Lamp, gooseneck 14 Counter, cabinets below 15 Sink 16 Negatoscope 17 Waste bin 18 Concealed floor drain 19 Storage/Supply Room 4300 4400 3100 3100 SD SD SD 1 2 3 4 5 6 7 2 2 8 9 7 2 2 10 11 12 13 14 15 16 17 18 18 18 17 17 19 CH CH D T 9 7 2 2 10 11 12 13 14 15 16 17 18 SD 2 4 3 8 8 2 2 2 239


Department: Room Title: OUTPATIENT STAFF PANTRY & LOUNGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. OPD staff make use of toilet facilities Electric fan 1 b. OPD staff eat during breaks Waste bin w/ black lining 1 c. Staff reads, writes and uses telephone d. Staff rests while awaiting their shifts People Involved: FURNITURE AND QUANTITY REMARKS OPD staff and doctors FIXTURE CHECKLIST Sofa, 2-seater 1 Chair, dining 6 Table, 6-seater 1 Table, side 1 Counter, 900mm high, 1 cabinets above and below Sink, with drainboard 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & QUANTITY REMARKS Planning Relationships: ENGINEERING TERMINALS a. Accesible from all OPD facilities Window curtain rail 1 Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots Outlet, 10A, 2P 240V, single 1 for emergency light Smoke detector 2 REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-14A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 240


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT STAFF PANTRY & LOUNGE 250B-OPD-RDS-14B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 35 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit OPD staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 241


KEY SCALE 1:100 M 1 Sofa, 2-seater 2 Chair, dining 3 Table, 6-seater 4 Table, side 5 Counter, 900mm high, cabinets above and below 6 Sink, with drainboard 7 Waste bin 8 Concealed floor drain 3000 6000 1 3 4 5 6 7 8 SD 2 2 2 2 2 2 242


Department: Room Title: OUTPATIENT PUBLIC TOILETS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient, patient's companions, hospital visitors makes Waste bins, foot-controlled 2 use of toilet facilities Exhaust fans 2 People Involved: FURNITURE AND Patients FIXTURE CHECKLIST Patients' companions Counter, open below; with 2 Hospital visitors vanity mirror Lavatory, over-the-counter 4 Water closet 5 Partition, cubicle, with door 5 Slop sink 2 Partition, urinal 2 Urinal 2 Floor drain 2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Accessible from all OPD facilities Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots Outlet, 10A, 2P 240V, single 1 for emergency light Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OPD-RDS-15A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 243


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OUTPATIENT PUBLIC TOILETS 250B-OPD-RDS-15B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit general public Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 244


KEY SCALE 1:100 M 1 FEMALE PUBLIC TOILET: 2 Counter, open below; with vanity mirror 3 Lavatory, over-the-counter 4 Water closet 5 Partition, cubicle, with door 6 Slop sink 3100 6000 7 MALE PUBLIC TOILET: 8 Partition, urinal 9 Urinal 10 Waste bin, general 11 Floor drain 2 1 3 3 4 5 5 6 4 4 10 2 3 3 4 4 5 5 6 8 9 8 9 7 11 11 10 SH SH 3100 5 245


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient may arrive on foot Examination light 1 b. Patient may arrive on wheelchair Sphygmomanometer 1 c. Transfer patient to/from wheelchair to examining Examination bed 1 table and vice versa Gooseneck lamp 1 d. Clinical handwashing Stethoscope 1 e. Use of monitoring/diagnostic equipment IV stand with IV fluid 1 f. Medical, surgical, nursing and first aid Sharps collector, puncture- 1 activities proof container

Footstool 1 Waste bin, black lining 1 Waste bin, yellow lining 1 specific clinic type FURNITURE AND FIXTURE CHECKLIST Desk 1 People Involved: Chair, upright, stacking 3 1 x Physician Cabinet, steel, filing 2 1 x Nurse or secretary Counter, 900mm high, cabinets 1 1 x Patient above and below

Sink, w/ gooseneck faucet 1

Concealed floor drain 1 specific clinic type ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 6 grounding type, Planning Relationships:

universal slots a. Close to other Ancillary Services Outlet, 10A,2P,240V, single 1 for emergency light

Outlet, data 1 This activity space provides facilities needed for Outlet, telephone 1

the delivery of general patient care Smoke detector 1 Cubicle curtain rail 1 specific clinic type Hospital: CLINIC (TYPICAL) 250-Bed (Level 3) Note: provide terminals and related accessories necessary to Note: provide other equipment and accessories necessary to Note: provide other furniture and fixture necessary to QUANTITY REMARKS QUANTITY REMARKS ROOM DATA SHEET OUTPATIENT Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Reference Sheet Number: QUANTITY REMARKS April 2016 250B-OPD-RDS-16A Updated Reference: 246


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit patient and medical staff Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET April 2016 250B-OPD-RDS-16B OUTPATIENT CLINIC (TYPICAL) 247


SD KEY SCALE 1:100 M 1 Desk 2 Chair, upright, stacking 3 Cabinet, steel, filing 4 Examination bed 5 Footstool 6 Examination light 7 Counter, 900mm high, cabinets above and below 8 Sink, with gooseneck faucet; stainless steel 9 Cart, supply 10 Sharps container 11 Cubicle curtain with rod 12 Waste bin 13 Concealed floor drain 3000 6000 1 2 3 6 4 5 9 10 7 8 12 13 11 2 2 3 D T 12 CH 248


Department: Room Title: AMBULATORY SURGERY CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient enters room with relative/companion Computer with monitor and 1 (Patient may be ambulant, in a wheelchair, printer

or on a stretcher) Waste bin 1 b. Patient approaches reception counter and registers / companion registers for patient c. Patient waits for his/her turn: consultation, examination, procedure, etc. d. Patient gets called for his/her turn e. Clinical handwashing f. Use of monitoring/diagnostic equipment g. Surgical activities People Involved: FURNITURE AND Patients FIXTURE CHECKLIST Relatives/companions Chair, swivel 1 Nurse Chair, visitor 1 Nursing attendant Chair, gang-type 2 Desk 1 Cabinet, steel, filing 3 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Accesible to ancillary services Outlet, 10A,2P,240V, duplex 4 grounding type, b. Near Consult/Exam Room

universal slots c. Near Treatment Room Outlet, 10A,2P,240V, single 1 emergency light Outlet, telephone outlet 1 Outlet, data 1 Smoke detector 1

Window curtain rail 1 RECEPTION/ WAITING AREA April 2016 250B-ASC-RDS-01A QUANTITY REMARKS QUANTITY REMARKS REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 249


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: AMBULATORY RECEPTION/ SURGERY CLINIC WAITING AREA TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ASC patients and staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 250B-ASC-RDS-01B 250 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 3000 6000 1 Desk, 600 x 1200mm 2 Chair, swivel 3 Chair, visitor 2 1 SD T D 3 4 4 5 6 4 Chair, gang-type 5 Cabinet, steel; filing 6 Waste bin 5 5 251


Department: Room Title: AMBULATORY SURGERY CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient enters room with relative/companion Examination table/bed 2 (Patient may be ambulant, in a wheelchair, Examination lamp 2 or on a stretcher) Instrument cart 2 b. Clinical handwashing Suction apparatus 2 c. Use of diagnostic equipment Glucometer 2 d. Patient is treated for minor injuries and/or illness Negatoscope 2 e. Transfer of patient to ASC Recovery Room, or Thermometer, non-mercurial 2 Operating Room, or be discharged Sphygmomanometer, non-mercurial 2 Neuro hammer 2 Stethoscope 2 IV Stand 2 Suture removal set, surgical 1 each set, ortho set, EENT People Involved: diagnostic set, etc. 2 x Patients Pulse oximeter 2 2 x Nurses Waste bins, various types 6 2 x Nursing Attendants FURNITURE AND 2 x Physicians FIXTURE CHECKLIST Footstool 2 Table, side 2 Cubicle curtain and rod 2 Lavatory, wall-hung 2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Near Waiting Area Outlet, 10A,2P,240V, duplex 9 grounding type, b. Near Ambulatory Surgery Clinic Operating Room

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, telephone outlet 1 Smoke detector 2 Window curtain rail 2

Window curtain rail Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: TREATMENT ROOM April 2016 250B-ASC-RDS-02A QUANTITY REMARKS QUANTITY REMARKS REMARKS QUANTITY 252


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: AMBULATORY SURGERY CLINIC TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 5,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:DESIRABLE:unnecessary Pressure: Emergency light ESSENTIAL:DESIRABLE:unnecessary % Dust filtration 93%-99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.5 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff, patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 250B-ASC-RDS-02B TREATMENT ROOM 253 Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary


3000 6000 3000 6000 KEY SCALE 1:100 M 1 Examination table 2 Table, side; 400 x 500mm 3 Footstool 4 Instrument cart 5 Examination lamp 6 Lavatory, wall-hung 7 Negatoscope 8 Cubicle curtain and rod 9 Waste bin 1 T SD 2 3 9 4 5 6 7 8 1 SD 2 3 9 4 5 6 7 8 254


Department: Room Title: AMBULATORY SURGERY CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient enters room with relative/companion Examination table/bed 1 (Patient may be ambulant, in a wheelchair, Examination lamp 1 or on a stretcher) Instrument cart 1 b. Doctor examines patient records Opthalmoscope 1 c. Clinical handwashing Otoscope 1 d. Doctor examines patient using Negatoscope 1 monitoring/diagnostic equipment Thermometer, non-mercurial 1 e. Surgical activities Sphygmomanometer, non-mercurial 1 Neuro hammer 1 Stethoscope 1 IV Stand 1 Suture removal set, etc. 1 each Waste bins, various types 3 People Involved: 1 x Patient FURNITURE AND 1 x Nurse FIXTURE CHECKLIST 1 x Nursing Attendant Desk 1 1 x Physician Chair, swivel 1 Chair, visitor 1 Stool, adjustable height 1 Footstool 1 Table, side 1 Counter, w/ cabinets 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Near Waiting Area Outlet, 10A,2P,240V, duplex 5 grounding type, b. Near Treatment Room

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, telephone outlet 1 Outlet, data 1 Smoke detector 1

Window curtain rail 1 CONSULT/ EXAM April 2016 250B-ASC-RDS-03A QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 255 c. Near Ambulatory Surgery Clinic Operating Room Sink, stainless steel
1


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: AMBULATORY SURGERY CLINIC TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff, patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 250B-ASC-RDS-03B CONSULT/ EXAM 256 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


3000 KEY SCALE 1:100 M 6000 SD T D CH 1 2 3 6 5 7 9 10 4 12 14 16 15 13 11 1 Desk, 600 x 1200mm 2 Chair, swivel 3 Chair, visitor 4 Stool, adjustable height 5 Table, side; 400 x 500mm 6 Examination table 7 Footstool 8 Counter, with cabinets below 9 Sink, stainless steel 10 Examination lamp 11 Instrument cart 12 Negatoscope 13 Cubicle curtain and rod 14 Concealed floor drain 15 Waste bin, infectious 16 Waste bin, pathological and anatomical 17 Sharps container 15 17 8 257


Department: Room Title: AMBULATORY SURGERY CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient enters room to change into Gown 1 gown; clean linen from cabinet Waste bin 1 b. Toileting activities c. After procedure / discharge from Recovery Room, patient returns to dressing room cubicle and changes back into own clothing; soiled linen is placed in hamper People Involved: FURNITURE AND Patients FIXTURE CHECKLIST Relatives/companions Chair, upright; stacking 2 Shelf, for clean linen 1 Hamper, for soiled linen 1 Cubicle curtain and rod 2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Near Waiting/Reception Area Outlet, 10A,2P,240V, duplex 2 grounding type, b. Near Treatment Room

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1 REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: PATIENT DRESS/ TOILET April 2016 250B-ASC-RDS-04A QUANTITY REMARKS REMARKS QUANTITY QUANTITY 258


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: AMBULATORY SURGERY CLINIC TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) NA Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ASC patients and staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 250B-ASC-RDS-04B PATIENT DRESS/ TOILET 259 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 1 Cubicle curtain and rod 2 Low partition, 1800mm high 3 Chair, upright; stacking 4 Hamper, soiled linen 5 Shelf, clean linen 4000 4500 1 SD 1500 2 4 1 2 3 3 5 260


Department: Room Title: AMBULATORY SURGERY CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Physician and nurses wash hands and arms Soap dispenser 3 with water and soap before and after Hand dryer 1 surgical operation / procedure in the Operating Room Waste bin 1 b. Use of hand dryer Clock 1 People Involved: FURNITURE AND 1 x Physician FIXTURE CHECKLIST 1 x Nurse Scrub sink, 3-station; with 1 goose-neck spout and

foot-control

Shelves, overhead 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Operating Room Outlet, 10A,2P,240V, duplex 2 grounding type, b. Near Staff Dress & Toilet

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1

April 2016 250B-ASC-RDS-05A QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: SCRUB-UP AREA 261


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: AMBULATORY SURGERY CLINIC TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 23 Night illumination (LUX) 250 Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 30 Standby light essential:desirable:UNNECESSARY Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.6 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at scrub sink tolerated Maximum temperature (°C) 70 Access limit ASC medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 250B-ASC-RDS-05B SCRUB-UP AREA 262 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 2500 1 3-Station scrub sink, with goose- neck spout & foot control, sensor type 2 Soap dispenser 3 Hand dryer 2700 SD 1 2 3 4 6 7 5 4 Shelves, overhead 5 Waste bin 6 Clock 7 Concealed floor drain 263


Department: Room Title: AMBULATORY SURGERY CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Physician and nurses wash hands and arms Soap dispenser 3 with water and soap before and after Hand dryer 1 surgical operation / procedure in the Operating Room b. Use of hand dryer People Involved: FURNITURE AND 1 x Physician FIXTURE CHECKLIST 1 x Nurse Double compartment laundry 1 sink w/ drainboard Shelves, overhead 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Operating Room Outlet, 10A,2P,240V, duplex 2 grounding type, b. Near Staff Dress & Toilet

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1

Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: April 2016 250B-ASC-RDS-06A QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS CLEAN-UP AREA 264 Waste bin, infectious 1 Waste bin, pharmaceutical 1 Sharps container 1 Hamper, soiled linen 1 Clock 1


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: AMBULATORY SURGERY CLINIC TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 23 Night illumination (LUX) 250 Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 30 Standby light essential:desirable:UNNECESSARY Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.6 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at scrub sink tolerated Maximum temperature (°C) 70 Access limit ASC medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 250B-ASC-RDS-06B CLEAN-UP AREA 265 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 2500 3300 SD 1 2 3 5 4 6 7 1 Counter, with cabinets above and below 2 Double compartment laundry sink with drainboard 3 Hamper, soiled linen CH 4 Waste bin, infectious 5 Waste bin, pharmaceutical 6 Sharps container 7 Concealed floor drain 266


Department: Room Title: AMBULATORY SURGERY CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives in a stretcher trolley Stretcher bed 3 b. Patient is transferred from stretcher trolley to bed Outlet, oxygen; wall-mounted 3 per bed; 1.6m high c. Regular monitoring of patient's vital signs Outlet, suction; wall-mounted 3 per bed; 1.6m high d. Use of monitoring and diagnostic equipment Suction apparatus 3 per bed; 1.6m high e. Patient is transferred to wheelchair and Cart, instrument 1 discharged from Ambulatory Surgery Clinic Clock 1 Waste bin, general 1 Waste bin, infectious 1 Waste bin, pharmaceutical 1 Sharps container 1 People Involved: FURNITURE AND 3 x Patient FIXTURE CHECKLIST 1 x Nurse Desk 1 1 x Nursing Attendant Table, side 3 1 x Physician Chair, upright; stacking 1 Chair, visitor 2 Cabinet, steel; filing 2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 10 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, telephone outlet 1 Outlet, data 1

Nurse Call System 1 Bed light 3 per bed;

at bed head Smoke detector 1

Window curtain rail 2 April 2016 250B-ASC-RDS-07A QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS RECOVERY ROOM Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 267 a. Near Ambulatory Surgery Clinic Operating Room


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: AMBULATORY SURGERY CLINIC TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature 23 Night illumination (LUX) 100 Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.5 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at toilet lavatory tolerated Maximum temperature (°C) 70 Access limit ASC medical staff, patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 250B-ASC-RDS-07B RECOVERY ROOM 268 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


SD 1 2000 5000 7000 KEY SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Chair, upright; stacking 3 Chair, visitor 4 Cabinet, steel; filing 5 Table, side; 400 x 500mm 6 Stretcher/hospital bed 7 Instrument cart 8 Clock 9 Waste bin, general 10 Waste bin, infectious 11 Waste bin, pharmaceutical 12 Sharps container 6000 T D 2 3 3 4 4 5 6 7 9 10 12 11 9 6 5 6 5 8 269


Department: Room Title: AMBULATORY SURGERY CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on wheelchair or stretcher trolley Operating table 1 b. Patient is transferred to operating table Operating lamp 1 c. If necessary, anesthesia is administered, Anesthesia unit 1 w/ scavenging sys d. Clinical handwashing Suction apparatus 1 e. Use of diagnostic equipment Negatoscope 1 f. Pre-operative care is given to the patient Mayo table 1 g. Patient is surgically operated on Anesthesist's table 1 h. After procedure/operation, patient is stabilized Instrument table 1 and wheeled out of the room Pack table 1 Single basin stand 1 Double basin stand 1

Kick bucket 1

Medical gas unit 1 Oxygen, Nitrogen People Involved: Tracheostomy, surgical, ortho set 1 each 1 x Patient Laryngoscope 1 1 x Nurse, circulatory Cardiac monitor w/ pulse oximeter 1 1 x Nurse, scrub Defibrillator 1 2 x Physicians Sphygmomanometer, non-mercurial 1 1 x Anesthesiologist FURNITURE AND FIXTURE CHECKLIST Footstool 2 Stool, adjustable 1 Stool, anesthetist's 1 Shelf 1 Clock 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Scrub-Up Area ENGINEERING TERMINALS b. Near Recovery Room Outlet, 10A,2P,240V, duplex 10 grndg type, univ'l Outlet, 10A,2P,240V, single 1 emergency light Outlet, telephone outlet 1 Outlet, data 1 Smoke detector 1

Isolation monitor 1 1600mm fr FFL Grounding terminal 4 duplex Heat detector 1 hospital grade Window curtain rail 2 QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: April 2016 250B-ASC-RDS-08A REMARKS QUANTITY OPERATING ROOM QUANTITY REMARKS 270


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: AMBULATORY SURGERY CLINIC TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 700 - 1,000 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 20,000 - 40,000 Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.5 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff, patients Fire risk low : medium: HIGH Other risks NA ROOM DATA SHEET April 2016 250B-ASC-RDS-08B OPERATING ROOM 271 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) 10 View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 6000 6000 1 Operating table 2 Operating lamp 3 Mayo table 4 Footstool 5 Instrument table 6 Single basin stand 7 Double basin stand 8 Anesthetist's stool 9 Adjustable stool 10 Anesthetist's table 11 Anesthesia unit 12 Kick bucket 13 Shelf, adjustable 14 Pack table 15 Clock 16 Double film negatoscope 17 Floor clean-out 18 Door; with vision panel SD T D 1 2 3 4 4 5 6 8 9 7 10 11 12 13 14 15 16 17 18 9 272


Department: Room Title: AMBULATORY SURGERY CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Washing of instruments Sterilizer, dressing 1 b. Sterilizing of instruments Sterilizer, hot air 1 c. Preparation of sterilized instruments for Sterilizer, instrument 1 w/ scavenging sys future use Autoclave 1 Rack, glove drying 1 Sharps container 1 People Involved: FURNITURE AND 1 x Sterilization Room Staff FIXTURE CHECKLIST 1 x Nurse Counter, with cabinets 1 1 x Nursing Attendant above and below

Sink, deep; with drainboard 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Near Ambulatory Surgery Clinic Operating Room ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 5 grounding type, and Supply Storage Room

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 1

  • Note : provide circuit breaker/s

    where necessary April 2016 250B-ASC-RDS-09A REMARKS QUANTITY STERILIZATION ROOM QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS 273 b. Near Ambulatory Surgery Clinic Sterile Instrument


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: AMBULATORY SURGERY CLINIC TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit ASC medical/service staff Fire risk LOW: medium: high Other risks exposure to hazardous chemicals ROOM DATA SHEET April 2016 250B-ASC-RDS-09B STERILIZATION ROOM 274 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


3500 KEY SCALE 1:100 M 1 Counter, with cabinets above and below 2 Deep sink with drainboard 3 Sterilizer, dressing 4 Sterilizer, hot air 5 Sterilizer, instrument 1 SD 2 9 10 CH 3400 5 6 3 4 8 6 Autoclave 7 Rack, glove drying 8 Sharps container 9 Door, with vision panel 10 Concealed floor drain CH 7 275


Department: Room Title: AMBULATORY SURGERY CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of sterilized/washed instruments b. Dispensing of supplies in ASC c. Inventory of instruments and supplies

People Involved: FURNITURE AND 1 x Sterilization Room Staff FIXTURE CHECKLIST Shelves 1 Cabinet 3 Cart 1 Planning Relationships: ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 2 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 1

Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: April 2016 250B-ASC-RDS-10A REMARKS QUANTITY STERILE INSTRUMENT SUPPLY & STORAGE ROOM QUANTITY REMARKS QUANTITY REMARKS 276 a. Near Ambulatory Surgery Clinic Operating Room b. Near Ambulatory Surgery Clinic Sterilization Room


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: AMBULATORY SURGERY CLINIC TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ASC medical/service staff Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET April 2016 250B-ASC-RDS-10B STERILE INSTRUMENT SUPPLY & STORAGE ROOM 277 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


3500 KEY SCALE 1:100 M 2600 1 Shelves, 450mm deep 2 Cabinet; instrument, etc. 3 Cart, instrument 4 Door, with vision panel SD 4 1 2 2 2 3 278


12000 12000 CONSULT/ EXAM INFO/ RECEPTION WAITING AREA TREATMENT AREA T T GYM AREA SUPPLY SCALE 1:300 M 279


Department: Room Title: PHYSICAL REHAB RECEPTION & WAITING FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST

White board 1 Waste bin, w/ black or 2 visitors.

People Involved: FURNITURE AND 1 x Receptionist FIXTURE CHECKLIST Patients, relatives, and visitors Counter, two-level
1 Chair, upright, stacking 2 Chair, gang-type 2 Cabinet, filing, steel 1

Planning Relationships: ADDITIONAL EQUIPMENT & a. Preferably near the Main Hospital Lobby ENGINEERING TERMINALS b. Preferably at the Ground Floor Window curtain rail 1

Outlet, 10A, 2P, 240V, duplex 6 grounding type, universal slots ACU, window/split type 1 Outlet, intercom 1 wall-mounted Outlet, Telephone 1 desktop Outlet, Data 1 Smoke Detector 1 Ionization type Hospital: Reference Sheet Number: 250B-PR-RDS-01A QUANTITY REMARKS QUANTITY REMARKS 250-Bed (Level 3) QUANTITY REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 280 a. Reception/waiting area for patients, relatives, and colorless lining


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PHYSICAL REHAB RECEPTION & WAITING 250B-PR-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Phys Rehab staff, patients, visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 281 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


SCALE 1:100 M 1 Counter, 2-level 2 Chair; upright, stacking 3 Chair; gang-type KEY 4 White board 5 Waste bin 6 Wheelchair park/area 1 2 3 4 6 5 SD D T 6600 3000 3 CH 2 282


Department: Room Title: PHYSICAL REHAB CONSULT/EXAM ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST

Sphygmomanometer, non-mercurial 1 Examination table 1 Negatoscope 1 Waste bin, general 1 c. Patient is transferred to/from wheelchair or stretcher trolley to examination bed and vice versa d. Clinical handwashing FURNITURE AND e. Use of monitoring/diagnostic equipment FIXTURE CHECKLIST f. Medical, nursing, and related activities Chair, upright, stacking 3 Table, side, 400 x 400mm 1 Foot stool 1

People Involved: 1 x Physician 1 x Nurse 1 x Patient, relatives, and visitor Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Waiting Area/Reception ENGINEERING TERMINALS b. Adjacent to Treatment/Patient Area Window curtain rail 1

Outlet, 10A, 2P, 240V, duplex 5 grounding type, universal slots ACU, window/split type 1 Outlet, intercom 1 wall-mounted Outlet, Telephone 1 desktop Outlet, Data 1 Smoke Detector 1 Ionization type 250-Bed (Level 3) QUANTITY REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: Reference Sheet Number: 250B-PR-RDS-02A QUANTITY REMARKS QUANTITY REMARKS 283 b. Patient may arrive on wheelchair or stretcher trolley a. Patient may arrive on foot. Desk, 600 x 1200mm 1


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PHYSICAL REHAB CONSULT/EXAM ROOM 250B-PR-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Phys Rehab staff, patients, visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 284 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


2100 KEY 4000 KEY SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Chair; upright, stacking 3 Table, side, with cabinet below 4 Examination table 5 Footstool 6 Negatoscope 7 Waste bin, general SD 1 T D 2 3 4 5 6 7 2 2 285


Department: Room Title: PHYSICAL REHAB TREATMENT/GYM AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST

Ultrasound 3 a. Patient may arrive on foot. Exercise bike 2 b. Patient may arrive on wheelchair or stretcher Parallel bar, adjustable 1 trolley Stair exerciser 1 c. Patient is transferred to/from wheelchair or Pulley system, wall mounted 1 stretcher trolley to plinth, or therapy equipment Waste bin, general 2 and vice versa FURNITURE AND d. Use of therapeutic equipment FIXTURE CHECKLIST e. Therapeutic activities Chair, upright, stacking

Table, side, with cabinet below 3 Counter, with sink, and cabinets 1 above and below

Lavatory, wall-mounted 1 People Involved: Concealed floor drain 1 5-7 x Physical Therapists 5-7 x Patients relatives, visitors ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Planning Relationships: Window curtain rail 1 a. Adjacent to Waiting Area/Reception Outlet, 10A, 2P, 240V, duplex 15 grounding type, b. Adjacent to Toilets/Dress Cubicles universal slots ACU, split type 2 Outlet, intercom 1 wall-mounted Outlet, Telephone 1 desktop Smoke Detector 2

Ionization type Hospital: Reference Sheet Number: 250B-PR-RDS-03A QUANTITY REMARKS QUANTITY REMARKS 250-Bed (Level 3) QUANTITY REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 286 Plinth 3


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PHYSICAL REHAB TREATMENT/GYM AREA 250B-PR-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary Humidity 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Phys Rehab staff, patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 287 Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary


KEY SCALE 1:200 M 1 TREATMENT AREA 2 Plinth 3 Chair, upright, stacking 4 Table, side 5 Cubicle curtain with rod 6 GYM AREA 7 Counter, with cabinets above and below 8 Sink, stainless steel 9 Lavatory, wall-hung SD 7 10 Ergometer 11 Parallel bars 12 Exercise/training stairs 13 Pulley exerciser, wall-mounted 14 Mirror, full-size 15 Clock 16 Waste bin 17 Concealed Floor Drain 18 STORAGE ROOM 8 12000 6100 2900 4900 5400 1700 SD SD 3 3 3 3 2 4 5 1 2 3 5 2 5 6 9 10 10 11 12 13 14 14 15 16 16 18 TD CH 3 3 4 3 4 3 17 288


Department: Room Title: PHYSICAL REHAB TOILETS, DRESS CUBICLES & SOILED LINEN AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST

Waste bin, general 2 a. Patient makes use of toilet facilities b. Patient makes use of dressing cubicles

c. Soiled/used linen is placed in hamper

FURNITURE AND FIXTURE CHECKLIST Water closet w/ spray hose 2 Lavatory 2 People Involved: Floor strainer 2 Physical Rehab patients and staff Grab bar, wall-mounted 2

Curtain rail with rod 2

Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Waiting Area/Reception ENGINEERING TERMINALS b. Adjacent to Treatment/Patient Area Window curtain rail 2

Outlet, 10A, 2P, 240V, duplex 2 grounding type, universal slots Smoke Detector 1 Ionization type

Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) QUANTITY REMARKS Reference Sheet Number: 250B-PR-RDS-04A QUANTITY REMARKS QUANTITY REMARKS 289 Hamper, linen 1


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PHYSICAL REHAB TOILETS, DRESS CUBICLES & SOILED LINEN AREA 250B-PR-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) NA Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Phys Rehab staff, patients, visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY 290


1900 KEY 1350 KEY SCALE 1:100 M SD 1 1 MALE TOILET 2 Waste bin 3 FEMALE TOILET 4 DRESS CUBICLE 5 Cubicle curtain and rod 6 SOILED LINEN HOLDING 7 Linen hamper, for soiled linen 2150 1900 3 2 2 4 5 4 5 5 7 6 1900 291 250B-PR-RDS-04C


UP 18000 12000 CONSULT 6000 6000 INFORMATION/ ADMITTING WAITING AREA DIALYSIS TREATMENT AREA ISOLATION TOILET PANTRY STORAGE RE- PROCESSING ROOM WATER TREATMENT ROOM SCALE 1:300 M 292


Department: Room Title: DIALYSIS INFORMATION, ADMITTING & WAITING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Information/Admitting area for patients, relatives, White board, wall mounted 1 and visitors Waste bin, w/ black or 1 b. Waiting area for patients, relatives, and visitors. colorless lining

c. Maintenance of OPD register People Involved: FURNITURE AND 1 x Receptionist FIXTURE CHECKLIST Patients, relatives, and visitors Desk, 600 x 1200mm 1 Chair, upright, stacking 3 Chair, gang-type 3 Cabinet, filing, steel 2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Near/accesible from the Main Hospital Lobby Outlet, 10A, 2P, 240V, duplex 7 grounding type,

universal slots ACU, window/split type 1 Outlet, Intercom 1 wall-mounted Outlet, Telephone 1 desktop Outlet, Data 1

Smoke Detector 2 Ionization type 250B-DIA-RDS-01A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 293


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DIALYSIS INFORMATION, ADMITTING & WAITING AREA 250B-DIA-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light ESSENTAIL:desirable:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Dialysis staff, patients, visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 294 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


8900 SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Chair; upright, stacking 3 Chair; gang-type 4 Cabinet, filing, steel KEY 5 White board 6 Waste bin 7 Wheelchair park/area 3700 1 2 2 2 3 3 3 4 4 6 5 7 7 SD SD D T 295


Department: Room Title: DIALYSIS CONSULT ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient may arrive on foot. Sphygmomanometer, non-mercurial 1 b. Patient may arrive on wheelchair or stretcher Examination table 1 trolley Waste bin, general 1 c. Patient is transferred to/from wheelchair or stretcher trolley to examination bed and vice versa d. Clinical handwashing e. Use of monitoring/diagnostic equipment f. Medical, nursing, and related activities People Involved: FURNITURE AND 1 x Physician FIXTURE CHECKLIST 1 x Nurse Desk, 600 x 1200mm 1 1 x Patient, relatives, and visitor Chair, upright, stacking 3 Cart, supply 1 Foot stool 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Info/Admitting Area Window curtain rail 1 b. Near dialysis treatment area Outlet, 10A, 2P, 240V, duplex 5 grounding type, universal slots ACU, window/split type 1 Outlet, intercom 1 wall-mounted Outlet, Telephone 1 desktop Outlet, Data 1 Smoke Detector 1 Ionization type 250B-DIA-RDS-02A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 296


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DIALYSIS CONSULT ROOM 250B-DIA-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Dialysis staff, patients, visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 297 Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary


3700 KEY 3100 KEY SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Chair; upright, stacking 3 Cart, supply 4 Examination table 5 Footstool 6 Waste bin, general SD 1 T D 2 2 2 3 4 5 6 298


Department: Room Title: DIALYSIS DIALYSIS TREATMENT AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient may arrive on foot. Weighing scale, floor-type 1 b. Patient may arrive on wheelchair or stretcher Dialysis machine 8 trolley Bed, trolley/stretcher 5 c. Patient is weighed; weight and vital signs are Chair, dialysis; reclinable 3 recorded Emergency cart 1 d. Patient is transferred to/from wheelchair to Waste bin, general 2 dialysis chair, or stretcher trolley and vice versa e. Use of dialysis equipment f. Monitoring of dialysis treatment People Involved: FURNITURE AND 1 x Physician-on-duty FIXTURE CHECKLIST 2 x Nurse Chair, upright, stacking 3 8 x Patients Counter, with sink, and cabinets 1 relatives, visitors below

Lavatory, wall-mounted 2 White board 1 Clock 1 Cubicle curtain and rod 8 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Information/Admitting Area Window curtain rail 1 Outlet, 10A, 2P, 240V, Duplex 22 grounding type, universal slots Outlet, 10A, 2P, 240V, Single 1 for emergency light ACU, Split type 2 Outlet, Intercom 1 at Nurse Station Outlet, Telephone 1 at Nurse Station Smoke Detector 2 Ionization type QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-DIA-RDS-03A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 299 Counter, two-level 1


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DIALYSIS DIALYSIS TREATMENT AREA 250B-DIA-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary Humidity 50 Black out essential:desirable:UNNECESSARY Cooling load (TR)

SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: at sink & lavatory tolerated Maximum temperature (°C) 70 Access limit Dialysis staff, patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 300 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:200 M 1 Counter, 2-level; with cabinets below 2 Chair; upright, stacking 3 Weighing scale, floor-type 4 Dialysis machine 5 Bed, trolley / stretcher 6 Chair, dialysis; adjustable back, fully reclinable 8300 12000 SD 1 T D 7 Emergency cart 8 Cubicle curtain and rod 9 Lavatory, wall-hung 10 Sink, stainless steel 11 Waste bin 12 White board 13 Clock 6000 6000 2 2 10 2 3 4 5 6 2 4 2 4 5 2 4 5 2 4 5 2 4 5 6 2 4 6 2 4 9 11 9 11 8 8 8 8 SD SD CH CH CH 13 12 7 8 8 8 8 2 3800 12100 301


Department: Room Title: DIALYSIS ISOLATION ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient may arrive on foot. Dialysis machine 1 b. Patient may arrive on wheelchair or stretcher Bed, trolley/stretcher 1 trolley Waste bin, general 1 c. Patient is weighed; weight and vital signs are recorded d. Patient is transferred to/from wheelchair to dialysis chair, or stretcher trolley and vice versa e. Use of dialysis equipment f. Monitoring of dialysis treatment g. Observance of infection control protocol for isolated patient People Involved: FURNITURE AND 1 x Physician FIXTURE CHECKLIST 1 x Nurse Chair, upright, stacking 1 1 x Patient, relatives, and visitor Lavatory, wall-mounted 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Information/Admitting Area Window curtain rail 1 b. Near Dialysis Treatment Area Outlet, 10A, 2P, 240V, duplex 4 grounding type, universal slots ACU, window/split type 1

Smoke Detector 1 Ionization type 250B-DIA-RDS-04A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 302


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DIALYSIS ISOLATION ROOM 250B-DIA-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature 23 Night illumination (LUX) 50 Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary Humidity 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.75 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit Dialysis staff, patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET Negative Pressure (Pa) 10 Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary 303


KEY SCALE 1:100 M 1 Bed, trolley / stretcher 2 Chair, upright; stacking 3 Dialysis machine 4 Lavatory, wall-hung 5 Waste bin, general 4000 3000 SD 2 1 3 4 5 304


Department: Room Title: DIALYSIS JAN CLO., SOILED LINEN & WASTE HOLDING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST

  1. Janitor's Closet Counter, with deep sink 1 a. Storage of janitor's cleaning tools Mop rack 1 b. Use of slop sink for cleaning of tools/implements Mop bucket 1

Linen hamper 2 medical 2. Waste Holding Area Waste bin, color-coded 4 mobile a. Storage of different types of waste : general (biodegradable & non-biodegradable), infectious, sharps 3. Soiled Linen Area a. Holding area for soiled linen People Involved: FURNITURE AND Dialysis staff FIXTURE CHECKLIST Janitor/Utility staff Slop sink 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Dialysis Treatment Area Window curtain rail 1

Outlet, 10A, 2P, 240V, duplex 3 grounding type,

universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke Detector 2 Ionization type QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-DIA-RDS-05A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 305


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DIALYSIS JAN CLO., SOILED LINEN & WASTE HOLDING AREA 250B-DIA-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Dialysis staff, utility staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 306 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


3000 KEY 1600 KEY SCALE 1:100 M SD 1 JANITOR'S CLOSET : 1 Counter, with top and bottom cabinets 2 Sink, stainless steel 3 Slop sink, with faucet bibb 4 Concealed floor drain 5 Mop rack 6 Mop bucket, with casters 2 1700 800 SD 3 5 6 7 7 8 CH 4 SOILED LINEN AREA : 7 Linen hamper, for soiled linen WASTE HOLDING AREA : 8 Waste bin, green lining 9 Waste bin, black lining 10 Waste bin, yellow lining 11 Waste bin, for sharps; puncture-proof 9 10 11 4100 307


Department: Room Title: DIALYSIS PANTRY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Dialysis staff makes use of the pantry Refrigerator 1 b. Dialysis patients make use of the pantry Counter, with sink 1 c. Dialysis staff does clean up activities Waste bin, general 1

Waste bin, biodegradable 1 medical People Involved: FURNITURE AND Dialysis staff FIXTURE CHECKLIST Dialysis patients Concealed floor drain 1 Patient relatives, visitors ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Near dialysis treatment area Outlet, 10A, 2P, 240V, duplex 3 grounding type,

universal slots Smoke Detector 1 Ionization type 250B-DIA-RDS-06A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 308


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DIALYSIS PANTRY 250B-DIA-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary Humidity 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Dialysis staff, patients, visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 309 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


3100 KEY 3000 KEY SCALE 1:100 M SD 1 1 Counter, with top and bottom cabinets 2 Sink, stainless steel 3 Concealed floor drain 4 Refrigerator 5 Waste bin, general 6 Waste bin, bio-degradable waste 4 2 3 5 CH 6 310


Department: Room Title: DIALYSIS REPROCESSING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Dialysis staff brings used dialyzer for reprocessing Reprocessing sterilizing machine 1 b. Staff does washing activities Dialyzer rack 2 c. Staff uses reprocessing sterilizing machine Waste bin, general 1 d. Reprocessed dialyzer is placed in dialyzer rack for storage e. Staff does clean up activities People Involved: FURNITURE AND Dialysis staff FIXTURE CHECKLIST Counter, with sink, and cabinets 1 above and below

Sink, deep 2 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Near dialysis treatment area Window curtain rail 1 Outlet, 10A, 2P, 240V, duplex 4 grounding type, universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke Detector 1 Ionization type QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-DIA-RDS-07A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 311


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DIALYSIS REPROCESSING ROOM 250B-DIA-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-1000 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:desirable:UNNECESSARY Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Dialysis staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 312 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 4100 2300 SD 1 2 5 6 1 Counter, with top and bottom cabinets 2 Sink, deep 3 Reprocessor sterilizing machine 4 Dialyzer rack 5 Waste bin, general 6 Concealed floor drain 2 CH 3 4 4 313


VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.4 ANCILLARY SERVICE FACILITIES PHARMACY 3.4.1 LABORATORY 3.4.2 BLOOD STATION 3.4.3 RADIOLOGY 3.4.4

First Edition DEPARTMENT OF HEALTH Manila 2017 315


Hospital: 250-Bed (Level 3) Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER 243.00 250B-PHAR-DDS-01 18.00 250B-PHAR-RDS-01 9.00 250B-PHAR-RDS-02 36.00 250B-PHAR-RDS-03 36.00 250B-PHAR-RDS-04 108.00 250B-PHAR-RDS-05 18.00 250B-PHAR-RDS-06 9.00 250B-PHAR-RDS-07 9.00 250B-PHAR-RDS-08 LABORATORY 454.00 250B-LAB-DDS-01 Waiting Area 82.00 250B-LAB-RDS-01 Reception/ Receiving/ Releasing 15.00 250B-LAB-RDS-02 Extraction Area 17.00 250B-LAB-RDS-03 Conference Room 23.00 250B-LAB-RDS-04 Pathology Office/ Library 26.00 250B-LAB-RDS-05 Chief Pathologist's Office 16.00 250B-LAB-RDS-06 Chemistry 44.00 250B-LAB-RDS-07 Hematology 23.00 250B-LAB-RDS-08 Serology/Immunology 23.00 250B-LAB-RDS-09 Microbiology/Bacteriology 43.00 250B-LAB-RDS-10 Microscopy 23.00 250B-LAB-RDS-11 Histopathology 26.00 250B-LAB-RDS-12 Blood Typing, Cross Matching, Post BTR 25.00 250B-LAB-RDS-13 Glass Washing 9.00 250B-LAB-RDS-14 Autoclave 9.00 250B-LAB-RDS-15 Staff Locker Room and T&B 37.00 250B-LAB-RDS-16 Staff Pantry 13.00 250B-LAB-RDS-17

HEALTH FACILITY Receiving/ Breakout/ Inspection Area Bulk Storage Service Facility Title: Department of Health ROOM TITLE Chief Pharmacist's Office DEVELOPMENT BUREAU PHARMACY Counseling Room 250B-AN-SFSI-01 ANCILLARY Reference Sheet Number: SERVICE FACILITY SHEET INDEX PAGE Dispensing Area & Drug Information Parenteral Admixture Room Extemporaneous Preparation Area Staff Pantry/ Lounge 317 319 320 323 326 329 332 335 338 341 344 345 348 351 354 357 360 363 366 369 372 375 378 381 384 387 390 393


Hospital: 250-Bed (Level 3) Hospital Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER 124.00 250B-BS-DDS-01 27.00 250B-BS-RDS-01 12.00 250B-BS-RDS-02 14.00 250B-BS-RDS-03 13.00 250B-BS-RDS-04 20.00 250B-BS-RDS-05 24.00 250B-BS-RDS-06 14.00 250B-BS-RDS-07 RADIOLOGY 479.00 250B-RAD-DDS-01 Sub-Lobby/ Waiting Area 86.00 250B-RAD-RDS-01 Clerical Room 19.00 250B-RAD-RDS-02 Chief Radiologist's Office 16.00 250B-RAD-RDS-03 Conference Room 21.00 250B-RAD-RDS-04 Reading Room 21.00 250B-RAD-RDS-05 Files Room 12.00 250B-RAD-RDS-06 Ultrasound Room 20.00 250B-RAD-RDS-07 Mammography Room 21.00 250B-RAD-RDS-08 Radiographic X-Ray Room 30.00 250B-RAD-RDS-09 Radiographic X-Ray Control Room 11.00 250B-RAD-RDS-10 Radiographic-Fluoroscopic X-Ray Room 37.00 250B-RAD-RDS-11 CT-Scan 45.00 250B-RAD-RDS-12 CT-Scan Control Room 11.00 250B-RAD-RDS-13 MRI Magnet Room 44.00 250B-RAD-RDS-14 MRI Control Room 32.00 250B-RAD-RDS-15 MRI System Component Room 14.00 250B-RAD-RDS-16 Dark Room 6.00 250B-RAD-RDS-17 Staff Lounge/ T&B 33.00 250B-RAD-RDS-18

ANCILLARY 250B-AN-SFSI-02 ROOM TITLE PAGE BLOOD STATION Waiting Area Screening & Assessment SERVICE FACILITY SHEET INDEX Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU Service Facility Title: Reference Sheet Number: Component Preparation Room Testing Room Blood Component Storage Blood Collection Room Staff Lockers, Pantry and T&B 318 396 397 400 403 406 409 412 415 418 419 422 425 428 431 434 437 440 443 446 449 452 455 458 461 464 467 470


12000 9000 3000 21000 3000 BULK STORAGE ROOM 3000 3000 3000 3000 6000 DISPENSING AREA RECEIVING/ BREAKOUT/ INSPECTION AREA STAFF PANTRY STAFF WORK AREA COUNSELING ROOM PARENTERAL ADMIXTURE EXTEMPORANEOUS PREPARATION AREA DISPENSING AREA CHIEF OFFICE SCALE 1:300 M 319


Department: Room Title: PHARMACY CHIEF PHARMACIST'S OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Pharmacist reads, writes, and uses intercom on his desk Computer w/ printer 1 b. Pharmacist stores, files and retrieves records Waste bin w/ black lining 1 c. Pharmacist receives visitors Waste bin w/ yellow lining 1 d. Pharmacist develops policies e. Pharmacist plans and coordinates activities f. Pharmacist requisitions drugs and medicines for actual procurements g. Pharmacist maintains and updates dangerous drug book (RA 9165) or the Comprehensive Dangerous Drugs Act of 2002 FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST Desk, 750mm x 1500mm 1 Junior executive chair 1 Chair, upright, stacking 2 Steel filing cabinet, 1 People Involved: 500mm x 700mm 1 x Pharmacist Cabinet, 400mm x 1200mm 1 for narcotics Desk return (extension) 1 Shelving, 300m x 1500mm 1 for narcotic drugs

ADDITIONAL EQUIPMENT & a. Close to Distribution Area ENGINEERING TERMINALS b. Close to Patient Dispensing Area Outlet, 10A,2P,240V, duplex 6 grounding type, c. Close to Staff Area

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1

Window blinds 2 Planning Relationships QUANTITY REMARKS REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-PHAR-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 320


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PHARMACY CHIEF PHARMACIST'S OFFICE 250B-PHAR-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit pharmacist, hosp. staff & visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 321 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary Outdoor air temperature (°C) ave. local station temp. reading '


KEY SCALE 1:100 M 1 Desk 2 Desk return (extension), 400 x 900mm 3 Cabinet (for narcotics), 400 x 1200mm 4 Shelving, 300 x 1500mm 6000 3000 1 SD T 2 3 5 4 6 7 7 9 D 5 File cabinet 6 Chair, junior executive 7 Chair, upright, stacking 8 Waste bin, pharmaceutical 9 Waste bin, general 8 322


Department: Room Title: PHARMACY COUNSELING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Pharmacist evaluates the appropriateness of the drug Computer w/ printer 1 therapy being used by the patient Waste bin w/ black lining 1 b. Pharmacist recommends compliance of the patient with or colorless lining the treatment regimen c. Pharmacist advises the patient to understand his/her illness and its treatment d. Pharmacist gives the patient instructions about the proper use of the medicines and knowledge about its side effects People Involved: FURNITURE AND 1 x Pharmacist FIXTURE CHECKLIST Desk, 600mm x 1200mm 1 Chair, upright, stacking 2 Clerical Chair, standard 1

Planning Relationships ADDITIONAL EQUIPMENT & a. Close to Patient Dispensing Area ENGINEERING TERMINALS b. Close to Chief Pharmacist's Office Outlet, 10A,2P,240V, duplex 2 grounding type,

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1

250-Bed (Level 3) Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-PHAR-RDS-02A QUANTITY REMARKS Updated Reference: April 2016 323


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PHARMACY COUNSELING ROOM 250B-PHAR-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.65 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit pharmacist, patient & companion Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 324 Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 3000 3000 1 2 1 Desk, 600 x 1200mm 2 Chair, clerical 3 Chair, upright, stacking 4 Waste bin 3 3 D T SD 4 325


Department: Room Title: PHARMACY DISPENSING AREA & DRUG INFORMATION FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Screens, fills, dispenses drugs, medicines, and galenicals Computer w/ printer 5 b. Supplies floor stocks to wards and other treatment areas Pharmaceutical refrigerator 1 c. Provides drug information services w/ freezer d. Preparation of IV admixtures Waste bin w/ yellow lining 1 e. Displays stocks on respective shelves Waste bin w/ black lining 2 Glass partition with transaction 2 window People Involved: FURNITURE AND 2 x Pharmacist FIXTURE CHECKLIST 1 x Pharmacy aide Counter, transaction, with 2 300mm deep cabinets below Table, computer 1 Chair; upright, stacking 1 Shelving, open
1 Sink, stainless 1 Planning Relationships ADDITIONAL EQUIPMENT & a. Close to Inpatient Nursing Wards ENGINEERING TERMINALS b. Close to Out Patient Department and Emergency Outlet, 10A,2P,240V, duplex 9 grounding type,

universal slots Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1

QUANTITY REMARKS REMARKS Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU REMARKS QUANTITY QUANTITY HEALTH FACILITY 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-PHAR-RDS-03A 326


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PHARMACY DISPENSING AREA & DRUG INFORMATION 250B-PHAR-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNESCESSARY Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit pharmacy staff Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET 327 Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary


12000 KEY SCALE 1:150 M 3000 1 Counter, transaction, with 300mm deep cabinets below 2 Glass partition with transaction window 3 Table, computer 4 Chair; upright, stacking 5 Sink, stainless steel 6 Shelving, open 7 Refrigerator, pharmaceutical 8 Computer, with printer 9 Waste bin, pharmaceutical 10 Waste bin, regular D 1 2 SD SD 1 2 3 4 6 7 8 9 10 10 8 8 8 8 2 T CH CH CH CH 5 328


Department: Room Title: PHARMACY RECEIVING/ BREAKOUT/ INSPECTION AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Pharmacist receives/ inspects pharmaceutical & Exhaust fan 1 biological deliveries Waste bin w/ yellow lining 1 b. Records data of deliveries in stock cards Waste bin w/ black lining 1 c. Records data of stocks transferred from bulk storage or colorless lining to the active storage People Involved: FURNITURE AND 1 x Pharmacist FIXTURE CHECKLIST 1 x Storekeeper Counter, 750mm high, 1 w/ cabinets above & below Sink-in-counter, drainboard 1 Chair, upright, stacking 1 Concealed floor drain w/ 1 waterless trap

Planning Relationships ADDITIONAL EQUIPMENT & QUANTITY REMARKS a. Adjacent to Bulk Storage ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1

QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-PHAR-RDS-04A QUANTITY REMARKS Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU 329


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PHARMACY RECEIVING/ BREAKOUT/ INSPECTION AREA 250B-PHAR-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNESCESSARY Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit pharmacy staff, delivery, COA Fire risk LOW:medium:high Other risks NA ROOM DATA SHEET 330 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


6000 KEY SCALE 1:100 M 6000 1 Counter, 750mm high, with cabinets above & below 2 Sink, with drainboard 3 Chair, upright, stacking 4 Waste bin, pharmaceutical 5 Waste bin, general 6 Concealed floor drain 7 Exhaust fan 1 SD 3 2 4 5 6 CH 7 CH 331


Department: Room Title: PHARMACY BULK STORAGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of pharmaceuticals Plastic Palletes 3 Waste bin w/ yellow lining 1 Waste bin w/ black lining 1 or colorless lining People Involved: FURNITURE AND 1 x Pharmacist FIXTURE CHECKLIST 1 x Utility Worker Shelving, adjustable, rail mounted 7

ADDITIONAL EQUIPMENT & a. Adjacent to Receiving/ Breakout/ Inspection Area ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 10 grounding type,

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 4

ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-PHAR-RDS-05A QUANTITY REMARKS Updated Reference: April 2016 REMARKS QUANTITY Planning Relationships Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) 332


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PHARMACY BULK STORAGE 250B-PHAR-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit pharmacy staff Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET 333 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:200 M 9000 12000 1 Shelving, open, adjustable, rail mounted 2 Pallet, plastic 3 Waste bin, pharmaceutical 4 Waste bin, general 1 2 4 SD SD SD SD 1 1 1 1 1 1 2 2 3 334


Department: Room Title: PHARMACY STAFF PANTRY/ LOUNGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Pharmacy staff eat their meals Computer w/ printer 1 b. Pharmacy staff rests and stores clothings Refrigerator 1 and other belongings at the lockers Water Dispenser 1 c. Staff do clean-up activities Waste bin w/ black lining 1 non-biodegradable Waste bin w/ green lining 1 biodegradable People Involved: FURNITURE AND Pharmacy Staff FIXTURE CHECKLIST Dining table, 4-seater 1 Dining chair 4 Steel lockers 4 Sink w/ drainboard 1 Counter w/ cabinets below 1 Lavatory 1 Water Closet 1 Concealed floor drain w/ 1 waterless trap

Planning Relationships ADDITIONAL EQUIPMENT & REMARKS a. Within the Pharmacy department ENGINEERING TERMINALS Window curtain rail 1 Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1

250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-PHAR-RDS-06A QUANTITY REMARKS Updated Reference: April 2016 QUANTITY Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 335


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PHARMACY STAFF PANTRY/ LOUNGE 250B-PHAR-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:DESIRABLE:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit pharmacy staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 336 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


6000 KEY SCALE 1:100 M 3000 1 Counter, with cabinets below 2 Sink, with drainboard 3 Table, 4-seater dining 4 Chair, dining 5 Locker, metal 6 Refrigerator 7 Water dispenser 8 Waste bin, general 9 Floor drain, concealed 10 Toilet 1 3 SD 2 4 CH 4 4 4 5 6 7 9 8 10 5 5 5 337


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Pharmacist and pharmacist's assistant Pharmaceutical refrigerator 1 perform admixture activities inside the room Cabinet, IV visual clarity 1 b. Finished items/products are stored and/or inspection

placed in cart for release to nursing wards and Scanner, laser 1 other hospital units Compounding machine, high 1

speed

Counting machine, for tablet 1 and capsule

Cart, stainless steel; with 1 casters Waste bin 2 People Involved: FURNITURE AND 1 x Pharmacist FIXTURE CHECKLIST 1 x Pharmacist's assistant Counter, work; with overhead 1 cabinets

Sink, stainless steel 1 Chair, upright 2 Dispenser, soap and paper 1 towel Clock 1

ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Planning Relationships: Outlet, 10A,2P,240V, duplex 5 grounding type, a. Near or accesible to the Bulk Storage Room

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light

Smoke detector 1 Outlet, Telephone 1

Updated Reference: ROOM DATA SHEET PHARMACY Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: PARENTERAL ADMIXTURE QUANTITY REMARKS REMARKS 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS April 2016 QUANTITY 250B-PHAR-RDS-07A 338


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 22 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit pharmacy staff Fire risk low : medium : HIGH Other risks NA ROOM DATA SHEET April 2016 250B-PHAR-RDS-07B PHARMACY PARENTERAL ADMIXTURE 339


KEY SCALE 1:100 M 3000 SD 1 2 4 5 3 6 7 8 9 10 11 12 13 1 Counter, work; with overhead cabinets for storage 2 Sink, stainless steel; with faucet 3 Chair, upright 4 Dispenser, soap and paper towel 5 Refrigerator, pharmaceutical 6 Cabinet, IV visual clarity inspection 7 Scanner, laser; handheld 8 Machine, compounder; high speed 9 Machine, counting; tablet and capsule 10 Cart, stainless steel; w/ casters 11 Clock 12 Waste bin 13 Window T 3000 340


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Pharmacist and pharmacist's assistant Counting machine, for tablet 1 perform extemporaneous preparation and
and capsule 1 compounding of medication as required Unit dose packing machine 1 b. Activities include preparation. Assembly, labeling Computer with printer 1 patient medications Waste bin 2 c. Clerical work is performed (documentation, inventory, etc.) People Involved: FURNITURE AND 1 x Pharmacist FIXTURE CHECKLIST 1 x Pharmacist's assistant Counter, work; with overhead 1

cabinets 1

Sink, stainless steel 1

Chair, upright 1 Clock 1

ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Planning Relationships: Outlet, 10A,2P,240V, duplex 4 grounding type, a. Near or accesible to Bulk Storage Room

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light

Smoke detector 3 Outlet, data 1 Outlet, telephone 1

PHARMACY QUANTITY Hospital: EXTEMPORANEOUS PREP 250-Bed (Level 3) ROOM DATA SHEET Reference Sheet Number: QUANTITY REMARKS April 2016 250B-PHAR-RDS-08A Updated Reference: REMARKS QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 341


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature 22 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit pharmacy staff Fire risk low: MEDIUM : high Other risks NA ROOM DATA SHEET April 2016 250B-PHAR-RDS-08B PHARMACY EXTEMPORANEOUS PREP 342


KEY SCALE 1:100 M 1 Counter, work; with overhead cabinets for storage 2 Sink, stainless steel; with faucet 3 Pegboard, wall-mounted 4 Machine, counting; tablet and capsule 5 Machine, unit dose packer 6 Desk, work; with computer and printer 7 Chair, upright 8 Clock 9 Waste bin 10 Window 3000 3000 SD 1 2 3 8 6 7 5 4 10 9 D T 343


UP WAITING AREA EXTRACTION (2) RECEPTION/ RECEIVING/ RELEASING CONFERENCE ROOM RECORDS ROOM PATHOLOGY OFFICE AFFILIATES' ROOM CMT OFFICE HEMATOLOGY BLOOD TYPING, CROSS MATCHING, POST BTR INVESTIGATION SEROLOGY/ IMMUNOLOGY STREAKING ROOM MICROBIOLOGY/ BACTERIOLOGY MICROSCOPY PANTRY M STAFF T&B CHIEF PATHO OFFICE CHEMISTRY HISTOPATHOLOGY GLASS WASHING/ STORAGE ROOM AUTOCLAVE F STAFF T&B JAN CLO LOCKERS STORAGE ANTE ROOM 3900 2100 6000 12000 2900 2100 2100 7300 11200 3100 1500 5900 2500 4200 5200 48000 2900 3300 3700 5200 3700 4100 3700 2500 3700 3700 7600 3000 2500 3900 1900 2000 SCALE 1:300 M 344


Department: Room Title: LABORATORY WAITING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patients await their turns to be examined attended to Waste bin w/ black or colorless 3 by Medical Laboratory Aide lining b. Patients/ Donors await their turns for their blood to be extracted People Involved: FURNITURE AND QUANTITY REMARKS 1 x Medical Laboratory Aide FIXTURE CHECKLIST Patients/ Relatives Counter; with queuing system 1 monitor 3-Seater Gang Chair 3 4-Seater Gang Chair 10 10-Seater Gang Chair 1 Water Closet 3 Urinal 1 Lavatory 2 Planning Relationships: a. Close to Blood Donor's Room b. Close to Pathologist's Office ADDITIONAL EQUIPMENT & QUANTITY REMARKS ENGINEERING TERMINALS Outlet, 10A, 2P, 240V, duplex 5 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 emergency light Smoke Detector 2 DEVELOPMENT BUREAU April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: ROOM DATA SHEET 250B-LAB-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) 345


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY WAITING AREA 250B-LAB-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) 50 Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff & general public Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 346 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY KEY SCALE 1:150 M 1 WAITING AREA 2 Counter; with queuing system monitor 3 Chair, gang-type 4 Waste bin 5200 12000 SD 2 3 3 3 3 3 3 4 SD 3000 3900 2500 1 3 3 3 3 3 3 3 3 5 6 4 4 5 MALE TOILET 6 FEMALE TOILET 347


Department: Room Title: LABORATORY RECEPTION/ RECEIVING/ RELEASING FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Medical Laboratory Aide attends to patients Computer w/ printer 1 b. Laboratory Staff receives specimen to be examined Waste bin w/ black lining 1 c. Laboratory Staff stores, files, and retrieves records d. Laboratory Staff release examination results to patients People Involved: FURNITURE AND 1 x Medical Laboratory Aide FIXTURE CHECKLIST 2 x Clerks Counter, 2-level, with 1 Patients/ Relatives bottom shelves below Counter, 900mm high, with 1 shelves below Stool, adjustable height 2 Cabinet, steel, filing 5 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Pathologist's Office Outlet, 10A, 2P, 240V, duplex 4 grounding type b. Accessible to Blood Donor's Room universal c. Close to Main Laboratory Outlet, 10A, 2P, 40V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke Detector 1 250B-LAB-RDS-02A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 348


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY RECEPTION/ RECEIVING/ RELEASING 250B-LAB-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff and visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 349


6000 KEY KEY SCALE 1:100 M 1 Counter, 2-level, with bottom shelves below 2 Counter, 900mm high, with shelves below 3 Stool, adjustable height 4 Cabinet, steel, filing 5 Waste bin, general 2450 SD 1 4 3 5 CH 3 4 4 4 4 CH CH T D 2 350


Department: Room Title: LABORATORY EXTRACTION AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Extraction of blood Cart, instrument 2 Cart, supply 2 Sharps container, wall-mounted 2 Waste bin, w/ black lining 2 Waste bin, w/ yellow lining 2 infectious People Involved: FURNITURE AND 2 x Medical Technologists FIXTURE CHECKLIST 2 x Laboratory Technicians Low partition, 1800mm high 1 2 x Patients Desk, 600 x 1000mm 2 Chair, swivel 2 Chair, upright, stacking 2 Chair, extraction
2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Waiting Area Outlet, 10A, 2P, 240V, duplex 10 grounding type b. Close to Pathologist's Room universal c. Close to Receiving Area Outlet, 10A, 2P, 40V, single 1 emergency light d. Adjacent to Screening Area Smoke Detector 1 QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 250B-LAB-RDS-03A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 351


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY EXTRACTION AREA 250B-LAB-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff and patients Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 352


KEY SCALE 1:100 M SD 1 2 5 6 1 Desk, 600 x 1000mm 2 Chair, swivel 3 Chair, upright, stacking 4 Chair, extraction 5 Cart, instrument 6 Cart, supply 7 Sharps container, wall-mounted 8 Waste bin, general 9 Waste bin, infectious 10 Low partition, 1800mm high 3 4 4200 3900 2100 2100 7 9 8 5 6 4 7 9 8 10 1 2 3 353


Department: Room Title: LABORATORY CONFERENCE ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Pathologist meets with Medical Technologist and White board/ projection screen 1 Medical Laboratory Technician/ Laboratory Aides, staff Projector, ceiling-mounted 1 and patient's relatives Waste bin w/ black lining 1 b. Pathologist interprets laboratory results c. Forum for information sharing and discussion of common laboratory procedures People Involved: FURNITURE AND 1 x Pathologist FIXTURE CHECKLIST Medical Technologist Table, conference, 10-seater 1 Medical Technician Chair, conference 10 Physicians Hospital Staff Companion/ Watcher ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Pathologist's Office and staff Outlet, 10A, 2P, 240V, duplex 7 grounding type universal Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 Outlet, Telephone 1 Outlet, DATA 1 QUANTITY REMARKS REMARKS QUANTITY QUANTITY REMARKS 250B-LAB-RDS-04A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 354


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY CONFERENCE ROOM 250B-LAB-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff and visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 355


KEY SCALE 1:100 M 1 Table, conference, 10-seater 2 Chair, conference 3 White board/ projection screen 4 Projector, ceiling-mounted 5 Waste bin, general 6000 SD 1 3 4 T D 2 3700 5 2 2 2 2 2 2 2 2 2 356


Department: Room Title: LABORATORY PATHOLOGY OFFICE/ LIBRARY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Pathologist reads, writes, examines histopath Whiteboard 1 samples and uses telephone in his desk 5-headed training microscope 1 b. Pathologist receives visitors Waste bin w/ black lining 1 c. Pathologist stores, files and retrieves records People Involved: FURNITURE AND QUANTITY REMARKS 1 x Pathologist FIXTURE CHECKLIST Visitors/ Consultants Shelf, open 2 1 x Registered Medical Technologist Desk, 600 x 1000mm; with 4 computer Table, 600 x 1800mm 1 Table, meeting, 4- or 5-seater 1 Chair, swivel 4 Chair/Stool, adjustable height 6 Chair, with arm rest 4 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Waiting Area/ Receiving Area Outlet, 10A, 2P, 240V, duplex 8 grounding type b. Close to Main Laboratory universal c. Adjacent to Donor's Screening Area Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 Outlet, DATA 4 QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-05A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 357


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY PATHOLOGY OFFICE/ LIBRARY 250B-LAB-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit pathologist and visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 358


KEY SCALE 1:100 M 1 Desk, 600 x 1000mm; with computer 2 Table, 600 x 1800mm 3 Table, meeting, 4- or 5-seater 4 Chair, swivel 5 Chair/Stool, adjustable height 6 Chair, with arm rest 7 Shelf, open 8 Whiteboard 9 5-headed training microscope 10 Waste bin, general 1500 1950 5900 3900 SD 1 2 3 4 4 4 4 5 5 5 5 5 5 6 6 6 6 7 7 9 10 10 D 1 D 1 D 1 D 10 8 359


Department: Room Title: LABORATORY CHIEF PATHOLOGIST'S OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Pathologist reads, writes, examines histopath Waste bin w/ black lining 2 samples and uses telephone in his desk b. Pathologist receives visitors c. Pathologist stores, files and retrieves records People Involved: FURNITURE AND QUANTITY REMARKS 1 x Pathologist FIXTURE CHECKLIST Visitors/ Consultants Shelf, open 1 1 x Registered Medical Technologist Desk, 600 x 1200mm; with 1 computer Desk extension 1 Chair, swivel 1 Chair, visitor 1 Cabinet, steel, filing 2 Counter, with top and
1 bottom cabinets Lavatory Water closet ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Waiting Area/ Receiving Area Outlet, 10A, 2P, 240V, duplex 4 grounding type b. Close to Main Laboratory universal c. Adjacent to Donor's Screening Area Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 Outlet, DATA 1 Outlet, Telephone 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-06A April 2016 360


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY CHIEF PATHOLOGIST'S OFFICE 250B-LAB-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit pathologist and visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 361


KEY SCALE 1:100 M 3100 3900 1 Desk, 600 x 1200mm 2 Desk, extension 3 Chair, swivel 4 Chair, visitor 1500 1950 SD 1 4 2 3 6 CH 7 5 8 8 5 Counter, with top and bottom cabinets 6 Cabinet, steel, filing 7 Shelf, open 8 Waste bin, general T D 6 362


Department: Room Title: LABORATORY CHEMISTRY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Microscopic & biochemistry examinations Urine Analyser 1 Clinical analysis, titrations & other procedures Cup Sink 1 b. Clinical handwashing Sink, utility, with drainboard 2 & wall-mounted pegboard Refrigerator, 8 cu. Ft. 1 Exhaust air grills 2 Clinical centrifuge 1 Floor-type Microscope 1 Chemistry Analyzer 1 Electrolyte Analyzer 1 Pipetor 1 set Sharps Container 1 Waste bin w/ yellow lining 3 infectious chemical People Involved: pathological & 2 (Urinalysis) anatomical 2 (Biochemistry) 1 x Registered Medical Technologist 1 x Medical Laboratory Technician 1 x Laboratory Aide FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST Counter, laboratory, with
1 cabinets above & below 1 Desk, 600 x 1200mm 1 Chair, upright, stacking 1 Stool, adjustable height 3 Concealed floor drain 2 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Histopathology Section Window curtain rail 5 b. Close to Hematology Section Outlet, 10A, 2P, 240V, duplex 10 grounding type universal 3 floor-type Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 2 Outlet, DATA 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-07A April 2016 363


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY CHEMISTRY 250B-LAB-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Laboratory staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 364


3900 KEY KEY SCALE 1:150 M 1 Counter, laboratory, with cabinets above & below 2 Sink, utility, with drainboard and wall-mounted pegboard 3 Sink, cup 4 Exhaust air grille 5 Desk, 600 x 1200mm 6 Chair, upright, stacking 7 Stool, adjustable height 11200 1 SD SD 8 Centrifuge, clinical; floor-type 9 Refrigerator 10 Concealed floor drain 11 Sharps container, wall-mounted 12 Waste bin, infectious 13 Waste bin, pathological & anatomical 14 Waste bin, chemical 2 2 3 4 7 5 7 6 8 9 7 10 4 10 11 11 121314 CH CH CH CH CH CH FO FO FO D 365


Department: Room Title: LABORATORY HEMATOLOGY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Hemoglobin tests, sedimentation rates, Sink, cup 1 staining and washing of pipettes Exhaust air grille 1 b. Clinical handwashing Centrifuge, micro-hematocrit 1 Refrigerator 1 Sharps container 1 wall-mounted Waste bin w/ yellow lining 2 chemical pathological & anatomical Hematology Analyzer 1 People Involved: FURNITURE AND QUANTITY REMARKS 2 x Medical Technologists FIXTURE CHECKLIST 1 x Medical Laboratory Technician Counter, laboratory, with
1 cabinets above & below Sink, staining, with drainboard 2 & wall-mounted pegboard Desk, 600 x 1200mm 1 Chair, upright, stacking 1 Stool, adjustable height 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Urinalysis/ Biochemistry Section Outlet, 10A, 2P, 240V, duplex 7 grounding type b. Adjacent to Pathologist's Office universal Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 Outlet, DATA 1 QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-08A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 366


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY HEMATOLOGY 250B-LAB-RDS-08B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Laboratory staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 367


6000 KEY KEY SCALE 1:100 M 1 Counter, laboratory, with cabinets above & below 2 Sink, staining, with drainboard and wall-mounted pegboard 3 Sink, cup 4 Exhaust air grille 5 Desk, 600 x 1200mm 6 Chair, upright, stacking 3700 7 Stool, adjustable height 8 Centrifuge, micro-hematocrit 9 Refrigerator 10 Concealed floor drain 11 Sharps container, wall-mounted 12 Waste bin, pathological & anatomical 13 Waste bin, chemical SD 1 D 2 3 4 5 6 7 8 9 10 11 12 13 CH CH CH CH CH 368


Department: Room Title: LABORATORY SEROLOGY/ IMMUNOLOGY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Testing of blood for serological test Sink, cup 1 Exhaust air grille 1 Refrigerator/ freezer 2 Sharps container 1 wall-mounted Centrifuge 1 table-top Incubator 1 VDRL Rotator 1 Vortex Mixer 1 Microscope 1 Computer w/ printer 1 Airconditioning Unit 1 Waste bin w/ yellow lining 3 infectious chemical pathological & People Involved: anatomical 2 x Medical Technologists 1 x Medical Laboratory Technician 1 x Laboratory Aide FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST Counter, laboratory, with
1 cabinets above & below Sink, staining, with drainboard 1 & wall-mounted pegboard Desk, 600 x 1200mm 1 Chair, upright, stacking 1 Stool, adjustable height 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Hispathology Section Outlet, 10A, 2P, 240V, duplex 7 grounding type b. Close to Hematology Section universal c. Adjacent to Clerical Room Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 Outlet, DATA 1 QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-09A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 369


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY SEROLOGY/ IMMUNOLOGY 250B-LAB-RDS-09B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Laboratory staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 370


6000 KEY KEY SCALE 1:100 M 1 Counter, laboratory, with cabinets above & below 2 Sink, utility, with drainboard and wall-mounted pegboard 3 Sink, cup 4 Exhaust air grille 5 Desk, 600 x 1200mm 6 Chair, upright, stacking 7 Stool, adjustable height 3700 8 Centrifuge, table-top 9 Refrigerator / freezer 10 Concealed floor drain 11 Incubator 12 Sharps container, wall-mounted 13 Waste bin, infectious 14 Waste bin, pathological & anatomical 15 Waste bin, chemical SD 1 5 2 3 4 6 7 7 8 9 9 10 12 13 14 15 11 CH CH CH CH CH D 371


Department: Room Title: LABORATORY MICROBIOLOGY/ BACTERIOLOGY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Preparation of culture media Hamper, soiled linen 1 b. Staining of slides Exhaust air grille 2 c. Preparation of specimens from suspect cases of Autoclave 1 tuberculosis, fungi and viral diseases Refrigerator 3 d. Washing/ Decontamination Freezer 2 e. Sample Receipt Room Sharps container 1 wall-mounted f. Determination/ quantification and description Oven, hot air 1 of microbes Stove, electric 1 g. Reference culturing of microorganisms Incubator 1 Water Bath 1 Negative Pressure Hepa Filter Hood 1 Analytical Balance 1 Microscope 1 Infrared Microsterilizer 1 People Involved: Heating Plate 1 2 x Medical Technologists Balance, rough 1 1 x Medical Laboratory Technician Waste bin w/ yellow lining 3 chemical, infectious, 1 x Bacteriologist 1 x Pathologist pathological & 1 x Laboratory Aide anatomical FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST Cabinet, PPE; with hook strip 1 Counter, laboratory, with 3 cabinets above and below Sink, utility, with drainboard 1 & wall-mounted pegboard w/ electric grinder Stool, adjustable height 3 Concealed floor drain 2 Sink, staining, w/ drainboard & 1 wall-mounted pegboard Biosafety cabinet 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Histo pathology Section Window curtain rail 5 b. Close to Sterilizing and Glass Washing Rooms Outlet, 10A, 2P, 240V, duplex 16 grounding type universal Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 3 Outlet, DATA 1 Outlet, Telephone 1 Utility Control Breaker Boxes Gas Shut-Off Valves Automatic Voltage Regulator 1 Outlet, for heavy-duty machine 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-10A April 2016 372 Biosafety cabinet 1


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY MICROBIOLOGY/ BACTERIOLOGY 250B-LAB-RDS-10B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: Autoclave Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) 100 Quality which cannot be Tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Laboratory staff Fire risk low: MEDIUM: high Other risks exposure to hazardous elements ROOM DATA SHEET 373


6000 KEY SCALE 1:00 M ANTE ROOM: 1 Cabinet, PPE; with hook strip 2 Hamper, soiled linen MICROBIOLOGY/BACTERIOLOGY LAB: 3 Counter, laboratory, with cabinets above and below 4 Sink, utility, with drainboard & wall-mounted pegboard; with electric grinder 5 Exhaust air grille 6 Autoclave 7 Refrigerator 8 Freezer 9 Stool, adjustable height 10 Concealed floor drain 11 Sharps container, wall-mounted 12 Waste bin, infectious 13 Waste bin, pathological & anatomical 14 Waste bin, chemical STREAKING ROOM: 15 Sink, staining, with drainboard and wall-mounted pegboard 16 Biosafety cabinet 17 Oven, hot air 18 Stove, electric 19 Incubator 1 1900 9 4 2 3 5 6 9 7 7 7 8 8 10 11 12 13 14 15 3 5 10 1617 18 19 9 SD SD SD CH CH CH CH CH CH CH 3 T D 7100 5200 374


Department: Room Title: LABORATORY MICROSCOPY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Viewing of samples and objects that cannot be seen Exhaust air grille 1 by the naked eye Centrifuge, clinical 1 b. Processing and staining of tissue/ samples Refrigerator 1 c. Clinical handwashing Sharps container 1 wall-mounted d. Examination of surgical and autopsy specimens Analytical balance 1 Fume hood 1 Cylinder, carbon dioxide 1 Cylinder, gas 1 Clinical microscope 1 Waste bin w/ yellow lining 3 chemical infectious pathological & anatomical People Involved: FURNITURE AND 1 x Medical Technologist FIXTURE CHECKLIST 1 x Microscopist Counter, laboratory, with
1 cabinets above & below Sink, utility, with drainboard 1 and wall-mounted pegboard Sink, staining 1 Desk, 600 x 1200mm 1 Chair, upright, stacking 1 Stool, adjustable height 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Histopathology Section Outlet, 10A, 2P, 240V, duplex 8 grounding type b. Close to Microbiology/ Bacteriology Section universal Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 Outlet, DATA 1 QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-11A April 2016 QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 375


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY MICROSCOPY 250B-LAB-RDS-11B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Laboratory staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 376


KEY KEY SCALE 1:100 M 1 Counter, laboratory, with cabinets above & below 2 Sink, utility, with drainboard and wall-mounted pegboard 3 Sink, cup 4 Exhaust air grille 5 Desk, 600 x 1200mm 6 Chair, upright, stacking 7 Stool, adjustable height 8 Centrifuge, clinical 9 Analytical balance 10 Concealed floor drain 11 Fume hood 12 Cylinder, carbon dioxide 13 Cylinder, gas 14 Sharps container, wall-mounted 15 Waste bin, infectious 16 Waste bin, pathological & anatomical 17 Waste bin, chemical 6000 3700 SD 1 D 2 9 4 11 7 3 10 5 CH CH CH CH 6 8 12 13 14 15 16 17 377


Department: Room Title: LABORATORY HISTOPATHOLOGY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Examination of surgical and autopsy specimens Sink, cup 1 Processing and staining of tissue/ samples Exhaust air grille 1 b. Clinical handwashing Centrifuge 1 table-top Refrigerator 1 Sharps container 1 wall-mounted Analytical balance 1 Fume hood 1 Cryostat 1 Microtome 1 Hot plate 1 Microscope 1 Hot air oven 1 Gross Cutting Cabinet 1 Immunohistochemistry analyzer 1 People Involved: Waste bin w/ yellow lining 3 chemical 1 x Pathologist infectious 2 x Medical Technologist pathological & 2 x Laboratory Aide anatomical Medical Laboratory Technician Interns Affiliates FURNITURE AND FIXTURE CHECKLIST Counter, laboratory, with
1 cabinets above & below Sink, utility, with drainboard 1 and wall-mounted pegboard Stool, adjustable height 2 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Clinical Microscopy Outlet, 10A, 2P, 240V, duplex 9 grounding type b. Close to Microbiology/ Bacteriology Section universal c. Adjacent to Pathologist's Office Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-12A April 2016 QUANTITY REMARKS 378


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY HISTOPATHOLOGY 250B-LAB-RDS-12B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) 2.5 Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Laboratory staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 379


KEY SCALE 1:100 M 1 Counter, laboratory, with cabinets above & below 2 Sink, utility, with drainboard and wall-mounted pegboard 3 Sink, cup 4 Exhaust air grille 5 Stool, adjustable height 6 Gross cutting cabinet 7 Refrigerator 8 Cryostat 9 Centrifuge, table-top 10 Microtome 11 Hot plate 12 Hot air oven 13 Analytical balance 14 Microscope 15 Immunohistochemistry analyzer 16 Concealed floor drain 17 Sharps container, wall-mounted 18 Waste bin, infectious 19 Waste bin, pathological & anatomical 20 Waste bin, chemical 5500 3900 1800 2700 SD CH CH CH CH CH 1 2 3 4 16 5 5 6 7 8 9 10 11 12 13 14 17 18 19 10 15 20 380


Department: Room Title: LABORATORY BLOOD TYPING, CROSS MATCHING, POST-BRT INVESTIGATION FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Blood typing procedures Centrifuge 1 b. Cross matching procedures Serofuge 1 c. Post BRT investigation Water bath 1 d. other related/necessary procedures Refrigerator 2 Waste bin, infectious 1 Waste bin, pathological and 1 anatomical

Waste bin, chemical 1 Sharp container 1 People Involved: FURNITURE AND QUANTITY REMARKS 1 x Medical Laboratory Technician FIXTURE CHECKLIST 1 x Laboratory Aide Chair, upright; stacking 1 Stool, adjustable height 1 Counter, laboratory 1 Sink, staining; with drainboard 1 and wall-mounted pegboard 1 Sink, cup 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Accessible to Blood Station Outlet, 10A,2P,240V, duplex 8 grounding type b. Preferable with direct access to outside

universal corridor/hallway Outlet, 10A,2P,240V, single 1 emergency light Outlet, data 1 Smoke detector 1 Window curtain rail 3 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-13A April 2016 381


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY BLOOD TYP, CROSS MATCH., POST-BRT INVEST. 250B-LAB-RDS-13B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Laboratory/Blood Station staff Fire risk low: MEDIUM : high Other risks NA ROOM DATA SHEET 382


6000 KEY KEY SCALE 1:100 M 1 Counter, laboratory, with cabinets above & below 2 Sink, staining, with drainboard and wall-mounted pegboard 3 Sink, cup 4 Exhaust air grille 5 Desk, 600 x 1200mm 6 Chair, upright, stacking 7 Stool, adjustable height 4100 8 Centrifuge 9 Serofuge 10 Water bath 11 Refrigerator 12 Concealed floor drain 13 Sharps container, wall-mounted 14 Waste bin, infectious 15 Waste bin, pathological & anatomical 16 Waste bin, chemical SD CH CH CH D 1 2 3 4 12 5 6 7 8 9 10 11 11 13 14 1516 383


Department: Room Title: LABORATORY GLASS WASHING FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Washing of instruments/ glasswares Fume hood 1 b. Preparation of glasswares/ instruments for Oven, hot air 1 future use Sharps container 1 Waste bin w/ yellow lining 1 Waste bin w/ black lining 1 People Involved: FURNITURE AND 1 x Laboratory Aide FIXTURE CHECKLIST Counter, with cabinets above
1 and below Sink, two compartment; 1 200mm deep Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Locker Room & Toilet Outlet, 10A, 2P, 240V, duplex 4 grounding type b. Close to Storage Room universal Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-14A April 2016 QUANTITY REMARKS 384


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY GLASS WASHING 250B-LAB-RDS-14B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: pressure sterilizer Speech privacy essential:desirable: UNNECESSARY Maximum temperature (°C) 100 Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Laboratory staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 385


KEY SCALE 1:100 M 1 Counter, with cabinets above and below 2 Sink, two compartment; 200mm deep 3 Fume hood 4 Oven, hot air 5 Concealed floor drain 3900 2100 SD 1 4 5 2 3 CH 386


Department: Room Title: LABORATORY AUTOCLAVE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Sterilization of instruments/ glasswares Autoclave
1 People Involved: FURNITURE AND Laboratory Staff FIXTURE CHECKLIST Counter, with cabinets below 1 Sink, with drainboard 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Accessible to Bacteriology Section Outlet, 10A, 2P, 240V, duplex 3 grounding type b. Close to Staff Lounge & Pantry universal c. Adjacent to Main Clinical Laboratory Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-15A April 2016 QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 387


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY AUTOCLAVE 250B-LAB-RDS-15B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: autoclave Speech privacy essential:desirable: UNNECESSARY Maximum temperature (°C) 100 Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit Laboratory staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 388


KEY SCALE 1:100 M 1 Counter, with cabinets below 2 Sink, with drainboard 3 Concealed floor drain 4 Autoclave 3900 2100 SD 1 2 3 4 CH 389


Department: Room Title: LABORATORY STAFF LOCKER ROOM AND T&B FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Laboratory staff change clothes in toilet Hamper, linen 1 and locker room Waste bin, w/ black lining 2 b. Laboratory staff bathe in shower cubicle c. Storing of clothing and personal effects People Involved: FURNITURE AND Laboratory Staff FIXTURE CHECKLIST Water Closet w/ spray hose 4 Lavatory 4 Urinal 3 Slop sink, with faucet
1 Shelf, open 1 Locker, steel 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Accessible to Staff Work Area and Main Entrance Outlet, 10A, 2P, 240V, duplex 1 grounding type to the Laboratory universal Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 Outler, Water heater, 30A, 2P, 240V 2 T&B QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-16A April 2016 QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 390


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY STAFF LOCKER ROOM AND T&B 250B-LAB-RDS-16B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 391


KEY SCALE 1:150 M 1 FEMALE T&B 2 Waste bin, general 3 MALE T&B 4 JANITOR'S CLOSET 5 Slop sink, with faucet 6 Shelf, open 7 LOCKER ROOM 8 Locker, steel 9 Hamper, linen 3900 3300 1300 1900 4900 1 3 4 7 8 9 5 6 2 2 SD 12000 392


Department: Room Title: LABORATORY STAFF PANTRY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Laboratory staff makes use of the pantry Whiteboard 1 b. Janitorial services do clean-up activities Water dispenser 1 Refrigerator 1 Waste bin w/ black lining 1 Microwave oven 1 People Involved: FURNITURE AND Laboratory Staff FIXTURE CHECKLIST Visitors Table, dining, 4- or 5-seater 1 Table, side, 400 x 400mm
1 Chair, dining 4 Sofa, 2-seater 1 Counter, with top and
1 bottom cabinets Sink, stainless steel 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Within the Laboratory Department Outlet, 10A, 2P, 240V, duplex 6 grounding type universal Outlet, 10A, 2P, 40V, single 1 emergency light Smoke Detector 1 QUANTITY REMARKS REMARKS QUANTITY 250B-LAB-RDS-17A April 2016 QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 393


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LABORATORY STAFF PANTRY 250B-LAB-RDS-17B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 394


KEY SCALE 1:100 M 1 Table, dining, 4- or 5-seater 2 Table, side, 400 x 400mm 3 Chair, dining 4 Sofa, 2-seater 5 Counter, with top and bottom cabinets 6 Sink, stainless steel 7 Whiteboard 8 Water dispenser 9 Refrigerator 10 Concealed floor drain 11 Waste bin, general 3900 3300 SD 1 CH 2 3 3 3 3 4 5 6 7 8 9 1011 395


WAITING AREA 3000 3000 3500 2500 SCREENING/ ASSESSMENT COMPONENT PREPARATION ROOM STAFF LOCKERS & PANTRY RECORDS ROOM BLOOD ISSUANCE AREA TESTING ROOM BLOOD COMPONENT STORAGE BLOOD COLLECTION ROOM SCALE 1:300 M 5900 12400 6400 2100 3900 2600 3900 15000 3200 3100 3600 2600 2500 1500 1500 396


Department: Room Title: BLOOD STATION WAITING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patients await their turns to be examined/ attended Weighing scale 1 to by Medical Laboratory Aide Waste bin, general 2 b. Patients/Donors await their turns for their blood to be extracted c. Patients await the release of their examination results People Involved: FURNITURE AND 1 x Medical Laboratory Aide FIXTURE CHECKLIST Patients/ Relatives Desk, 600 x 1200mm 1 Cabinet, steel, filing 1 Chair, upright, stacking 2 Chair, gang-type 3 4-seater 1 5-seater 1 6-seater Water closet 1 Urinal 1 Lavatory 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Blood Donor's Room ENGINEERING TERMINALS b. Close to Pathologist's Office Outlet, 10A, 2P, 240V, duplex 6 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 emergency light Outlet, DATA 1 wall-mounted Outlet, Telephone 1 Smoke Detector 1 ROOM DATA SHEET 250B-BS-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: QUANTITY REMARKS 397


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 BLOOD STATION WAITING AREA 250B-BS-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
150 Room temperature (°C) ambient Night illumination (LUX) 50 Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff & general public Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 398 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY KEY SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Cabinet, steel, filing 3 Chair, upright, stacking 4 Chair, 4- or 5-seater, gang-type 5 Weighing scale 6 Waste bin, general 3300 4500 2700 3000 1500 1 6000 SD 3 6 2 4 6 4 4 4 4 T D 3 5 399


Department: Room Title: BLOOD STATION SCREENING & ASSESSMENT FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Collecting blood samples for the presence of infectious Waste bin, w/ black lining 2 or transmittable diseases Waste bin, w/ yellow lining 1 b. Screening potential donors Low partition, with sliding door 2 c. Collecting appropriate donor information and Weighing scale, heavy duty 1 administering donor health questionnaire Sphygmomanometer 1 d. Documentation of patients' record Stethoscope 1 Thermometer, non-mercurial 1 Refrigerator 1 Rotator 1 Phlebotomist's Tray 1 Microscope 1 Hemoglobin Ometer w/ reader, 1 washer & incubator Needle Disposal 1 Sharps Container 1 Detecto w/ rod 1 People Involved: FURNITURE AND 2 x Medical Technologist/ Phlebotomist FIXTURE CHECKLIST Patient Desk, 600 x 1200mm 2 Clerk/ Staff Cabinet, steel, filing 1 Blood Station Nurse Chair, swivel 2 Blood Donor Chair, visitor 3 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Waiting Area ENGINEERING TERMINALS b. Close to Staff Room c. Accessible to Pathologist's Office Outlet, 10A, 2P, 240V, duplex 4 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 emergency light Outlet, DATA 2 wall-mounted Outlet, Telephone 1 Smoke Detector 1 ROOM DATA SHEET 250B-BS-RDS-02A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: QUANTITY REMARKS 400


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 BLOOD STATION SCREENING & ASSESSMENT 250B-BS-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff & blood donors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 401 Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary


3000 KEY KEY SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Cabinet, steel, filing 3 Chair, swivel 4 Chair, visitor 5 Waste bin, general 6 Low partition, with sliding door 3900 SD 1 3 5 2 T D 4 3 4 1 D 5 4 6 6 402


Department: Room Title: BLOOD STATION COMPONENT PREPARATION ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Labeling of blood component Centrifuge 1 b. Storing of whole blood and blood components as a Platelet incubator 1 part of blood donation Weighing scale 1 Waste bin, general 1 Waste bin, w/ yellow lining 1 pathological anatomical waste Computer w/ Printer 1 People Involved: FURNITURE AND QUANTITY REMARKS 1 x Medical Technologist FIXTURE CHECKLIST 1 x Medical Laboratory Technician Counter, laboratory; with 1 cabinets above and below Sink, with drainboard 1 Stool, adjustable height 1 Biosafety cabinet 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Donor's Blood Donation Area/ Screening Area ENGINEERING TERMINALS b. Close to Extraction Area c. Adjacent to Hematology Outlet, 10A, 2P, 240V, duplex 7 grounding type, d. Adjacent to Immunology/ Serology

universal e. Adjacent to Pathologist's Office Outlet, 10A, 2P, 240V, single 1 emergency light Smoke Detector 1 ROOM DATA SHEET 250B-BS-RDS-03A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: 403


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 BLOOD STATION COMPONENT PREPARATION ROOM 250B-BS-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
400 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff Fire risk LOW: medium: high Other risks blood contamination ROOM DATA SHEET 404 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 1 Counter, laboratory; with cabinets above and below 2 Sink, with drainboard 3 Stool, adjustable height 4 Biosafety cabinet 5 Centrifuge 3500 SD 1 3900 2 3 4 5 6 Platelet incubator 7 Weighing scale 8 Concealed floor drain 9 Waste bin, general 10 Waste bin, pathological and anatomical waste 6 7 CH CH 9 10 8 CH CH 405


Department: Room Title: BLOOD STATION TESTING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Labeling of blood component Microscope 1 b. Storing of whole blood and blood components as a Refrigerator 2 part of blood donation Waste bin, general 1 Waste bin, w/ yellow lining 1 pathological anatomical waste People Involved: FURNITURE AND QUANTITY REMARKS 1 x Medical Technologist FIXTURE CHECKLIST 1 x Medical Laboratory Technician Counter, laboratory; with 1 cabinets above and below Sink, with drainboard 1 Stool, adjustable height 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Donor's Blood Donation Area/ Screening Area ENGINEERING TERMINALS b. Close to Extraction Area c. Adjacent to Hematology Outlet, 10A, 2P, 240V, duplex 7 grounding type, d. Adjacent to Immunology/ Serology

universal e. Adjacent to Pathologist's Office Outlet, 10A, 2P, 240V, single 1 emergency light Smoke Detector 1 ROOM DATA SHEET 250B-BS-RDS-04A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: 406


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 BLOOD STATION TESTING ROOM 250B-BS-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
400 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff Fire risk LOW: medium: high Other risks blood contamination ROOM DATA SHEET 407 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 3200 3900 SD CH CH 1 Counter, laboratory; with cabinets above and below 2 Sink, with drainboard 3 Stool, adjustable height 4 Concealed floor drain 5 Refrigerator 6 Waste bin, general 7 Waste bin, pathological and anatomical waste 1 2 3 5 6 7 5 4 408


Department: Room Title: BLOOD STATION BLOOD COMPONENT STORAGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Labeling of blood component Refrigerator/ Freezer 6 b. Storing of whole blood and blood components as a Waste bin, general 1 part of blood donation Computer w/ Printer People Involved: FURNITURE AND QUANTITY REMARKS 1 x Medical Technologist FIXTURE CHECKLIST 1 x Medical Laboratory Technician Desk, 600 x 1200mm 1 Chair, upright, stacking 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Donor's Blood Donation Area/ Screening Area ENGINEERING TERMINALS b. Close to Extraction Area c. Adjacent to Hematology Outlet, 10A, 2P, 240V, duplex 7 grounding type, d. Adjacent to Immunology/ Serology

universal e. Adjacent to Pathologist's Office Outlet, 10A, 2P, 240V, single 1 emergency light Smoke Detector 1 Outlet, DATA 1 ROOM DATA SHEET 250B-BS-RDS-05A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: 409


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 BLOOD STATION BLOOD COMPONENT STORAGE 250B-BS-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff Fire risk LOW: medium: high Other risks blood contamination ROOM DATA SHEET 410 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


3100 KEY KEY SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Chair, upright, stacking 3 Refrigerator / Freezer 4 Waste bin, general 6400 SD D 2 3 4 1 3 3 3 3 3 411


Department: Room Title: BLOOD STATION BLOOD COLLECTION ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Blood extraction/ donation or collecting blood from Table, instrument 3 eligible donors Refrigerator 1 b. Supervising donor's recovery Clock 1 c. Checking and storing donated blood prior to examination Television 1 Waste bin, w/ black lining 1 Waste bin w/ yellow lining 2 infectious pathological & anatomical People Involved: FURNITURE AND QUANTITY REMARKS 1 x Medical Technologist FIXTURE CHECKLIST 1 x Medical Laboratory Technician Desk, 600 x 1200mm 1 1 x Blood Station Nurse Chair, upright, stacking 1 1 x Patient Blood donor bed, adjustable 3 1 x Utility Worker Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Waiting Area ENGINEERING TERMINALS b. Close to Pathologist's Office c. Adjacent to Screening Area Outlet, 10A, 2P, 240V, duplex 9 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 emergency light Smoke Detector 1 Outlet, DATA 1 QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: ROOM DATA SHEET 250B-BS-RDS-06A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU 412 Sharps container 3


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 BLOOD STATION BLOOD COLLECTION ROOM 250B-BS-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff & blood donors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 413 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


3600 KEY KEY SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Chair, upright, stacking 3 Blood donor bed, adjustable 4 Table, instrument 5 Refrigerator 6 Clock 6400 7 Television 8 Waste bin, general 9 Waste bin, infectious 10 Waste bin, pathological & anatomical 11 Sharps container SD D 2 1 3 4 5 6 7 8 3 4 3 4 10 9 11 10 9 11 10 9 11 414


Department: Room Title: BLOOD STATION STAFF LOCKERS, PANTRY & TOILET FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Blood Station staff makes use of the pantry Refrigerator 1 b. Janitorial Services do clean-up activities Microwave oven 1 Water dispenser
1 Waste bin w/ black lining 2 People Involved: FURNITURE AND QUANTITY REMARKS Blood Station Staff FIXTURE CHECKLIST Visitors Counter, with top and
1 bottom cabinets Sink, stainless steel 1 Table, 4- or 5-seater 1 Chair, dining 4 Locker, steel
4 Concealed floor drain 1 Water Closet 1 Lavatory 1 Urinal 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Blood Station Department ENGINEERING TERMINALS Outlet, 10A, 2P, 240V, duplex 5 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 emergency light Smoke Detector 1 QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: ROOM DATA SHEET 250B-BS-RDS-07A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU 415


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 BLOOD STATION STAFF LOCKERS, PANTRY & TOILET 250B-BS-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Laboratory staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 416 Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 1100 4000 1 Counter, with top and bottom cabinets 2 Sink, stainless steel 3 Table, 4- or 5-seater 4 Chair, dining 2800 1500 5 Refrigerator 6 Water dispenser 7 Locker, steel 8 Concealed floor drain 9 Waste bin, general 3900 2500 SD 1 3 2 4 4 4 4 5 7 8 9 9 CH 7 7 7 6 417


UP 3100 WAITING AREA 2200 7100 5300 1550 4200 3000 4200 3150 3100 2100 4600 4400 3000 CLERICAL ROOM RECEPTION/ INFO FT MT ULTRA SOUND 1 ULTRA SOUND 2 ULTRA SOUND 3 SUPPLY MAMMOGRAPHY X-RAY 1 DARK ROOM CONTROL T T DRESS DRESS T SUB- WAITING AREA FILM FILE STORAGE READING ROOM RAD HEAD OFFICE T JAN CLO STAFF MT STAFF FT PANTRY & LOCKERS CONFERENCE/ TRAINING ROOM CONTROL T CT-SCAN R/F X-RAY T DARK ROOMCONTROL X-RAY 2 6500 2400 3000 3000 3900 3000 3000 4100 6700 3900 4500 3400 12000 51000 CONTROL ROOM MRI MAGNET ROOM TECHNICAL ROOM 2500 7300 2200 1900 1600 2900 6100 11900 418


Department: Room Title: RADIOLOGY SUB-LOBBY/ WAITING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patients wait to be x-rayed Wheelchair 2 b. Patients wait for the release of their x-rayed results Stretcher 1 c. Patients in stretchers and wheelchairs and their Waste bin w/ black lining 3 comapnionship/ watchers wait FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST Chair, gang-type, 4- & 5-seater 10 Television w/ queuing system 1 People Involved: 1 x X-Ray Clerk Patients Companion/ Watchers

ADDITIONAL EQUIPMENT & a. Frontline area of the Radiology Department ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 7 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1

Outlet, TV 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-RAD-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: Planning Relationships QUANTITY REMARKS REMARKS QUANTITY 419


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY SUB-LOBBY/ WAITING AREA 250B-RAD-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit radiology staff & patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 420 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


SCALE 1:200 M 1 Chair, gang-type, 4- & 5-seater 2 Waste bin 3 Wheelchair & stretcher park 4 Television w/ queuing system KEY 4600 7400 5500 1 1 1 1 1 1 1 1 1 1 2 2 SD SD 3 4 12000 8950 421


Department: Room Title: RADIOLOGY CLERICAL ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Clerk receives request of patients to be x-rayed Computer 1 b. X-ray Technician/ Technologist schedules patient Waste bin w/ black lining 3 and special radiographic procedures Airconditioning Unit 1 c. Clerk types results, files and retrieves records. Uninterrupted Power Supply 1 d. Clerk issues results of radiographic procedures done Automatic Voltage Regulator 1 People Involved: FURNITURE AND Radiologic Technician/ Technologist FIXTURE CHECKLIST 3 x Clerks Desk, 600 x 1200mm 1 X-ray interns, if there are any Desk, extension, 400 x 800mm 1 Desk, 600 x 1200mm 2 Counter, 1200mm high 1 Chair; upright, stacking 3 Visitor's Chair 1 Stool, adjustable height 1 Cabinet, filing, steel 4

Planning Relationships ADDITIONAL EQUIPMENT & QUANTITY REMARKS a. Adjacent to Film Storage ENGINEERING TERMINALS b. Close to Radiologist's Office Window Curtain Rail 2 Outlet, 10A,2P,240V, duplex 7 grounding type,

universal slots Smoke detector 1 Outlet, DATA 3 Outlet, Telephone 2

Outlet, ACU 1

DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-02A QUANTITY REMARKS Updated Reference: April 2016 Department of Health 422


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY CLERICAL ROOM 250B-RAD-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.4 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit radiology staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 423 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Desk, extension, 400 x 800mm 3 Desk, 600 x 1200mm 4 Counter, 1200mm high 5 Chair; upright, stacking KEY 6 Chair; visitor 7 Stool, adjustable height 8 Cabinet, filing, steel 9 Waste bin 4200 4400 SD 1 3 3 5 5 5 6 7 8 2 4 8 8 8 9 9 9 T D T D D 424


Department: Room Title: RADIOLOGY CHIEF RADIOLOGIST'S OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Radiologist interprets x-ray film and/ or ultrasound image Wall-mounted negatoscope 4 1 b. Clerk type results banks 14 x 17 sg. In per bank 1 c. Radiologist meets with x-ray technologist, physicians Magnifying lens 1 and other hospital staff Computer 1 d. Radiologist receives visitors or patients Printer 1 Uninterrupted Power Supply 1 Automatic Voltage Regulator 1 Waste bin w/ black lining 3 Whiteboard 1 People Involved: FURNITURE AND Radiologist FIXTURE CHECKLIST 1 x X-Ray Clerk Desk, 600 x 1200mm 1 Companions/ Watchers Desk, extension 1 Desk, 600 x 100mm 1 Shelf, open 1 Cabinet, steel, filing 1 Chair, upright; stacking 2 Chair, visitor 2 Pass-through window 1 Lavatory 1

Water Closet 1 Planning Relationships ADDITIONAL EQUIPMENT & QUANTITY REMARKS a. Easily accessible to all other rooms ENGINEERING TERMINALS within the Radiology Department
Window Curtain Rail Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 2 wall-mounted Outlet, Telephone 1 desktop Outlet, ACU 1 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-03A QUANTITY REMARKS Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 425


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY CHIEF RADIOLOGIST'S OFFICE 250B-RAD-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Chief Radiologist, staff and visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 426 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


KEY SCALE 1:100 M 1 Desk, 600 x 1200mm 2 Desk, extension 3 Desk, 600 x 100mm 4 Shelf, open 5 Cabinet, steel, filing 6 Chair, upright; stacking 7 Chair, visitor 1500 3000 1900 4100 SD 1 T D 2 3 4 5 6 6 7 7 11 10 12 11 D 8 Negatoscope 9 Whiteboard 10 Pass-through window 11 Waste bin 12 TOILET 8 9 427


Department: Room Title: RADIOLOGY CONFERENCE ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Radiology staff members meet for conferences, Negatoscope (X-Ray film viewer) 1 discussions or trainings Whiteboard 1 Wall Clock 1 Airconditioning Unit 1 Liquid-Crystal Projector (LCD) 1 Waste bin w/ black lining 1 Projection Screen 1 People Involved: FURNITURE AND 1 x Radiologist FIXTURE CHECKLIST Radiologic Technologist Table, conference 1 Physicians Cabinet, low 1 Hospital staff Chair, conference 10

Planning Relationships ADDITIONAL EQUIPMENT & a. Close to Radiologist Office and Staff ENGINEERING TERMINALS Window Curtain Rail 1 Outlet, 10A,2P,240V, duplex 6 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 1 wall-mounted Outlet, Telephone 1 desktop Outlet, ACU 1 QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-04A QUANTITY REMARKS Updated Reference: April 2016 428


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY CONFERENCE ROOM 250B-RAD-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Radiology Staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 429 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


6500 KEY KEY SCALE 1:100 M SD 1 1 Table, conference 2 Cabinet, low 3 Chair, conference 4 Projection screen 5 Negatoscope 6 Whiteboard 7 Waste bin 3100 6 7 CH 4 2 3 3 3 3 3 3 3 3 3 3 5 SH T D 430


Department: Room Title: RADIOLOGY READING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Radiology staff members meet for conferences, Negatoscope (X-Ray film viewer) 6 discussions or trainings Wall Clock 1 Airconditioning Unit 1 Digitizer, floor-mounted unit 1 Automatic Voltage Regulator 1 Uninterrupted Power Supply 1 Whiteboard 1 Waste bin w/ black lining 1 People Involved: FURNITURE AND 1 x Radiologist FIXTURE CHECKLIST Radiologic Technologist Desk, 600 x 1000mm; with 3 Physicians computer and monitor (linked to Hospital staff imaging units) Desk, 600 x 1200mm; with 3 computer and monitor (linked to imaging units) Chair; swivel-type 6 Shelf, open 1 Pass-through window 1

Planning Relationships ADDITIONAL EQUIPMENT & a. Close to Radiologist Office and Staff ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 10 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, DATA 2 wall-mounted Outlet, Telephone 1 desktop Outlet, ACU 1 REMARKS QUANTITY Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-05A QUANTITY REMARKS Updated Reference: April 2016 431


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY READING ROOM 250B-RAD-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Radiology Staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 432 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


3000 KEY SCALE 1:100 M 6700 KEY 1 Desk, 600 x 1000mm; with computer and monitor (linked to imaging units) 2 Desk, 600 x 1200mm; with computer and monitor (linked to imaging units) 3 Chair; swivel-type 4 Shelf, open SD 1 4 7 5 6 8 9 5 Digitizer, floor-mounted unit 6 AVR and UPS 7 Negatoscope 8 Whiteboard 9 Pass-through window 10 Waste bin, general T D D 1 3 1 7 2 7 2 2 10 3 3 3 3 3 7 7 7 7 433


Department: Room Title: RADIOLOGY FILES ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Radiologic Technician/ Technologist/ Clerk stores Exhaust fan 1 radiographs b. Radiologic Technician/ Technologist/ Clerk retrieves radiographs on file for follow-up of patient conditions Note: Radiographs beyond five years of age will be stored in the central records People Involved: FURNITURE AND 1 x Radiologist FIXTURE CHECKLIST Radiologic Technologist Shelf, open 1 Physicians Aluminum ladder 1 Hospital staff

Planning Relationships ADDITIONAL EQUIPMENT & a. Close to Radiologist Office and Staff ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 3 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, Exhaust fan 2 wall-mounted QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-06A QUANTITY REMARKS Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) 434


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY FILES ROOM 250B-RAD-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Radiology Staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 435 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 1 Shelf, open 2 Ladder, aluminum NOTE : Provide 1000mm clear distance from ceiling to topmost shelf 3000 3900 SD 1 2 436


Department: Room Title: RADIOLOGY ULTRASOUND ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is assisted on to examination table Ultrasound unit 1 b. Ultrasonologist performs specified examination Ultrasound Printer 1 c. Patient and staff use toilet Automatic Voltage Regulator 1 Uninterrupted Power Supply 1 Examination bed 1 Exhaust fan 1 Waste bin w/ black lining 1 People Involved: FURNITURE AND 1 x Ultrasonologist FIXTURE CHECKLIST 1 x Patient Table, with computer 1 Desk, 600 x 1200mm 1 Stool, adjustable 1 Chair, upright; stacking 2 Footstool 1 Counter, with cabinets below 1 Sink, stainless steel 1 Concealed floor drain 1 Cubicle curtain and rod 1

Water Closet 1 Lavatory 1 Hook, wall-mounted 1 Planning Relationships ADDITIONAL EQUIPMENT & a. Close to X-ray Room ENGINEERING TERMINALS b. Close to Waiting Area Window Curtain Rail 2 Outlet, 10A,2P,240V, duplex 7 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Outlet, 30A,2P,240V 1 for ultrasound machine Smoke detector 1 Outlet, DATA 1 wall-mounted Outlet, Telephone 1 QUANTITY REMARKS QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-07A QUANTITY REMARKS Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) 437


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY ULTRASOUND ROOM 250B-RAD-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit Radiology Staff & patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 438 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 1 Examination bed 2 Ultrasound machine 3 Table, with computer 4 Automatic Voltage Regulator (AVR) 5 Desk, 600 x 1200mm 6 Stool, adjustable 7 Chair, upright; stacking 8 Footstool 3100 1900 4600 T D SD 1 2 3 4 5 6 7 7 8 9 10 11 13 12 14 16 15 SH CH 9 Counter, with cabinets below 10 Sink, stainless steel 11 Concealed floor drain 12 Uninterrupted Power Supply (UPS) 13 Cubicle curtain and rod 14 Toilet 15 Hook, wall-mounted 16 Waste bin 439


Department: Room Title: RADIOLOGY MAMMOGRAPHY ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient enters room; enters dress cubicle to change into hospital gown Mammography machine 1 b. Patient stands in front of mammography machine and control unit

c. 1 breast will be placed on the X-Ray plate. To ensure a Negatoscope 1 clear and correct image, the technologist may palpate the breast before placing it on the plate. d. The technologist operates the machine, bringing down the top plate to compress the breast against the X-Ray plate. Patient is asked to hold breath while image is being taken. e. Technologist will operate the controls, taking 2 pictures at different angles of each breast FURNITURE AND f. When the 1st breast is finished, the patient FIXTURE CHECKLIST undergoes the same procedures with the 2nd breast Chair, upright 1 g. After the X-Rays have been taken, patient waits for Stool, adjustable height 1 the films to be examined by a radiologist to ensure Hamper, soiled linen 1 that the images are clear. Additional images will be
Hook, wall-mounted 1 taken if images are not satisfactory. Cubicle curtain with rod 1 h. If images are already satisfactory, patient is asked to dress back into street clothes; hospital gown is placed into soiled linen hamper

People Involved 1 x Patient 1 x Technologist Planning Relationships ADDITIONAL EQUIPMENT & a. Accessible to Waiting Area ENGINEERING TERMINALS b. Accessible to Dress Cubicle/s Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 emergency light Outlet, telephone outlet 1 Smoke detector 1 Window curtain rail 1

250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-08A QUANTITY REMARKS Updated Reference: April 2016 QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 440 Waste bin 1


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY MAMMOGRAPHY ROOM 250B-RAD-RDS-08B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light
ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit radiology staff & patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 441 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


6500 KEY 3150 KEY SCALE 1:100 M 1 Mammography unit 2 Mammo control unit 3 Chair, upright 4 Stool, adjustable height 5 Negatoscope SD SH 1 2 3 4 5 7 9 9 6 10 11 6 Dress cubicle 7 Hamper, soiled linen 8 Hook, wall-mounted 9 Cubicle curtain with rod 10 Waste bin 11 Indicator light (above door, exterior side) 8 T D 442


Department: Room Title: RADIOLOGY RADIOGRAPHIC X-RAY ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient puts on hospital gown Radiographic X-ray Unit 1 b. X-ray technologist prepares and positions patient Vertical Casette Stand 1 for x-ray examination IV stand 1 c. Patient undergoes radiographic examination X-ray machine transformer 1 d. Patient puts on personal clothing after instructions Waste bin w/ black lining 1 to leave Lead rubber gown/ apron 1 Lead rubber gloves 1 pair Patient caliper 1 Compression band 1 Film ID marker set 1 Lead apron hanger 1 People Involved: Pelvimeter 1 X-ray Technologists Oxygen Tank 1 Patient Contact 90 nadal shields 1 Nurse Upright 90 nadal shields 1 Institution Worker/ Companion X-ray Technologist Interns FURNITURE AND FIXTURE CHECKLIST Footstool 1 Cabinet, storage 1

Indicator light (above door, 1 exterior side) Water Closet 1 Lavatory 1 ADDITIONAL EQUIPMENT & a. Close to Outpatient Department ENGINEERING TERMINALS b. Close to Emergency Department Outlet, 10A,2P,240V, duplex 8 grounding type, c. Close to other Ancillary Services

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Outlet, Airconditioning unit 1 Window type Smoke detector 1 Outlet, DATA 1 wall-mounted Outlet, Telephone 1 ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-09A QUANTITY REMARKS Updated Reference: April 2016 QUANTITY REMARKS REMARKS QUANTITY Planning Relationships Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) 443


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY RADIOGRAPHIC X-RAY ROOM 250B-RAD-RDS-09B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY Cooling load (TR) 2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C)
Access limit Radiology Staff & patient Fire risk LOW: medium: high Other risks exposure to radiation ROOM DATA SHEET 444 Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 1 Radiographic X-Ray Machine 2 Transformer 3 X-Ray cassette stand, vertical 4 Lead apron rack 5 Footstool 6 IV stand 7 Oxygen tank 4200 3000 3600 4200 6350 1800 2550 SD 8 Cabinet, storage 9 Indicator light (above door, exterior side) 10 TOILET 11 DARK ROOM 12 CONTROL ROOM 13 Waste bin 2000 1 2 3 4 5 6 7 8 9 10 11 12 13 (SHARED) T D 445


Department: Room Title: RADIOLOGY RADIOGRAPHIC X-RAY CONTROL ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. X-ray Radiologic Technician/Technologist formulates/ sets Control console 1 radiographic techniques Automatic Voltge Regulator 1 b. X-ray Radiologic Technician/Technologist gives instruction to Lead Glass View Window 2 patient undergoing radiographic examinations
Automatic Film Processor 2 c. X-ray Radiologic Technician/Technologist conducts Waste bin w/ black lining 1 radiographic exposures d. X-ray Radiologic Technician/ Technologist views patient during radiographic examination People Involved: FURNITURE AND X-ray Technicians/ Technologist FIXTURE CHECKLIST RT Interns Chair, swivel 2 Radiologist Cassette rack 2 Resident Physician

Planning Relationships ADDITIONAL EQUIPMENT & a. Adjacent to X-ray Rooms ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Power supply for x-ray machine 1 1 dia. Or 3 dia. Smoke detector 1 QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-10A QUANTITY REMARKS Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) 446


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY RADIOGRAPHIC X-RAY CONTROL ROOM 250B-RAD-RDS-10B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50% Black out ESSENTIAL:desirable:unnecessary Cooling load (TR) 1 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Radiology Staff & patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 447 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 2550 4200 1 Control console 2 Cassette rack 3 Automatic film processorr 4 Automatic voltage regulator 5 Chair, swivel 6 Window, with lead glass panel SD 1 2 2 3 3 4 5 5 1 6 6 448


Department: Room Title: RADIOLOGY RAD-FLUOROSCOPIC X-RAY ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient puts on hospital gown Radiographic-Fluoroscopic X-ray Unit 1 b. X-ray technologist prepares contrast medium Bucky Vertical Casette Stand 1 c. X-ray technologist prepares and position patient IV stand 1 d. X-ray radiologist introduces contrast medium X-ray machine transformer 1 e. Patient undergoes radiographic and/ or fluoroscopic Waste bin w/ black lining 1 examination Lead rubber gown/ apron 1 f. Patient uses toilet Lead rubber gloves 1 pair Patient caliper 1 Compression band 1 Film ID marker set 1 Lead apron hanger 1 People Involved: Immobilizing device 1 X-ray Technologists Oxygen Tank 1 Patient Contact 90 nadal shields 1 Nurse Upright 90 nadal shields 1 Institution Worker/ Companion Barium preparation gadgets 1 X-ray Technologist Interns Lead goggles 1 Radiologist Thyroid shield 1 FURNITURE AND FIXTURE CHECKLIST Counter, w/ cabinets above & below 1 Cabinet, mobile 1

Sink, stainless steel 1 Footstool 1 Monitor, vital signs 1 Hamper, soiled linen 1 Sharps disposal unit 1 Clock 1 Concealed floor drain 1 a. Close to Outpatient Department Indicator light 1 b. Close to Emergency Department ADDITIONAL EQUIPMENT & c. Close to other Ancillary Services ENGINEERING TERMINALS

Outlet, 10A,2P,240V, duplex 8 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Outlet, Airconditioning unit 1 Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1 Planning Relationships Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-11A QUANTITY REMARKS Updated Reference: April 2016 449


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY RAD-FLUOROSCOPIC X-RAY ROOM 250B-RAD-RDS-11B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50% Black out ESSENTIAL:desirable:unnecessary Cooling load (TR) 2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) Access limit Radiology Staff & patient Fire risk LOW: medium: high Other risks exposure to radiation ROOM DATA SHEET 450 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 5250 1550 4650 2150 6350 1800 2550 1960 SD 1 Rad/Fluoro X-Ray Machine 2 Transformer 3 Counter, with cabinets above and below 4 Cabinet, mobile 5 Sink, stainless steel 6 IV stand 7 Lead apron rack 8 Footstool 9 Monitor, vital signs 10 Hamper, soiled linen 11 Sharps disposal unit 12 Clock 13 Waste bin, infectious 14 Concealed floor drain 15 Medical gas console : Air, Oxygen, Vacuum) 16 Indicator light (above door, exterior side) 17 TOILET 18 CONTROL ROOM 19 DARK ROOM 1 2 3 4 5 6 7 8 13 11 12 9 10 14 15 16 17 18 19 CH T D 6800 451


Department: Room Title: RADIOLOGY CT-SCAN FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient puts on hospital gown Radiographic unit, Computerized 1 b. Radiologic Technologist prepares and position patient c. for CT-Scanning procedure Emergency kit 1 d. Patient undergoes CT-Scanning procedure IV stand 1 e. Patient uses toilet Transformer & Power Distrubution 2 Unit Negatoscope 1 CT Injector Unit 1 Lead rubber gown 1 Lead rubber gloves 1 pair Dehumidifier 1 People Involved: Medical gas console : (Air, 1 1 x Radiologic Technologist Oxygen, Vacuum) 1 x Radiologist Waste bin w/ yellow lining 1 Patient Patient's Companion FURNITURE AND RT Intern FIXTURE CHECKLIST Counter, with cabinets above and bel 1 Cabinet, mobile 1 Sink, stainless steel 1 Footstool 1 Concealed floor drain 1

Indicator light (above door, 1 exterior side) 1 Lead apron rack 1 Clock 1 Lavatory 1 water closet 1 ADDITIONAL EQUIPMENT & QUANTITY REMARKS a. Close to Outpatient Department ENGINEERING TERMINALS b. Close to Emergency Department Outlet, 10A,2P,240V, duplex 6 grounding type, c. Close to other Ancillary Services

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Outlet, Airconditioning unit 2 Split-type Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1 Hospital Pole Transformer 1 75 KVA min., 3 dia. Standby Generator Set 1 75 KVA min., 3 dia. Reference Sheet Number: 250B-RAD-RDS-12A QUANTITY REMARKS Updated Reference: April 2016 Planning Relationships Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) QUANTITY REMARKS ROOM DATA SHEET Hospital: 452 Tomography


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY CT-SCAN 250B-RAD-RDS-12B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50% Black out ESSENTIAL:desirable:unnecessary Cooling load (TR) 2.8 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Radiology Staff & patient Fire risk LOW: medium: high Other risks exposure to radiation ROOM DATA SHEET 453 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:150 M SD 1 2 3 5 CH 8 6350 4800 2200 7080 1 Radiographic unit, Computerized Tomography 2 Transformer & power distribution unit 3 Counter, with cabinets above and below 4 Cabinet, mobile 5 Sink, stainless steel 6 IV stand 7 Lead apron rack 8 Footstool 9 Negatoscope 10 CT injector unit 11 Sharps disposal unit 12 Clock 13 Waste bin 14 Concealed floor drain 15 Medical gas console : Air, Oxygen, Vacuum) 16 Indicator light (above door, exterior side) 17 TOILET 18 CONTROL ROOM 2 4 6 11 12 13 10 9 14 7 15 16 17 18 D T 1650 454


Department: Room Title: RADIOLOGY CT-SCAN CONTROL ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Radiologic Technician/Technologist formulates/ sets
Control console 1 CT techniques Automatic Voltage Regulator 1 b. Radiologic Technician/Technologist gives instruction to
Lead Glass View Window 1 patient undergoing CT-Scans Automatic Film Processor 1 c. Radiologic Technician/Technologist conducts
Waste bin w/ black lining 1 CT-Scan examination Uninterrupted Power Supply 1 d. Radiologic Technician/ Technologist views patient
Surge Supressor 1 during CT-Scan examinations People Involved: FURNITURE AND Radiologic Technologist FIXTURE CHECKLIST RT Interns Desk, with computer & printer 1 Radiologist Chair, swivel 2 Resident Physician Clock 1 Whiteboard 1

Planning Relationships ADDITIONAL EQUIPMENT & a. Adjacent to CT-Scan ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Power supply for CT-Scan 1 1 dia. Or 3 dia. Smoke detector 1 Outlet, Telephone 1 Outlet, Data 1 QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-13A QUANTITY REMARKS Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) 455


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY CT-SCAN CONTROL ROOM 250B-RAD-RDS-13B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50% Black out ESSENTIAL:desirable:unnecessary Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Radiology Staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 456 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


SCALE 1:100 M 1 Control console 2 Desk, with computer & printer 3 Chair, swivel 4 Clock 5 Whiteboard 6 Waste bin KEY 4800 2280 SD 1 2 3 3 4 5 6 T D 457


Department: Room Title: RADIOLOGY MRI MAGNET ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient enters room wearing hospital gown MRI Machine 1 b. Patient is positioned by technologist on the Penetration panel 1 moveable examination table. Oxygen monitor/depletion 1 c. Patient will be fitted with devices depending alarm

on requirement of procedure d. If necessary, physician, technologist, or nurse will insert IV line into patient's hand/arm and inject contrast media. e. Patient will be placed into the magnet of the MRI unit and radiologist and technologist will perform the examination from the control room f. After images have been taken, patient waits FURNITURE AND until radiologist and technologist checks the FIXTURE CHECKLIST images to ensure that no additional images are Footstool 1 necessary IV Stand 1 g. IV line is removed, and patient is asked to dress Sharps disposal unit 1 back into street clothes; hospital gown is placed Cabinet, storage 1 into soiled linen hamper People Involved: 1 x Patient 1 x Technologist Planning Relationships ADDITIONAL EQUIPMENT & a. Adjacent to MRI Control Room ENGINEERING TERMINALS b. Adjacent to MRI System Component Room Outlet, 10A,2P,240V, duplex 8 grounding type, c. Near Imaging Department

universal slots d. Accessible from ER Department Outlet, 10A,2P,240V, single 1 emergency light e. Accessible from OPD Medical gas console (Air, 1 f. Accessible from Nursing Wards Oxygen, Vacuum flowmeter)

Updated Reference: QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU HEALTH FACILITY April 2016 250-Bed (Level 3) QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-14A QUANTITY REMARKS 458 Medgas Console 1


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY MRI MAGNET ROOM 250B-RAD-RDS-14B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out ESSENTIAL:desirable:unnecessary Cooling load (TR) 2.5 - 3 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit MRI, radiology staff & patient Fire risk LOW: medium: high Other risks exposure to radiation ROOM DATA SHEET 459 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 5900 7300 2 8 1 MRI Machine 2 Penetration panel (locate between MRI Magnet Room and System Component Room) 3 Footstool 4 IV stand 5 Sharps disposal unit 6 Medical gas console : Air, Oxygen, Vacuum) 7 Oxygen monitor / depletion alarm 8 Cabinet, storage 3 4 5 6 7 1 460


Department: Room Title: RADIOLOGY MRI CONTROL ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. MRI technologist prepares MRI technique/ MRI control console 1 program per patient's requirement Clock 1 b. After briefing and preparing the patient in the

MRI Magnet Room, technologist returns to

Control Room c. Technologist performs MRI examination on patient from Control Room d. Technologist checks the images before informing the patient that examination is finished f. If necessary, technologist performs additional FURNITURE AND examination on patient FIXTURE CHECKLIST Desk 1 Computer with printer 1 Chair, swivel 1 Whiteboard 1 People Involved: Waste bin 1 1 x Technologist 1 x Radiologist

Planning Relationships ADDITIONAL EQUIPMENT & a. Adjacent to MRI Magnet Room ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 emergency light REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-15A QUANTITY REMARKS Updated Reference: QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU HEALTH FACILITY April 2016 250-Bed (Level 3) QUANTITY 461


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY MRI CONTROL ROOM 250B-RAD-RDS-15B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out ESSENTIAL:desirable:unnecessary Cooling load (TR) 2.5 - 3 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit MRI, radiology staff Fire risk LOW: medium: high Other risks exposure to radiation ROOM DATA SHEET 462 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


SCALE 1:100 M 1 Control console 2 Desk, with computer & printer 3 Chair, swivel KEY 4 Clock 5 Whiteboard 6 Waste bin 5500 9000 SD 1 2 3 4 5 6 3 T D 463


Department: Room Title: RADIOLOGY MRI SYSTEM COMPONENT ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Location of MRI system components MRI system components

refer to vendor for qty

MRI magnet chiller

refer to vendor for qty Note : MRI magnet chiller located remotely Penetration panel

located between

MRI Magnet Room & Sys Component Room People Involved: FURNITURE AND 1 x Technologist FIXTURE CHECKLIST 1 x Radiologist

Planning Relationships ADDITIONAL EQUIPMENT & a. Adjacent to MRI Magnet Room ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1 Updated Reference: QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU HEALTH FACILITY April 2016 250-Bed (Level 3) QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-16A QUANTITY REMARKS 464


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY MRI SYSTEM COMPONENT ROOM 250B-RAD-RDS-16B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) refer to supplier Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) refer to supplier Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) refer to supplier Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration refer to supplier Privacy essential:desirable:UNNECESSARY Humidity (%RH) refer to supplier Black out essential:desirable:UNNECESSARY Cooling load (TR) refer to supplier SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit MRI, radiology staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 465 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


2200 KEY 6100 KEY SCALE 1:100 M SD 1 3 2 1 MRI system components (per MRI vendor) 2 MRI magnet chiller (remotely located) 3 Penetration panel (locate between MRI Magnet Room and System Component Room) 2 466


Department: Room Title: RADIOLOGY DARK ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. X-ray Technician/Technologist mixes/ prepares processing Manual Film Processing tank 1 b. X-ray Technician/Technologist loads unexposed X-ray films Leaded pass box 1 to the casette Safelight 1 c. X-ray Technician/Technologist unloads exposed X-ray films Automatic Film Processor 1 from the casette for processing X-ray casetter w/ intensifying screens 1 d. X-ray Technician/ Technologist processes X-ray film Exhaust fan 1 X-ray Technician/ Technologist cleans manual processing Luminous timer 1 tanks and automatic processor Film hanger rock 1 X-ray Technician/ Technologist maintains processing Waste bin w/ yellow lining 1 equipment and performs dark room quality control tests Metallic Stem dial type thermometer 1 Towel bar 1 Film Dryer 1 Plastic Paddles 2 Patient ID film marker 1 People Involved: X-ray Radiologic Technologist Radiology Department Staff X-ray Interns FURNITURE AND FIXTURE CHECKLIST Film loading counter 1 Counter, with cabinets above and 1

below Sink, stainless steel 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & a. Close to X-ray Room ENGINEERING TERMINALS b. Adjacent to Control Room Outlet, 10A,2P,240V, duplex 3 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 1 Outlet, Telephone 1 Outlet, Data 1 ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-17A QUANTITY REMARKS Updated Reference: April 2016 REMARKS QUANTITY Planning Relationships Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) QUANTITY REMARKS 467


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY DARK ROOM 250B-RAD-RDS-17B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50% Black out ESSENTIAL:desirable:unnecessary Cooling load (TR) 1 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Radiology Staff Fire risk low: MEDIUM : high Other risks NA ROOM DATA SHEET 468 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


KEY SCALE 1:100 M 1800 1 Film processor 2 Film loading counter 3 Film bin 4 Processing tank 5 Counter, with cabinets above and below 6 Sink, stainless steel 7 Pass-through box 8 Concealed floor drain 9 Exhaust fan, ceiling mounted 10 Waste bin 3000 CH SD 1 T D 4 2 3 5 6 8 9 10 7 469


Department: Room Title: RADIOLOGY STAFF LOUNGE/ T&B FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Lounging area for Radiology staff Waste bin w/ black lining 3 b. Radiology staff stores personal belongings Exhaust fan 1 c. Radiology staff uses toilet facilities Ceiling fan 1 People Involved: FURNITURE AND 10 x Radiologic Technologist FIXTURE CHECKLIST 1 x Ultranologist Table, dining 1 3 x Clerk Chair; dining 4 Resident Physicians Counter, with cabinets above 1 and below Sink, stainless steel 1 Refrigerator 1 Water dispenser 1 Locker, steel, 300 x 500mm 5 Concealed floor drain 1 Slop sink with faucet 1

Shelf, open 1 Water closet 4 Lavatory 4 Urinal 2 Planning Relationships ADDITIONAL EQUIPMENT & a. Adjacent to Radiologist's office ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots

Outlet, 10A,2P,240V, single 1 for emergency light Smoke detector 1 QUANTITY REMARKS QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-RAD-RDS-18A QUANTITY REMARKS Updated Reference: April 2016 Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 250-Bed (Level 3) 470


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 RADIOLOGY STAFF LOUNGE/ T&B 250B-RAD-RDS-18B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:desirable:UNNECESSARY % Dust filtration 93% - 99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.75 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit Radiology Staff Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET 471 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


SCALE 1:150 M KEY 3000 3000 3000 1900 10 9 9 11 12 13 14 3900 1 CH 2 3 4 5 6 7 8 9 7 7 7 7 2 2 2 SD 1 Table, dining 2 Chair; dining 3 Counter, with cabinets above and below 4 Sink, stainless steel 5 Refrigerator 6 Water dispenser 7 Locker, steel, 300 x 500mm 8 Concealed floor drain 9 Waste bin 10 FEMALE STAFF TOILET 11 MALE STAFF TOILET 12 JANITOR'S CLOSET 13 Slop sink with faucet 14 Shelf, open 11800 472


VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.5 NURSING SERVICE FACILITIES

First Edition DEPARTMENT OF HEALTH Manila 2017 473


Hospital: 250-Bed (Level 3) Hospital Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER 178.00 42.00 250B-NU-RDS-01 12.00 250B-NU-RDS-02 21.00 250B-NU-RDS-03 31.00 250B-NU-RDS-04 18.00 250B-NU-RDS-05 36.00 250B-NU-RDS-06 Isolation Room (Typical) 18.00 250B-NU-RDS-07 Conference Room Patient Room (Typical) PAGE Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU NURSING WARDS

250B-NU-SFSI-01 NURSING WARDS Reference Sheet Number: SERVICE FACILITY SHEET INDEX

Service Facility Title: ROOM TITLE Nurse Station Treatment Area 4-Bed Ward (Typical)

Department Head's Office

250B-NU-DDS-01 476 477 475 480 483 486 489 492 495


476


Department: Room Title: NURSING WARDS NURSE STATION FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Nurse makes plan of her activities and determines Nurse call console 1 priorities Rack, chart 1 b. Nurse makes proper inventory of available resources: E-cart 1 supplies, medicine, etc.; to determine requisitions Whiteboard 1 c. Nurse prepares for admission of patient Clock 1 d. Nurse enters name of patient in admission book, Sharps container 1 ward directory, and diet work book Hamper, dirty linen 1 e. Nurse makes phones calls to coordinate with other Computer 1 hospital units regarding admitted patient Waste bin w/ yellow lining 1 infectious f. Nurse entertains queries from visitors of patient Waste bin w/ black lining 1 general g. Nurse records and reports patient care activities and observations made h. Nurse receives endorsements i. Nurse carries out doctor's orders FURNITURE AND j. Nurse prepares and gives out medication FIXTURE CHECKLIST k. Nurse conducts health education Counter, 2-level 1 l. Nurse transfers patient to examining table Table, 6-seater 1 m. Physician/Nurse administers necessary medical and Chair, upright; stacking 6 surgical treatment to patient Stool, adjustable height 2 Counter, with cabinets above 1 and below Sink 2 People Involved: Concealed floor drain 1 1 x Chief Nurse Desk, 600 x 1200mm; with 1 2 x Staff Nurse computer and printer 1 x Nursing Attendant Chair, swivel 1 Physicians Shelf 1 Cabinet 1 Sink, deep 1 Stretcher / wheelchair nook 1 Lavatory 1 Water closet 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Nursing Wards ENGINEERING TERMINALS b. Adjacent to Utility Rooms and Linen Rooms Window curtain rail 1 c. Close to Treatment Room Outlet, 10A,2P,240V, duplex 12 grounding type, universal Outlet, 10A, 2P, 240V, single 3 for emergency light Outlet, telephone 2 Outlet, DATA 2 Paging System 1 Smoke detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-NU-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS REMARKS REMARKS QUANTITY QUANTITY QUANTITY 477


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NURSING WARDS NURSE STATION 250B-NU-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General Illumination (LUX) 750 Room temperature (°C) 23 Night illumination (LUX) 750 Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.8 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be Tonal Impact Domestic hot water: at medical preparation sink tolerated Maximum temperature (°C) 70 Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 478 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NURSING WARDS NURSE STATION 250B-NU-RDS-01C TECHNICAL DESIGN DATA: LAYOUT OF ROOM AND SPACE COMPONENTS: DIRECT SERVICES DESIGN DATA

Disposal hospital solid waste type: A, B, G Hot Water required at medical sink Cold Water required at sink & toilet fixtures Drainage req'd at sink, toilet fixt. & floor Gas NA Compressed Air NA Steam NA Others

DIRECT DEMANDS ON FLOOR AND WALL Loading NA Spillage SLIGHT:occasional:frequent Foot Traffic light:MEDIUM:heavy Wheel Traffic NA Impacts NA Abrasion NA Easy Maintenance ESSENTIAL:desirable:unnecessary Vibration Free essential:DESIRABLE:unnecessary Door Set NA, open to circulation Windows NA Internal Glazing NA Space Components Minimum Space Required/Component (sq.m.) Work Area Medicine Preparation Toilet

REGULATIONS AND NOTES: ROOM DATA SHEET SPACE DEMANDS (Total Minimum Space Required in sq.m.) : NA 479 KEY SCALE 1:150 M 4000 NURSE STATION: 1 Counter, 2-level 2 Table, 6-seater 3 Chair, upright; stacking 4 Stool, adjustable height 5 Rack, chart 6 Nurse call console 7 E-cart 8 Whiteboard 9 Clock MEDICATION PREPARATION & CLEAN UTILITY: 10 Counter, with cabinets above and below 11 Sink 12 Concealed floor drain 13 Waste bin, general 14 Waste bin, infectious 15 Sharps container OFFICE: 16 Desk, 600 x 1200mm; with computer and printer 17 Chair, swivel 18 Shelf CLEAN LINEN: 19 Cabinet DIRTY UTILITY/DIRTY LINEN: 20 Sink, deep 21 Hamper, dirty linen 22 Stretcher / wheelchair nook 4300 1700 SD T D CH CH CH T D CH 1 5 4 2 3 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 2000 3000 22 11


Department: Room Title: NURSING WARDS TREATMENT AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on foot, in wheelchair or on a Footstool 1 stretcher trolley from ward Table, instrument 1 b. Transfer of patient from wheelchair or stretcher Table, Mayo 1 trolley to examining table Cart, dressing 1 c. Physician or nurse administers necessary medical, Examination lamp 1 surgical and/or first-aid treatment to patient IV / Irrigator stand 1 Negatoscope 1 Nurse call 1 Whiteboard 1 Kick bucket 1 Sharps container 1 Waste bin w/ yellow lining 1 infectious Waste bin w/ black lining 1 general

People Involved: FURNITURE AND 1 x Physician FIXTURE CHECKLIST 1 x Nurse/ Nursing Attendant Examination table 1 1 x Patient Stool, adjustable height 1 Counter, with cabinets above 1 and below Sink, combination scrub and 1 instrument; with goose-neck foot-operated/elbow control Cubicle curtain and rod or 1 PVC folding partition Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Nurse Station ENGINEERING TERMINALS b. Close to Inpatient Nursing Wards Window curtain rail 1

Nurse call station, emergency 1 Outlet, 10A,2P,240V, duplex 5 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke Detector 1 QUANTITY REMARKS Hospital: 250-Bed (Level 3) Reference Sheet Number: 250B-NU-RDS-02A QUANTITY REMARKS QUANTITY REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 480


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NURSING WARDS TREATMENT AREA 250B-NU-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.8 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: at sink & toilet lavatory tolerated Maximum temperature (°C) 70 Access limit medical staff & patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 481 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NURSING WARDS TREATMENT AREA 250B-NU-RDS-02C TECHNICAL DESIGN DATA: LAYOUT OF ROOM AND SPACE COMPONENTS: DIRECT SERVICES DESIGN DATA

Disposal hospital solid waste type: A,B,G Hot Water required at sink Cold Water required at sink

Drainage required at floor below sink Medical Oxygen 20 lpm @ 4.0 Bar Medica Vacuum 40 lpm @ 450mm Hg Compressed Air NA Steam NA Others 1 Nurse Call (to Nurse Station) DIRECT DEMANDS ON FLOOR AND WALL Loading NA Spillage SLIGHT:occasional:frequent Foot Traffic light:MEDIUM:heavy Wheel Traffic light:MEDIUM:heavy Impacts NA Abrasion NA Easy Maintenance ESSENTIAL:desirable:unnecessary Vibration Free ESSENTIAL:desirable:unnecessary Door Set examining table, wheel- chair & stretcher access Windows clear, solar control, Space Components Minimum Space Required/Component (sq.m.) privacy control Treatment Area Internal Glazing NA

REGULATIONS AND NOTES: Provide window shade ROOM DATA SHEET SPACE DEMANDS (Total Minimum Space Required in sq.m.) : 4000 3000 SD 1 3 2 4 5 6 7 8 9 10 11 12 14 15 16 17 18 19 13 CH KEY SCALE 1:100 M 1 Examination table 2 Stool, adjustable height 3 Footstool 4 Counter, with cabinets above and below 5 Table, instrument 6 Table, Mayo 7 Cart, dressing 8 Sink, combination scrub and instrument; with goose-neck foot-operated/elbow control 9 Examination lamp 10 IV / Irrigator stand 11 Negatoscope 12 Nurse call 13 Whiteboard 14 Cubicle curtain and rod or PVC folding partition 15 Kick bucket 16 Concealed floor drain 17 Waste bin, infectious 18 Waste bin, general 19 Sharps container 482


Department: Room Title: NURSING WARDS DEPARTMENT HEAD'S OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Department Head reads, writes and uses telephone Waste bin w/ black lining 2 general on his desk b. Department Head receives visitors c. Department Head is consulted by patients/relatives d. Secretary stores, files and retrieves records e. Department Head supervises the nursing department's activities People Involved: FURNITURE AND 1 x Department Head FIXTURE CHECKLIST Physicians Clerical desk 1 Nurses Executive desk, 1200mm x 600mm 1 Visitors Shelves 1 Table, side; 400 x 400mm 1 Chair, upright; stacking 4 Visitor's Chair 1 Executive chair w/ armrest 1 Sofa, 2-seater 1 Steel filing cabinet 3 Lavatory 1 Water closet 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Department's main entrance ENGINEERING TERMINALS b. Close to Inpatient Nursing Wards Station Window curtain rail 1 Outlet, 10A,2P,240V, duplex 6 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 for emergency light Outlet, Telephone 2 Outlet, DATA 2 Smoke Detector 1 QUANTITY REMARKS 250B-NU-RDS-03A QUANTITY REMARKS QUANTITY REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 483


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NURSING WARDS DEPARTMENT HEAD'S OFFICE 250B-NU-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) 70 Access limit Department Head, Staff, Visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 484 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


485 NA


Department: Room Title: NURSING WARDS CONFERENCE ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Department Head receives visitors Whiteboard / projection screen 1 b. Department Head is consulted by patients/relatives Waste bin w/ black lining 1 c. Department Head conducts staff meetings and LCD Projector 1 special lectures Sound System 1 People Involved: FURNITURE AND 1 x Department Head FIXTURE CHECKLIST Physicians Table, 500 x 1500mm 6 Nurses Counter, with cabinets above 1 Visitors and below 1 Chair, upright; stacking 12 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Department's main entrance ENGINEERING TERMINALS b. Close to Inpatient Nursing Wards Station Window curtain rail 2 Outlet, 10A,2P,240V, duplex 6 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 for emergency light Outlet, Telephone 1 Outlet, DATA 1 Smoke Detector 1 Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS QUANTITY REMARKS 250B-NU-RDS-04A QUANTITY REMARKS 486


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NURSING WARDS CONFERENCE ROOM 250B-NU-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 400-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) 70 Access limit Department Head, Staff, Visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 487 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


NA 488


Department: Room Title: NURSING WARDS PATIENT ROOM (TYPICAL) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on foot, in wheelchair or on a stretcher Television 1 trolley Console, bedhead 1 b. Transfer of patient to a hospital bed from a Waste bin w/ yellow lining 1 infectious wheelchair or a stretcher trolley and vice versa Waste bin w/ black lining 2 non-biodegradable c. Patient undresses/dresses in the vicinity of Water Heater 1 hospital bed, with or without assistance

d. Patient takes meal in bed or in sitting area FURNITURE AND e. Patient receives visitors FIXTURE CHECKLIST f. Patient stores clothing and other personal Hospital bed, adjustable; with 1 belongings adjustable side rails g. Patient requires privacy Chair, upright; stacking 1 h. Patient uses toilet and bath Footstool 1 i. Use of monitoring/ diagnostic equipment on the patient Bench, cushioned 1 j. Physicians and nurses check on patients Table, side; with cabinet 1 k. Handwashing and other clean up activities Table, overbed 1 l. Nurse gives medication to patient Closet, wardrobe 1 m. Nurse may feed or wash patient, in the absence of Lavatory, wall-hung 1 at strategic locations a relative or watcher along corridor Concealed floor drain 1 Water Closet w/ spray hose 1 Lavatory 1 People Involved: Shower Set 1 1 x Patient 2 x Visitors ADDITIONAL EQUIPMENT & 1 x Resident Physician/ Medical Specialist ENGINEERING TERMINALS 1 x Nurse or Nursing Aide Window curtain rail 1 Bedhead light w/ night lamp 1 fluorescent, 20W

w/ pendant switch Outlet, 10A,2P,240V, duplex 6 grounding type, Planning Relationships:

universal a. Close to Nurse Station Outlet, 10A,2P,240V, single 1 for emergency light b. Close to Medical/Surgical Services Nurse call station, normal 1 w/ pendant switch c. Distant from Out-patient Department Nurse call station, emergency 1 w/ pendant switch Outlet, antenna/Cable 1 Smoke Detector 1 REMARKS QUANTITY QUANTITY REMARKS ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) 250B-NU-RDS-05A QUANTITY REMARKS Updated Reference: Reference Sheet Number: April 2016 489


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NURSING WARDS PATIENT ROOM (TYPICAL) 250B-NU-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) 50 Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit medical staff, relatives/watcher & patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 490 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


491


Department: Room Title: NURSING WARDS 4-BED WARD (TYPICAL) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on foot, in wheelchair or on a stretcher Television 1 trolley Console, bedhead 4 b. Transfer of patient to a hospital bed from a Waste bin w/ yellow lining 1 infectious wheelchair or a stretcher trolley and vice versa Waste bin w/ black lining 2 non-biodegradable c. Patient undresses/dresses in the vicinity of Water Heater 1 hospital bed, with or without assistance

d. Patient takes meal in bed or in sitting area FURNITURE AND e. Patient receives visitors FIXTURE CHECKLIST f. Patient stores clothing and other personal Hospital bed, adjustable; with 4 belongings adjustable side rails g. Patient requires privacy Chair, upright; stacking 4 h. Patient uses toilet and bath Footstool 4 i. Use of monitoring/ diagnostic equipment on the patient Cubicle curtain and rod 4 j. Physicians and nurses check on patients Table, side; with cabinet 4 k. Handwashing and other clean up activities Table, overbed 4 l. Nurse gives medication to patient Closet, wardrobe 4 m. Nurse may feed or wash patient, in the absence of Lavatory, wall-hung 1 at strategic locations a relative or watcher along corridor Concealed floor drain 2 Water Closet w/ spray hose 1 Lavatory 1 People Involved: Shower Set 1 4 x Patient 4 x Visitors ADDITIONAL EQUIPMENT & 1 x Resident Physician/ Medical Specialist ENGINEERING TERMINALS 1 x Nurse or Nursing Aide Window curtain rail 1 Bedhead light w/ night lamp 4 fluorescent, 20W

w/ pendant switch Outlet, 10A,2P,240V, duplex 16 grounding type, Planning Relationships:

universal a. Close to Nurse Station Outlet, 10A,2P,240V, single 1 for emergency light b. Close to Medical/Surgical Services Nurse call station, normal 1 w/ pendant switch c. Distant from Out-patient Department Nurse call station, emergency 1 w/ pendant switch Outlet, antenna/Cable 1 Smoke Detector 1 Hospital: 250-Bed (Level 3) 250B-NU-RDS-06A QUANTITY REMARKS Updated Reference: Reference Sheet Number: April 2016 REMARKS QUANTITY QUANTITY REMARKS ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 492


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NURSING WARDS 4-BED WARD (TYPICAL) 250B-NU-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) 50 Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit medical staff, relatives/watcher & patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 493 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


494


Department: Room Title: NURSING WARDS ISOLATION ROOM (TYPICAL) FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on foot, in wheelchair or on a stretcher Television 1 trolley Waste bin w/ yellow lining 1 infectious b. Transfer of patient to a hospital bed from a Waste bin w/ black lining 1 general wheelchair or a stretcher trolley and vice versa Water Heater 1 c. Patient undresses/dresses in the vicinity of Console, bedhead 1 hospital bed, with or without assistance

d. Patient takes meal in bed or in sitting area FURNITURE AND QUANTITY REMARKS e. Patient receives visitors FIXTURE CHECKLIST f. Patient stores clothing and other personal Hospital bed, adjustable; with 1 belongings adjustable side rails g. Patient requires privacy Chair, upright; stacking 1 h. Patient uses toilet and bath Footstool 1 i. Patient uses monitoring/diagnostic equipment Bench, cushioned 1 j. Physicians and nurses check on patients Table, side; with cabinet 1 k. Handwashing and other clean up activities Table, overbed 1 l. Nurse gives medication to patient Closet, wardrobe 1 m. Nurse may feed or wash patient, in the absence of Lavatory, wall-hung 1 a relative or watcher Concealed floor drain 1 Cabinet, PPE 1 Water closet 1 Lavatory 1 People Involved: Shower set 1 1 x Patient 2 x Visitors ADDITIONAL EQUIPMENT & 1 x Resident Physician/ Medical Specialist ENGINEERING TERMINALS 1 x Nurse or Nursing Aide Window curtain rail 1 Bedhead light w/ night lamp 1 fluorescent, 20W Outlet, 10A,2P,240V, duplex 7 grounding type,

universal Planning Relationships: Outlet, 10A,2P,240V, single 1 for emergency light a. Acessible to Nurse Station Nurse call station, emergency 1 w/ pendant switch b. Located at end portion of Nursing Ward Outlet, antenna/Cable 1 c. Close to medical/surgical services Smoke Detector 1 QUANTITY REMARKS 250B-NU-RDS-07A QUANTITY REMARKS Updated Reference: April 2016 Reference Sheet Number: ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) 495


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NURSING WARDS ISOLATION ROOM (TYPICAL) 250B-NU-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) 50 Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.75 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit medical staff, relatives/watcher & patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary 496


497


VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.6 BURN UNIT SERVICE FACILITIES

First Edition DEPARTMENT OF HEALTH Manila 2017 499


Hospital: 250-Bed (Level 3) Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER 39.00 Nurse Station 15.00 250B-BU-RDS-01 Patient Cubicle 13.00 250B-BU-RDS-02 Whirlpool Bath 11.00 250B-BU-RDS-03 DEVELOPMENT BUREAU 250B-BU-SFSI-01 BURN UNIT BURN UNIT Reference Sheet Number: SERVICE FACILITY SHEET INDEX Service Facility Title: ROOM TITLE PAGE Department of Health

HEALTH FACILITY 501 503 506 509 502 250B-BU-DDS-01


DN 10600 12000 2700 2400 2100 1500 SURGICAL ICU BURN UNIT 3300 COUNSELLING ROOM COUNSELLING ROOM FAMILY WAITING ROOM VIEWING CORRIDOR CHANGING AREA T CLEAN UTILITY DIRTY UTILITY/ LINEN WHIRLPOOL BATH 4 3 2 1 SCALE 1:300 M 502


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a wheelchair or stretcher trolley Emergency light 1 b. Patient is transferred to bed and vice versa Central monitor (cardiac) 1 c. Nurses and nursing attendants monitor vital E-cart 1 signs of patient at regular intervals EENT diagnostic set 1 d. Nurses and nursing attendants attend to patient's Computer, with monitor and 1 needs at regular intervals: cleaning and dressing printer of wounds, application of medicine, etc. Clock 1 e. High level nursing and medical dependence Rack, chart 1 Waste bin w/ yellow lining 2 hazardous Waste bin w/ black lining 2 FURNITURE AND FIXTURE CHECKLIST Counter, nurse station 1 People Involved: Counter, work, with cabinets 1 Patients above and below 1 x Resident Physician / Medical Specialist Shelf, open 1 1 x Nurse Sink, stainless steel 1 1 x Nursing Attendant Sink, utility 1 Stool, adjustable height 2 Lavatory 1 Water closet 1

ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 8 grounding type,

universal slots Outlet, 10A,2P,240V, single 2 for emergency light Outlet, data 1 Planning Relationships: Outlet, telephone 1 a. Close to patient cubicles Paging system 1

b. Visual control of main entrance and visitors' Nurse call console 1 changing room Split-type, ACU 3-ton 1 Smoke detector 2 QUANTITY REMARKS Updated Reference: ROOM DATA SHEET BURN UNIT Department of Health DEVELOPMENT BUREAU HEALTH FACILITY QUANTITY REMARKS Hospital: NURSE STATION QUANTITY REMARKS 250-Bed (Level 3) APRIL 2016 250B-BU-RDS-01A Reference Sheet Number: 503


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature 23 Night illumination (LUX) 100 Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 12.75 Color rendering ESSENTIAL:desirable:unnecessary Velocity (m.hr.) 900 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Exhaust (psi) NA Daylight essential:DESIRABLE:unnecessary Inlet (psi) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 6 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit patient and medical staff Fire risk LOW: medium : high Other risks infection from bacteria ROOM DATA SHEET APRIL 2016 250B-BU-RDS-01B BURN UNIT NURSE STATION 504


2250 KEY SCALE 1:100 M 6600 1 Counter 2 Computer, with printer 3 Chair; adjustable 4 Counter, with cabinets above and below 5 Sink 6 E-cart 1 2 4 5 6 7 8 9 7 Glass board / white board 8 Clock 9 Waste bin SD D T 3 505


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a wheelchair or stretcher trolley Emergency light 1 b. Patient is transferred to bed and vice versa Volume respirator 1 c. Nurses and nursing attendants monitor vital Sphygmomanometer, wall-mtd 1 signs of patient at regular intervals Ambu bag, adult/pedia 1 d. Nurses and nursing attendants attend to patient's Suction apparatus 1 needs at regular intervals: cleaning and dressing Oxygen gauge 1 of wounds, application of medicine, etc. Tracheostomy set 1 e. High level nursing and medical dependence Infusion pump 1 f. Nurses and nursing attendants screen potentially Respirator/defribrillator 2 infectious visitors Patient headwall 2 g. Nurses and nursing attendants observe barrier IV track 1 technique: use of gloves and gown during contact Bedhead light/lamp 1 with patient, washing or disinfecting of hands patient monitor 1 before donning gloves and after removal of gloves FURNITURE AND FIXTURE CHECKLIST People Involved: Hospital bed, adjustable 1 1 x Patient Bedhead console, w/ med gas 1 1 x Resident Physician Table, overbed 1 1 x Nurse Counter, with storage 1 1 x Nursing Attendant Door, glass; w/ windows 1

ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 8 grounding type, Planning Relationships:

universal slots a. Visible from Burn Unit Nurse Station Outlet, 10A,2P,240V, single 2 for emergency light Outlet, data 1 Outlet, telephone 1 Paging system 1

Nurse call console 1 Smoke detector 2 Hospital: PATIENT CUBICLE 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS April 2016 ROOM DATA SHEET BURN UNIT Department of Health DEVELOPMENT BUREAU HEALTH FACILITY QUANTITY REMARKS QUANTITY REMARKS 250B-BU-RDS-02A Updated Reference: 506


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature 20-22 Night illumination (LUX) 100 Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering ESSENTIAL:desirable:unnecessary Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Exhaust (psi) NA Daylight essential:DESIRABLE:unnecessary Inlet (psi) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) 70 Access limit patient and medical staff Fire risk LOW: medium : high Other risks infection from bacteria ROOM DATA SHEET April 2016 250B-BU-RDS-02B BURN UNIT PATIENT CUBICLE 507


KEY SCALE 1:100 M 1 Hospital bed, adjustable 2 Bedhead console, with medical gas outlets, power outlet, and bedhead light 3 Table, overbed 4 Monitor, patient 5 Counter; for medicine, supplies 6 Light, emergency 7 Alcohol/alcogel station; wall-mounted 8 Waste bin 9 Door, glass; with full windows 10 Window 4100 3000 SD 1 2 3 4 5 6 7 8 9 10 508


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Immersion tub is filled with sterile water Emergency light 1 b. Patient is gently placed in tub (using a transfer patient monitor 1 trolley) Clock 1 c. Nurse/nursing attendant perform initial evaluation d. Nurse/nursing attendant perform debridement, blisters and wounds area cleaned and cared for e. After the hydrotherapy procedure, patient is gently lifted out of the immersion tub f. Patient is returned to his/her cubicle for dressing of wounds, and application of topical antimicrobial agent, and dressed again FURNITURE AND FIXTURE CHECKLIST Immersion tub, stainless steel 1 Counter, with storage 1 People Involved: Cart, supply 1 1 x Patient Towel rack 1 1 x Resident Physician 1 x Nurse 1 x Nursing Attendant

ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Planning Relationships: Outlet, 10A,2P,240V, duplex 4 grounding type, a. Visible from Burn Unit Nurse Station

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Paging system 1 Nurse call console 1 Smoke detector 1

Hospital: WHIRPOOL BATH 250-Bed (Level 3) QUANTITY REMARKS Reference Sheet Number: QUANTITY REMARKS April 2016 QUANTITY REMARKS 250B-BU-RDS-03A Updated Reference: ROOM DATA SHEET BURN UNIT Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 509


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature 22-25 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1,000 Volume (cu.m./hr.-person) 25 Color rendering ESSENTIAL:desirable:unnecessary Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Exhaust (psi) NA Daylight essential:desirable:UNNECCESARY Inlet (psi) NA View out essential:desirable:UNNECCESARY % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SAFETY SOUND Accessible hot surface: NA Acceptable sound level (db) 40 Maximum temperature (°C) NA Speech privacy essential:desirable:UNNECESSARY Domestic hot water: at tub Quality which cannot be tonal impact Maximum temperature (°C) 70 (water temperature tolerated

depends on patient comfort) Access limit patient and medical staff Fire risk LOW: medium : high Other risks infection from bacteria ROOM DATA SHEET April 2016 250B-BU-RDS-03B BURN UNIT WHIRPOOL BATH 510


KEY SCALE 1:100 M 1 Immersion tub; stainless steel 2 Counter, with overhead cabinets 3 Cart, supply 4 Towel rack 5 Floor drain, concealed 6 Clock 4350 2400 SD 1 2 3 4 5 6 511


VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.7 OPERATING ROOM & ICU SERVICE FACILITIES

OR 3.7.1 CSSR 3.7.2

First Edition DEPARTMENT OF HEALTH Manila 2017 513 ICU .3 7 3.


Hospital: 250-Bed (Level 3) Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER OPERATING ROOM COMPLEX 390.00 250B-OR-DDS-01 516 Transfer Area 12.00 250B-OR-RDS-01 517 Pre-Operation Area 23.00 250B-OR-RDS-02 520 Nurse Station 36.00 250B-OR-RDS-03 523 Operating Room 36.00 250B-OR-RDS-04 526 Post-Anesthetic Care Unit (PACU) 78.00 250B-OR-RDS-05 529 Dress, Lockers, T&B 31.00 250B-OR-RDS-06 532 Lounge 24.00 250B-OR-RDS-07 535 Anesthesiologist's Office 30.00 250B-OR-RDS-08 538 Anesthesia Storage 7.00 250B-OR-RDS-09 541 Sterile Instrument and Supply Storage 9.00 250B-OR-RDS-10 544 Scrub-Up Area 18.00 250B-OR-RDS-11 547 Sub-Sterile Room 18.00 250B-OR-RDS-12 550 Clean-Up Room 18.00 250B-OR-RDS-13 553 Janitor's Closet 5.00 250B-OR-RDS-14 556 Family Waiting Room 18.00 250B-OR-RDS-15 559 Scope Room 27.00 250B-OR-RDS-16 562 Dirty / Trauma 27..00 250B-OR-RDS-17 565 158.00 250B-ICU-DDS-01 568 46.00 250B-ICU-RDS-01 569 57.00 250B-ICU-RDS-02 572 13.00 250B-ICU-RDS-03 575 13.00 250B-ICU-RDS-04 578 13.00 250B-ICU-RDS-05 581 5.00 250B-ICU-RDS-06 584 11.00 250B-ICU-RDS-07 587 CENTRAL STERILIZING & SUPPLY ROOM 129.00 250B-CSSR-DDS-01 590 Receiving Room 13.00 250B-CSSR-RDS-01 591 71.00 250B-CSSR-RDS-02 594 16.00 250B-CSSR-RDS-03 597 29.00 250B-CSSR-RDS-04 600 Storage Room Office Family Counseling Room Visitor's Dressing Room Staff Lockers and Toilet

250B-OR-SFSI-01 INTENSIVE CARE UNIT Autoclave Room Isolation Room Work Area Nurse Station Patient Bay OPERATING ROOM COMPLEX Reference Sheet Number: SERVICE FACILITY SHEET INDEX Service Facility Title: ROOM TITLE PAGE Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU 515


516


Department: Room Title: OPERATING ROOM COMPLEX TRANSFER AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient scheduled for delivery is transferred from Stretcher, ward 1 ward use ward stretcher to surgical suite stretcher Stretcher, OR Complex 1 surgical suite use People Involved: FURNITURE AND 2 x Nursing Attendant FIXTURE CHECKLIST 1 x Patient Planning Relationships: ADDITIONAL EQUIPMENT & a. Located at the entrance of Operating Room Complex ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 2 grounding type,

parallel slots Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 517


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX TRANSFER AREA 250B-OR-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit patient and medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 518


519


Department: Room Title: OPERATING ROOM COMPLEX PRE-OPERATION AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient may arrive on a stretcher trolley Thermometer, non-mercurial 1 b. Patient may arrive in a wheelchair Sphygmomanometer 1 non-mercurial c. Patient is transferred from stretcher/ wheelchair Paper towel dispenser 1 to examining bed and vice-versa Towel rack 1 d. Preparation of a patient for surgery Gooseneck lamp 1 e. Evaluation of laboratory tests and medical history Sharps collector 1 f. Sterilizing the bowel with drugs Waste bin w/ black lining 1 g. Anesthesia is administered People Involved: 3 x Anesthesiologist 3 x Nurse 3 x Nursing Attendant 3 x Patient FURNITURE AND QUANTITY REMARKS FIXTURE CHECKLIST Hospital bed, adjustable 3 Footstool 3 Planning Relationships: a. Close to Anesthesiologist's Office ADDITIONAL EQUIPMENT & QUANTITY REMARKS b. With direct access to Transfer Area ENGINEERING TERMINALS Window curtain rail 2 Cubicle curtain rail 1 Outlet, 10A,2P,240V, duplex 9 grounding type,

universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Outlet, telephone 1 Outlet, DATA 1 Airconditioning unit 1 window/ split type Smoke Detector 1 Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-02A 520


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX PRE-OPERATION AREA 250B-OR-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.4 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) 70 Access limit medical staff and patient Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 521


NA 522


Department: Room Title: OPERATING ROOM COMPLEX NURSE STATION FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a stretcher trolley Hamper, soiled linen 2 b. Patient is transferred from a stretcher trolley to bed Glass board / white board 1 and vice versa Clock 1 c. Nurses and nursing attendants monitor vital signs of Waste bin w/ black lining 3 patient at regular intervals d. Use of monitoring and diagnostic equipment e. High level nursing and medical dependence People Involved: FURNITURE AND QUANTITY REMARKS Patients FIXTURE CHECKLIST 1 x Resident Physician/ Medical Specialist Counter, 2-level 1 1 x Nurse Counter, with cabinets above 2 1 x Nursing Attendant and below Sink, stainless steel; with 2 drainboard Desk, 600 x 1200mm; with 1 computer Chair; upright, stacking 1 Stool, adjustable height 2 Shelf, 450mm deep 1 Concealed floor drain 2 Lavatory 1 Water Closet 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Post-Anesthetic Care Unit Window curtain rail 2 b. Close to Nurse Supervisor's Office Outlet, 10A,2P,240V, duplex 10 grounding type,

universal Outlet, 10A, 2P, 240V, single 2 for emergency light Outlet, DATA 1 Outlet, telephone 1 Smoke detector 4 QUANTITY REMARKS REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-03A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 523


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX NURSE STATION 250B-OR-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) 100 Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 12.75 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 900 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 5000% Black out essential:desirable:UNNECESSARY Cooling load (TR) 6 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit patient and medical staff Fire risk LOW: medium: high Other risks infection from transmissible diseases ROOM DATA SHEET 524 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


525


Department: Room Title: OPERATING ROOM COMPLEX OPERATING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a stretcher trolley Double X-ray Film Illuminator 1 b. Patient is transferred from stretcher trolley to Anesthesia Unit 1 w/ scavenging sys. operating table Clock 1 c. Anesthesia is administered Operating lamp 1 d. Clinical handwashing UV Light 1 e. Use of diagnostic equipment Oxygen Unit 1 w/ tank holder f. Patient is surgically operated Nitrogen 1 g. Pre-operative care O2 tank holder 1 Double-film negatoscope 1 Footstool 2 Glass/ white board 1 Suction apparatus 1 Tracheostomy set 1 Laryngoscope 1 E-cart 1 Suction machine 1 Orthopedic instrument set 1 ACU 1 Cardial monitor w/ pulse oximeter 1 Sphygmomanometer, non-mercurial 1 Defibrillator 1 People Involved: FURNITURE AND 2 x Physicians FIXTURE CHECKLIST 1 x Circulatory Nurse Operating table 1 1 x Scrub Nurse Mayo table 1 1 x Patient Instrument table 2 1 x Anesthesiologist Double basin stand 1 Single basin stand 1 Anesthetist's stool 1 Adjustable stool 2 Anesthetist's table 1 Anesthesia unit 1 Kick bucket 1 Irrigator stand 1 Sponge rack 1 Shelving; adjustable, 500mm deep 1 Pack table 1 Floor clean-out 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Sub-Sterilizing Room ENGINEERING TERMINALS b. Adjacent to Scrub-Up Shades, light-proof 1 light-proof for special eye/ dark rm. surgery Outlet, 10A,2P,240V, duplex 11 grounding type,

universal slots Outlet, 10A, 2P, 240V, single 2 for emergency light Isolation Monitor 1 1.6m above floor Grounding terminal 4 duplex Outlet, telephone 1 Outlet, DATA 1 wall-mounted Heat Detector 1 hospital grade, locking type Door with vision panel 1 QUANTITY REMARKS QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-04A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) 526


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX OPERATING ROOM 250B-OR-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 750-1000 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 20,000-40,000 Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) 10 View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff and patient Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET 527


NA 528


Department: Room Title: OPERATING ROOM COMPLEX POST-ANESTHETIC CARE UNIT FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a stretcher trolley Oxygen outlet, mounted 1600mm 8 b. Patient is transferred from stretcher trolley to bed Suction outlet, mounted 1600mm 8 and vice versa Suction apparatus 8 c. Nurses monitor vital signs of patient at regular Laundry hamper 1 intervals Waste bin w/ yellow lining 1 infectious d. Use of monitoring and diagnostic equipment Standby BP apparatus 2 Wall Clock 1 Emergency light 1 Oxygen unit 1 Footstool 8 Sharps container 1 People Involved: FURNITURE AND 1 x Physcian FIXTURE CHECKLIST Nurses Hospital bed, adjustable 8 Nursing Attendants Cabinet, bedside 8 Chair, upright, stacking 8 Nurse counter, w/ cabinets 1 above Desk
1 Chair, swivel 3 Bed pan flusher 1 Sink, work 1 Water closet 1 Lavatory 1 Urinal 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Operating Room Complex ENGINEERING TERMINALS Cubicle curtain and rod 8 Outlet, 10A,2P,240V 21 grounding type,

parallel slots Outlet, 15A, 2P, 240V 1 grounding type, tandem slots Outlet, intercom 1 Split type, ACU, 3 ton 1 preferably ceiling mounted FCU Smoke Detector 2 Bedlight 8 Nurse Call System 1 set QUANTITY REMARKS QUANTITY REMARKS REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-05A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 529


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX POST-ANESTHETIC CARE UNIT 250B-OR-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) 100 Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.75 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff and patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 530


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX POST-ANESTHETIC CARE UNIT 250B-OR-RDS-05C TECHNICAL DESIGN DATA: LAYOUT OF ROOM AND SPACE COMPONENTS: DIRECT SERVICES DESIGN DATA

Disposal hospital solid waste type: A, B Hot Water required at sink Cold Water required at plumbing fixtures Drainage required at toilet Medical Oxygen 20 lpm/bed @ 4.0 Bar Medical Vacuum 40 lpm/bed @ 450mm Hg Medical Air 40 lpm/bed @ 4.0 Bar Steam NA Others DIRECT DEMANDS ON FLOOR AND WALL Loading NA Spillage SLIGHT: occasional: frequent Foot Traffic LIGHT: medium: heavy Wheel Traffic LIGHT: medium: heavy Impacts NA Abrasion NA Easy Maintenance ESSENTIAL:desirable:unneccesary Vibration Free ESSENTIAL:desirable:unneccesary Door Set bed, stretcher trolley chair, wheelchair access SPACE DEMANDS (Total Minimum Space Required in sq.m.) : Windows clear, solar control Space Components Minimum Space Required/Component (sq.m.) privacy control Internal Glazing NA

REGULATIONS AND NOTES: ROOM DATA SHEET 1 Hospital bed, adjustable 2 Cabinet, bedside 3 Chair, upright, stacking 4 Footstool 5 Nurse counter, w/ cabinets above KEY 6 Desk 7 Chair, swivel 8 Cubicle curtain and rod 9 Waste bin, infectious 10 Sharps container 6000 12200 6 7 5 SD SD 2100 D T 1 3 4 2 8 11 9 5 7 7 10 SCALE 1:150 M 12 13 CLEAN UTILITY ROOM: 11 Bed pan flusher 12 Sink, work 13 Concealed floor drain 1 8 1 8 1 8 1 8 1 8 1 8 1 3 4 2 8 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 NA 531


Department: Room Title: OPERATING ROOM COMPLEX DRESS, LOCKERS, T&B FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. OR staff change clothes in toilet and bathroom Waste bin w/ black lining 1 b. OR staff bathe in the bathroom Linen hamper 2 c. Storing of clothing and personal effects Dressing cubicle 1 Water heater, potable 2 People Involved: FURNITURE AND Resident Physicians FIXTURE CHECKLIST Bench 2 Locker; steel 11 Lavatory 2 Water closet 2 Shower 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Operating Room Complex ENGINEERING TERMINALS b. Close to access door of Operating Room Complex Outlet, 10A,2P,240V, duplex 6 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 2 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-06A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 532


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX DRESS, LOCKERS, T&B 250B-OR-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 85 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at toilet and bath tolerated Maximum temperature (°C) 70 Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 533


NA 534


Department: Room Title: OPERATING ROOM COMPLEX LOUNGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Resident Physician to take rest in between surgeries Airconditioning unit 1 Waste bin w/ black lining 1 People Involved: FURNITURE AND Resident Physicians and Operating Room Staff FIXTURE CHECKLIST Sofa, 2-seater 2 Table, low corner 1 Table, 6-seater dining 1 Chair, dining 6 Counter, with cabinets 1 above and below Sink, kitchen 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Operating Room Complex ENGINEERING TERMINALS Outlet, 10A, 2P 240V, double 6 grounding type, universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-07A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 535


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX LOUNGE 250B-OR-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 35 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 536


NA 537


Department: Room Title: OPERATING ROOM COMPLEX ANESTHESIOLOGIST'S OFFICE & STAFF OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Anesthesiologist reads and writes in the work station Hamper, soiled linen 1 b. Anesthesiologist records, stores and retrieves data Waste bin w/ black lining 2 from data file People Involved: FURNITURE AND 1 x Anesthesiologist FIXTURE CHECKLIST 1 x Nurse or Nursing Attendant Desk, 600 X 1500mm 1 Desk, 600 x 1200mm 1 Desk, extension, 400 x 1200mm 1 Cabinet, steel; filing 2 Shelf, open 1 Table, meeting 1 Chair, junior executive 1 Chair, swivel 1 Chair, upright, stacking 2 Chair, with armrest 4 Cabinet, storage 1 Lavatory 1 Water Closet 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Dress, Lockers, T&B ENGINEERING TERMINALS b. Adjacent to Operatiing Room Outlet, 10A,2P,240V, duplex 5 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 for emergency light Outlet, DATA 1 wall-mounted Outlet, Telephone 2 desktop Smoke detector 1 ionization type Outlet, TV 1 ceiling-mounted Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-08A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 538


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX ANESTHESIOLOGIST'S OFFICE & STAFF OFFICE 250B-OR-RDS-08B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 539


540


Department: Room Title: OPERATING ROOM COMPLEX ANESTHESIA STORAGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of materials related to anesthetics Waste bin w/ black lining 1 b. Retrieval of stored materials Fluorescent lamp, explosion-proof 1 c. Physical inventory of stored materials People Involved: FURNITURE AND 1 x Resident Physician/ Anesthesiologist FIXTURE CHECKLIST Shelving, 450mm deep 2 Sink, with gooseneck spout & 1 knee or elbow control Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Located within the Surgical Area ENGINEERING TERMINALS b. Close to Surgical Supervisor's Area Explosion-proof light fixture 1 240-W Smoke detector 1 ionization type Explosion-proof outlet 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-09A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 541


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX ANESTHESIA STORAGE 250B-OR-RDS-09B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 542


NA 543


Department: Room Title: OPERATING ROOM COMPLEX STERILE INSTRUMENT & SUPPLY STORAGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Nurse checks the availability of supplies for issuance b. Nursing Attendants prepare needed supplies and articles listed in requisition form c. Nursing Attendants pack items individually, in bulk or wrap w/ clean paper before issuance d. Nurse performs physical inventory and updates stock cards e. Nurse receives sterile supplies and instruments, puts entry into stock cards and stores supplies into shelves People Involved: FURNITURE AND 1 x Nurse FIXTURE CHECKLIST 1 x Nursing Attendant Shelf, open 1 Cabinet, instrument 2 Door with vision panel 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Located at the Surgical Area ENGINEERING TERMINALS b. Adjacent to Nurse Supervisor's Room Outlet, 10A,2P,240V, duplex 1 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-10A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 544


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX STERILE INSTRUMENT & SUPPLY STORAGE 250B-OR-RDS-10B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 545


NA 546


Department: Room Title: OPERATING ROOM COMPLEX SCRUB-UP AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Physician and nurse rinse arms and hands with water Soap dispenser 6 and soap prior to and after surgical operation Hand Dryer 2 Clock 1 Waste Bin w/ yellow lining 1 infectious People Involved: FURNITURE AND 1 x Physician FIXTURE CHECKLIST 1 x Nurse 3-Station Scrub sink, 2 with gooseneck spout & foot control, sensor type Shelves, overhead 2 Concealed floor drain 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Operating Room ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 3 grounding type,

or drier (touch free) Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke detector 1 ionization type Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-11A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 547


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX SCRUB-UP AREA 250B-OR-RDS-11B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) 250 Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 30 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.6 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at scrub sink tolerated Maximum temperature (°C) 70 Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 548


7 Concealed Floor Drain NA 549


Department: Room Title: OPERATING ROOM COMPLEX SUB-STERILE ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Preparation of packed surgical instruments Sterilizer, small instrument 1 b. Storing and retrieving of instruments from cabinets c. Minor sterilizing works d. Handwashing and other clean-up activities People Involved: FURNITURE AND 1 x Physician FIXTURE CHECKLIST 1 x Nurse or Nursing Attendant Counter, 900mm high; 2 open below Sink with drainboard 1 Concealed floor drain 1 Door with vision panel 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Operating Room ENGINEERING TERMINALS b. Adjacent to Scrub-Up Outlet, 10A,2P,240V, duplex 3 grounding type,

universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke detector 1 ionization type ACU window/ split type 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-12A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 550


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX SUB-STERILE ROOM 250B-OR-RDS-12B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.4 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: at sterilizer Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) 70 Access limit medical staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 551


NA 552


Department: Room Title: OPERATING ROOM COMPLEX CLEAN-UP ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Nurse and Nursing Attendant perform post-operation Hamper, linen 2 clean-up activities Waste bin w/ yellow lining 1 infectious 1 pharmaceutical People Involved: FURNITURE AND 1 x Nurse FIXTURE CHECKLIST 1 x Nursing Attendant Counter, with cabinets below 1 Counter, open below 1 Double compartment laundry tray 1 with drainboards Clinical sink 1 Concealed floor drain 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Operating Room ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 4 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke detector 1 ionization type Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-13A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 553


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX CLEAN-UP ROOM 250B-OR-RDS-13B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 30 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.75 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 554


555 NA


Department: Room Title: OPERATING ROOM COMPLEX JANITOR'S CLOSET FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of janitor's cleaning tools People Involved: FURNITURE AND 1 x Janitor FIXTURE CHECKLIST Slop sink 1 Open shelving 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Operating Room ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 1 grounding type,

universal slots

QUANTITY REMARKS QUANTITY REMARKS REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-OR-RDS-14A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 556


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 OPERATING ROOM COMPLEX JANITOR'S CLOSET 250B-OR-RDS-14B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) NA Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit janitorial/ utility staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 557


NA 558


Department: Room Title: OPERATING ROOM COMPLEX FAMILY WAITING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Resident Physician explains to patient's relatives complex Airconditioning Unit 1 medical terminologies and technologies Waste bin w/ black lining 1 b. Resident Physician updates and advises patient's relatives on his/her isolation status/prognosis and care preferences while acknowledging uncertainty c. Clinician listens with patience and sensitivity to relatives' emotions, including anger, grief and guilt d. Ciinician prepares families for a patient's death People Involved: FURNITURE AND 1 x Resident Physician/ Clinician FIXTURE CHECKLIST Patient's Relatives Sofa, single-seater 2 Sofa, 2-seater 2 Table, 400 x 400mm 2 Lavatory 1 Water Closet 1 Urinal 1

ADDITIONAL EQUIPMENT & a. Adjacent to Nurse Station ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 3 grounding type,

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1

Planning Relationships Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) QUANTITY REMARKS ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-OR-RDS-15A QUANTITY REMARKS Updated Reference: November 2015 559


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: November 2015 OPERATING ROOM COMPLEX FAMILY WAITING ROOM 250B-OR-RDS-15B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Resident Physician, Patient's Relatives Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary 560


561


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is assessed/scheduled to be brought to Endoscopic viewing monitor 1 Scope Room Light source and processor 1 b. Patient arrives on a stretcher trolley Diathermy recorder and printer 1 c. Patient is transferred from stretcher trolley to Monitoring equipment 1 procedure table Anesthesia unit 1 d. Anesthesia is administered Endoscope washer 1 e. Clinical handwashing Computer and printer 1 f. Use of scope/s equipment; necessary

procedure is done on patient

g. Patient is wheeled out to PACU for recover/ FURNITURE AND observation FIXTURE CHECKLIST

Trolley/cart 1

Endoscope/scope storage 1

cabinet Desk 1 Side table 1 People Involved: Chair, upright 1 1-2 x gastroenterologists/specialists Counter, w/ cabinets above and 1 1 x Nurse below 1 x Nursing Attendant Sink, stainless steel 1 1 x Patient

1 x Anesthesiologist ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Planning Relationships: Outlet, 10A,2P,240V, duplex 9 grounding type, a. Adjacent to Nurse Station

universal slots b. Near PACU Outlet, 10A,2P,240V, single 1 for emergency light c. Accessible from sub-sterile corridor Outlet, data 1 d. Outside OR Complex sterile area Outlet, telephone 1 Smoke detector 1

Hospital: SCOPE ROOM 250-Bed (Level 3) April 2016 250B-OR-RDS-16A QUANTITY Updated Reference: ROOM DATA SHEET OPERATING ROOM COMPLEX Department of Health DEVELOPMENT BUREAU HEALTH FACILITY REMARKS QUANTITY REMARKS Reference Sheet Number: QUANTITY REMARKS 562


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 750-1,000 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 20,000-40,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (psi) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (psi) NA View out essential:desirable:UNNECESSARY % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff and patient Fire risk low : medium : HIGH Other risks NA ROOM DATA SHEET April 2016 250B-OR-RDS-16B OPERATING ROOM COMPLEX SCOPE ROOM 563


KEY SCALE 1:100 M 9 Desk 10 Side table, with computer and printer 11 Chair, upright 12 Counter, 900mm high; with cabinets above and below 13 Sink, stainless steel with gooseneck faucet 14 Concealed floor drain 15 Door with vision panel 1 Stretcher 2 Endoscope viewing monitor 3 Light source and processor 4 Diathermy / recorder and printer 5 Trolley/cart 6 Monitoring equipment 7 Endoscope washer 8 Endoscope/scope storage cabinet 6000 4500 SD 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 D T CH 564


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient is assessed to be brought to Trauma Room Double X-ray film illuminator 1 b. Patient arrives on a stretcher trolley Anesthesia unit 1 w/ scavenging sys. c. Patient is transferred from stretcher trolley to Clock 1 operating table Operating lamp 1 d. Anesthesia is administered UV light 1 e. Clinical handwashing Oxygen unit 1 w/ tank holder f. Use of diagnostic equipment, if necessary Nitrogen 1 g. Patient is surgically operated O2 tank holder 1 h. Pre-operative care Footstool 1 Glass/white board 1 Suction apparatus 1 Tracheostomy set 1 Laryngoscope 1 E-cart 1 Orthopedic instrument set 1 Cardiac monitor w/ pulse oximeter 1 Sphygmomanometer, non-merc. 1 Defibrillator 1 People Involved: FURNITURE AND 2 x Surgeons FIXTURE CHECKLIST 1 x Circulation Nurse Operating table 1 1 x Scrub Nurse Mayo table 1 1 x Patient Instrument table 1

1 x Anesthesiologist Double basin stand 1 Single basin stand 1 Adjustable stool 1 Anesthesist's stool 1 Anesthesist's table 1 Kick bucket 1

Irrigator stand 1 Sponge rack 1 Shelving; adjustable, 500mm deep 1 Pack table 1 Floor clean-out 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Nurse Station Shades, light-proof 1 light-proof for b. Accessible from sub-sterile corridor special dark rm c. Outside OR Complex sterile area Outlet, 10A,2P,240V, duplex 8 grounding type,

universal slots Outlet, 10A,2P,240V, single 2 for emergency light Isolation Monitor 1 1.6m above floor Grounding terminal 4 duplex Outlet, Telephone 1 Outlet, Data 1 wall-mounted Door with vision panel 1 REMARKS QUANTITY REMARKS 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS April 2016 250B-OR-RDS-17A QUANTITY Updated Reference: ROOM DATA SHEET OPERATING ROOM COMPLEX Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: DIRTY/TRAUMA ROOM 565


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 750-1,000 Room temperature 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 20,000 - 40,000 Volume (cu.m./hr.-person) 25 Color rendering ESSENTIAL:desirable:unnecessary Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (psi) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (psi) NA View out essential:desirable:UNNECESSARY % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff and patient Fire risk low: medium : HIGH Other risks NA ROOM DATA SHEET April 2016 250B-OR-RDS-17B OPERATING ROOM COMPLEX DIRTY/TRAUMA ROOM 566


6000 KEY SCALE 1:100 M 4500 SD 12 Kick bucket 13 Irrigator stand 14 Sponge rack 15 Clock 16 Double-film negatoscope 17 Floor clean-out 18 Shelving; adjustable, 500mm deep 19 Pack table 20 Door with vision panel 1 Operating table 2 Operating lamp 3 Mayo table 4 Footstool 5 Instrument table 6 Double basin stand 7 Single basin stand 8 Anesthetist's stool 9 Adjustable stool 10 Anesthetist's table 11 Anesthesia unit 1 2 4 4 3 5 5 6 19 9 9 13 15 16 12 11 8 10 14 18 7 17 20 D T 567


568


Department: Room Title: INTENSIVE CARE UNIT NURSE STATION FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a stretcher trolley Emergency light 1 b. Patient is transferred from a stretcher trolley to bed Central monitor/ Cardiac 1 and vice versa Laryngoscope w/ blades 1 c. Nurses and nursing attendants monitor vital signs of of assorted sizes patient at regular intervals E-cart 4 d. Use of monitoring and diagnostic equipment EENT diagnostic set 1 e. High level nursing and medical dependence Mirror Set 2 Computer, w/ monitor and printer 1 Clock 1 Rack, chart 1 Hamper, medical 2 Waste bin w/ yellow lining 2 infectious Waste bin w/ black lining 2 Sharps container 1 FURNITURE AND FIXTURE CHECKLIST Counter, nurse station 1 People Involved: Counter, work; with cabinets 2 Patients above and below 1 x Resident Physician/ Medical Specialist Shelf, open 1 1 x Nurse Sink, stainless steel 1 1 x Nursing Attendant Sink, utility 1 Slop sink 1 Stool, adjustable height 2 Concealed floor drain 2 Lavatory 1 Water Closet 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Medical/Surgical Services Outlet, 10A,2P,240V, duplex 8 grounding type,

universal Outlet, 10A, 2P, 240V, single 2 for emergency light Outlet, DATA 1 Outlet, telephone 1 Paging System 1 Nurse Call Console 1 Split type, ACU 3-ton 1 Smoke detector 2 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-ICU-RDS-01A Department of Health HEALTH FACILITY Hospital: (250-Bed, Level 3) April 2016 Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 569


Hospital: Department of Health (250-Bed, Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 INTENSIVE CARE UNIT NURSE STATION 250B-ICU-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) 100 Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 12.75 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 900 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50% Black out essential:desirable:UNNECESSARY Cooling load (TR) 6 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit patient and medical staff Fire risk LOW: medium: high Other risks infection from transmissible diseases ROOM DATA SHEET 570 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


571


Department: Room Title: INTENSIVE CARE UNIT PATIENT BAY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a stretcher trolley Volume respirator 1 b. Patient is transferred from a stretcher trolley to bed Sphygmomanometer, wall-mtd 5 and vice versa Cuffs, pediatric 1 c. Nurses and nursing attendants monitor vital signs of Ambu bag, pediatric 1 patient at regular intervals Ambu bag, adult/pediatric 1 d. Use of monitoring and diagnostic equipment Suction apparatus 5 e. High level nursing and medical dependence Oxygen gauge 5 O2 set 5 O2 tank holder 5 Tracheostomy set 1 Infusion pump 1 Respirator/defribrillator 1 Emergency light 5 Patient Monitor 5 People Involved: 5 x Patients 1 x Resident Physician/ Medical Specialist FURNITURE AND 1 x Nurse FIXTURE CHECKLIST 1 x Nursing Attendant Hospital bed, adjustable
5 Bedhead console, with medical
5 Table, overbed
5 ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Window curtain rail 4 Planning Relationships: Cubicle curtain and rod 5 a. Close to Medical/Surgical Services Outlet, 10A,2P,240V, duplex 21 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke detector 5 QUANTITY REMARKS REMARKS Hospital: 250-Bed (Level 3) 250B-ICU-RDS-02A QUANTITY REMARKS Updated Reference: April 2016 QUANTITY Reference Sheet Number: ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY 572 Footstool
5 gas outlets, power outlets, and bedhead light


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 INTENSIVE CARE UNIT PATIENT BAY 250B-ICU-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) 100 Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 12.75 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 900 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 5000% Black out essential:desirable:UNNECESSARY Cooling load (TR) 6 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) 70 Access limit patien and medical staff Fire risk LOW: medium: high Other risks infection from transmissible diseases ROOM DATA SHEET Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY 573


574


Department: Room Title: INTENSIVE CARE UNIT ISOLATION ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a stretcher trolley Emergency light 1 b. Patient is assessed by physician and nurse to determine Volume respirator 1 isolation requirements Sphygmomanometer, wall-mtd 1 c. Patient is transferred from a stretcher trolley to bed Cuffs, pediatric 1 and vice versa Ambu bag, pediatric 1 d. Nurses and nursing attendants monitor vital signs of Ambu bag, adult/pediatric 1 patient at regular intervals Suction apparatus 1 e. Use of monitoring and diagnostic equipment Oxygen gauges 1 f. High level nursing and medical dependence O2 set 1 g. Nurses and nursing attendants screen potentially infectious O2 tank holder 1 visitors Tracheostomy set 1 Infusion pump 1 Respirator/defribrillator 1 ICU patient headwall 1 ICU IV track 1 Bedhead light/lamp 1 Patient Monitor 1 People Involved: 1 x Patient FURNITURE AND 1 x Resident Physician FIXTURE CHECKLIST 1 x Nurse Hospital bed, adjustable
1 1 x Nursing Attendant Bedhead console, with medical
1 Table, overbed
1 Footstool
1 Door, glass; with full windows
1 a. Close to Operating Room Complex ADDITIONAL EQUIPMENT & b. Visible from ICU Nurse Station ENGINEERING TERMINALS c. At the end of ICU patient bays Window curtain rail 1

Outlet, DATA 1 Outlet, Telephone 1

Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots Outlet, 15A,2P,240V, single 1 for emergency light ACU, split-type; 1-ton 1 Fire alarm 1

Smoke detector 1

QUANTITY ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) QUANTITY REMARKS REMARKS QUANTITY REMARKS Updated Reference: April 2016 Planning Relationships Reference Sheet Number: 250B-ICU-RDS-03A gas outlets, power outlets, and bedhead light 575


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 INTENSIVE CARE UNIT ISOLATION ROOM 250B-ICU-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) 100 Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 25 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit patient and medical staff Fire risk LOW: medium: high Other risks infection from transmissible diseases ROOM DATA SHEET 576 Negative Pressure (Pa) 10 Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


577


Department: Room Title: INTENSIVE CARE UNIT OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Resident Physician reads and writes in his work station Computer 1 w/ printer & scanner b. Resident Physician records, stores and retrieves data Airconditioning unit 1 from data file Waste bin w/ black lining 1 People Involved: FURNITURE AND 1 x Resident Physician FIXTURE CHECKLIST Desk, 600 X 1200mm
1 Desk, extension, 400 x 1200mm
1 Cabinet, steel; filing
2 Shelf, open
1 Chair, junior executive
1 Chair, upright, stacking
2 ADDITIONAL EQUIPMENT & a. Within the ICU unit ENGINEERING TERMINALS b. Adjacent to Operating Room Outlet, 10A,2P,240V, duplex 3 grounding type,

universal Outlet, 15A,2P,240V, single 1 for emergency light Outlet, DATA 1

Outlet, Telephone 1

Outlet, Aircon 1

Smoke detector 1

ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ICU-RDS-04A QUANTITY REMARKS Updated Reference: April 2016 Planning Relationships QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU QUANTITY HEALTH FACILITY REMARKS 250-Bed (Level 3) 578


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 INTENSIVE CARE UNIT OFFICE 250B-ICU-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) NA Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.32 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Resident Physician Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 579 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary


580


Department: Room Title: INTENSIVE CARE UNIT FAMILY COUNSELING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Resident Physician explains to patient's relatives complex Airconditioning Unit 1 medical terminologies and technologies Waste bin w/ black lining 1 b. Resident Physician updates and advises patient's relatives on his/her isolation status/prognosis and care preferences while acknowledging uncertainty c. Clinician listens with patience and sensitivity to relatives' emotions, including anger, grief and guilt d. Ciinician prepares families for a patient's death People Involved: FURNITURE AND 1 x Resident Physician/ Clinician FIXTURE CHECKLIST Patient's Relatives Desk, 600 x 1200mm 1 Desk, extension; 400 x 1200mm 1 Cabinet, steel; filing 2 Chair, swivel 1 Chair, visitor 2 Sofa, 2-seater 1

ADDITIONAL EQUIPMENT & a. Adjacent to Nurse Station ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 2 grounding type,

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1

ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ICU-RDS-05A QUANTITY REMARKS Updated Reference: April 2016 Planning Relationships Department of Health DEVELOPMENT BUREAU QUANTITY QUANTITY HEALTH FACILITY REMARKS REMARKS 250-Bed (Level 3) 581


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 INTENSIVE CARE UNIT FAMILY COUNSELING ROOM 250B-ICU-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Resident Physician, Patient's Relatives Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary 582


583


Department: Room Title: INTENSIVE CARE UNIT VISITOR'S DRESSING ROOM SIGN REQUIREMENTS:

provides facilities needed EQUIPMENT AND llowing activities: ACCESSORY CHECKLIST a. Visitors/Patient's Family and relatives wear a gown Gown and mask Gloves b. Visitors/Patient's Family and relatives use alcohol N-95 mask hand sanitizer c. Storing of clothings and personal effects People Involved: FURNITURE AND Visitors FIXTURE CHECKLIST Patient's family/relatives Closet, 600mm deep 1 with clothes rod and hooks Hamper, medical 1

ADDITIONAL EQUIPMENT & a. Should have direct access from the corridor ENGINEERING TERMINALS Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1

Planning Relationships Department of Health DEVELOPMENT BUREAU QUANTITY QUANTITY HEALTH FACILITY REMARKS REMARKS 250-Bed (Level 3) ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ICU-RDS-06A QUANTITY REMARKS Updated Reference: April 2016 584


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 INTENSIVE CARE UNIT VISITOR'S DRESSING ROOM 250B-ICU-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit ICU staff, patient's visitors/relatives Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 585 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


586


Department: Room Title: INTENSIVE CARE UNIT STAFF LOCKERS & TOILET FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Resident Physician and nurses change clothes in staff Waste Bin w/ black lining 1 lockers room Hamper 1 b. Storing of clothings and personal effects Water Heater 1 c. Wearing of gowns, masks and gloves d. Resident Physician and nurses wash hands or use alcohol hand santizer e. Resident Physician and nurses use toilet and bath People Involved: FURNITURE AND Resident Physicians FIXTURE CHECKLIST Nurses Locker; steel 4 Nursing Attendants Shower set 1 Lavatory 1 Water Closet 1 Urinal 1 Concealed Floor Drain 1

ADDITIONAL EQUIPMENT & a. Should have direct access from the corridor ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 1 grounding type,

universal slots

Outlet, 15A,2P,240V, single 1 for emergency light Smoke detector 1

ROOM DATA SHEET Hospital: Reference Sheet Number: 250B-ICU-RDS-07A QUANTITY REMARKS Updated Reference: April 2016 Planning Relationships Department of Health DEVELOPMENT BUREAU QUANTITY QUANTITY HEALTH FACILITY REMARKS REMARKS 250-Bed (Level 3) 587


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 INTENSIVE CARE UNIT STAFF LOCKERS & TOILET 250B-ICU-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY 588


589


590


Department: Room Title: CENTRAL STERILIZING & SUPPLY ROOM RECEIVING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Receiving of instruments for washing and sterilizing from the different departments of the hospital People Involved: FURNITURE AND 1 x Central Supply Service Worker FIXTURE CHECKLIST Counter, work; with cabinets 2 above and below Sink, 350-400mm deep; with 1 drainboard Stool, adjustable height 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Operating Room Complex ENGINEERING TERMINALS b. Adjacent to Delivery Room Suite Outlet, 10A, 2P, 240V, duplex 3 grounding type, c. Accessible from the different departments of

universal the hospital Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke Detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-CSSR-RDS-01A Department of Health HEALTH FACILITY Hospital: (250-Bed, Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 591


Hospital: Department of Health (250-Bed, Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 CENTRAL STERILIZING & SUPPLY ROOM RECEIVING ROOM 250B-CSSR-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-1000 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit CSSR staff Fire risk low: medium:HIGH Other risks exposure to hazardous chemicals ROOM DATA SHEET 592 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


NA 593


Department: Room Title: CENTRAL STERILIZING & SUPPLY ROOM WORK AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Disassembling and arranging of instruments Multi rubber tube washer Dressing Sterilizer Instrument Sterilizer Supply cart Step lader Heavy duty autoclave Sterilizer, hot air 1 Water still 1 Rack, gloves drying 1 Whiteboard 1 Waste bin w/ black lining 2 Waste bin w/ yellow lining 1 chemical Sharps container 1 People Involved: FURNITURE AND 4 x Central Supply Service Workers FIXTURE CHECKLIST Counter, work; with cabinets below 1 Counter, work; with cabinets 3 above and below Sink, double compartment; 2 with drainboard Table, work; with overhead shelf 1 Desk, 600 x 1200mm 1 Chair, upright; stacking 6 Concealed floor drain 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Operating Room Complex ENGINEERING TERMINALS b. Adjacent to Delivery Room Suite Outlet, 10A,2P,240V, duplex 9 grounding type, c. Accessible from the different departments of

universal the hospital Outlet, 10A, 2P, 240V, single 1 for emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke Detector 3 QUANTITY QUANTITY REMARKS REMARKS REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-CSSR-RDS-02A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 594 b. Washing of instruments in a washer - sterilizer c. Sterilizing of instruments Preparation of instruments for future use d.


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 CENTRAL STERILIZING & SUPPLY ROOM WORK AREA 250B-CSSR-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-1000 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) 100 Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit CSSR staff Fire risk low: medium:HIGH Other risks exposure to hazardous chemicals ROOM DATA SHEET 595 Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


NA 596


Department: Room Title: CENTRAL STERILIZING & SUPPLY ROOM AUTOCLAVE ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Sterilization of instruments/ glasswares Sterilizer, instrument 1 Autoclave, heavy-duty 1 People Involved: FURNITURE AND 1 x Central Supply Service Worker FIXTURE CHECKLIST Floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to CSSR ENGINEERING TERMINALS b. Adjacent to the work area of the CSSR Outlet, 10A, 2P, 240V, duplex 4 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke Detector 1 Overhead room exhaust 1 Automatic Sprinkler System
REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-CSSR-RDS-03A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 597


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 CENTRAL STERILIZING & SUPPLY ROOM AUTOCLAVE ROOM 250B-CSSR-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration 93%-99%@ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: Sterilizer Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit CSSR staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 598 Negative Pressure (Pa) NA Daylight ESSENTIAL:desirable:unnecessary Positive Pressure (Pa) NA View out ESSENTIAL:desirable:unnecessary


599 NA


Department: Room Title: CENTRAL STERILIZING & SUPPLY ROOM STORAGE ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of sterilized/ washed instruments Ladder
1 b. Issuance of instruments as requested by other hospital services c. Dispensing of supplies in clinical areas d. Inventory of instruments and supplies People Involved: FURNITURE AND 1 x Central Supply Service Worker FIXTURE CHECKLIST Counter, with transaction window 1 Table, work 1 Cabinet, sterile supply 12 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Operating Room Complex ENGINEERING TERMINALS b. Adjacent to Delivery Room Complex Outlet, 10A,2P,240V, duplex 4 grounding type, c. Accessible from the different departments of

universal the hospital Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke Detector 2 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-CSSR-RDS-04A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 600


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 CENTRAL STERILIZING & SUPPLY ROOM STORAGE ROOM 250B-CSSR-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit CSSR staff Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET 601 Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY


NA 602


VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.8 DELIVERY ROOM & NICU SERVICE FACILITIES

First Edition DEPARTMENT OF HEALTH Manila 2017 603


REFERENCE SHEET NUMBER 250B-DR-RDS-01 250B-DR-RDS-02 250B-DR-RDS-03 250B-DR-RDS-04 250B-DR-RDS-05 250B-DR-RDS-06 250B-DR-RDS-07 250B-DR-RDS-08 250B-DR-RDS-09 250B-DR-RDS-10 250B-DR-RDS-11 250B-DR-RDS-12 250B-DR-RDS-13 250B-DR-RDS-14 250B-NICU-RDS-01 250B-NICU-RDS-02 250B-NICU-RDS-03 250B-NICU-RDS-04 250B-NICU-RDS-05 PAGE Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU

250B-DR-SFSI-01 Reference Sheet Number:

Hospital: SERVICE FACILITY SHEET INDEX 250-Bed (Level 3) Updated Reference: Service Facility Title: April 2016 DELIVERY ROOM AND NICU SPACE DEMAND TOTAL AREA ROOM TITLE (SQ. MTS.) (SQ. MTS.) DELIVERY ROOM COMPLEX 350.00 Nurse Station 27.00 Labor Room 46.00 Delivery Room 36.00 Caesarian Delivery Room 36.00 Recovery Room 59.00 High-Risk Pregnancy Unit 42.00 Scrub-Up Area 9.00 Sub-Sterilizing Room 9.00 Sterile Instrument and Supply Storage 12.00 Dressing, Lockers, and T&B 36.00 Lounge 18.00 Clean-Up Room 9.00 Janitor's Closet 2.00 Wheeled Stretcher's Area 9.00 NEONATAL INTENSIVE CARE UNIT (NICU) 201.00 Nurse Station 19.00 Level III Sick Room 44.00 Breastfeeding Room 14.00 Lounge 14.00 Dressing, Lockers, and T&B 28.00 Isolation Room 20.00 Level II Step-Down 31.00 Level I Growers 31.00

250B-DR-DDS-01 606 605 607 610 613 616 619 622 625 628 631 634 637 640 643 649 250B-NICU-DDS-01 650 653 656 659 662 646 250B-NICU-RDS-06 665 250B-NICU-RDS-07 668 250B-NICU-RDS-08 671


DN 6000 15000 6000 3000 CS DELIVERY ROOM 6000 2000 9700 3300 3500 2100 4000 3000 2800 3000 3000 3000 6000 6000 7300 6100 9800 2100 3000 51000 TO NICU NICU RECEIVING AREA DR RELEASING AREA SCRUB UP SUB- STERILIZATION ROOM DELIVERY ROOM DELIVERY ROOM RECOVERY ROOM ESSENTIAL INTRA-PARTUM NEWBORN CARE NURSE STATION SUPPLY CLEAN UP NURSES' LOUNGE AFFILIATES' ROOM DOCTORS' LOUNGE M DR DRESS STERILE INSTRUMENTS/ STERILE SUPPLY ROOM HIGH RISK PREGNANCY UNIT SEPTIC LABOR WHEELED STRETCHER AREA F DR DRESS ISOLATION ROOM SEPTIC DELIVERY LABOR ROOM CS DELIVERY ROOM SCALE 1:300 M 2600 3000 6000 3000 1700 51000 JANITOR'S CLOSET 606


Department: Room Title: DELIVERY ROOM COMPLEX NURSE STATION FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Nurse administers nursing care clinical procedures to Hot plate, single element 1 baby Instrument sterilizer 1 b. Nurse examines baby and records data gathered Refrigerator, 10 cu. ft. 1 c. Nurse performs necessary monitoring activities to babies Glass board / white board 1 d. Nurse takes inventories of nursery supplies Clock 1 Waste bin w/ black lining general waste 2 Waste bin w/ yellow lining pharmaceutical 1 Sharps container 1 People Involved: FURNITURE AND 1 x Nurse FIXTURE CHECKLIST 2 x Nursing Attendants Counter, nurse 1 Counter, work; with cabinets 2 above and below Table, computer 1 Sink, stainless steel 1 Chair; upright, stacking 1 Stool, adjustable 1 Concealed floor drain 2 Shelf, 450mm deep 1 Lavatory 1 Water Closet 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Breastfeeding Room ENGINEERING TERMINALS grounding type, 6 Outlet, 10A,2P,240V, duplex b. Adjacent to Sub-Sterilizing Room universal slots c. Close to NICU for emergency light 1 Outlet, 10A, 2P, 240V, single Outlet, DATA 1 1 Outlet, Telephone Smoke detector 2 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 607


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX NURSE STATION 250B-DR-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.35 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory and sink tolerated Maximum temperature (°C) 70 Access limit nursing staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 608


609 NA


Department: Room Title: DELIVERY ROOM COMPLEX LABOR ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on foot Clock 1 b. Patient may arrive in a wheelchair or on a stretcher trolley Waste bin w/ yellow lining 1 infectious c. Transfer patient from wheelchair or stretcher trolley 1 chemical to obstetrical bed 1 pharmaceutical d. Clinical handwashing Waste bin w/ black lining 1 e. Patient undergoes labor prior to delivery Sharps container 1 f. Use of toilet facilities People Involved: FURNITURE AND 2 x Resident Physicians FIXTURE CHECKLIST 1 x Nurse Hospital bed, adjustable 6 1 x Nursing Attendant Footstool 6 6 x Maternity Patients Chair, upright, stacking 7 Side cabinet 6 Desk, 600 x 1000mm 1 Counter, with cabinets above 1 and below Water closet 1 Lavatory 1 Floor Drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Delivery Room ENGINEERING TERMINALS grounding type, 9 Outlet, 10A,2P,240V, duplex b. Close to Caesarian Delivery Room universal slots c. Close to Scrub-up and Sub-Sterilizing Room for emergency light 1 Outlet, 10A, 2P, 240V, single Outlet, DATA 1 1 Outlet, Telephone Smoke detector 1 6 Cubicle Curtain and Rod 6 Calling Station Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-02A Department of Health HEALTH FACILITY 610


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX LABOR ROOM 250B-DR-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.7 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff and patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 611


NA 612


Department: Room Title: DELIVERY ROOM COMPLEX DELIVERY ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a stretcher trolley Anesthesia machine 1 b. Patient is transferred from stretcher trolley to Bag valve mask unit 1 delivery table Clinical infant weighing scale 1 c. Anesthesia is administered Thermometer, non-mercurial 1 d. Clinical handwashing D.R. instrument set 1 e. Normal delivery of a child by the patient Laryngoscope 1 O2 unit w/ tank holder 1 Suction apparatus 1 Stretcher 1 Obstetrical lamp 1 Emergency light, portable 1 Heated bassinet/warmer 1 People Involved: Aspirator 1 2 x Resident Physicians Clock 1 1 x Nurse BP apparatus 1 1 x Nursing Attendant Stethoscope 1 1 x Maternity Patient FURNITURE AND FIXTURE CHECKLIST Delivery table 1 Mayo table 1 Instrument table 1 Single basin stand 2 Anesthetist's stool 1 Adjustable stool 1 Anesthetist's table 1 Planning Relationships: Anesthesia unit 1 a. Adjacent to Sub-Sterilizing Room Kick bucket 1 b. Adjacent to Scrub-Up Floor clean-out 1 Shelving; adjustable, 500mm deep 1 ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS 2 Window curtain rail grounding type, 5 Outlet, 10A,2P,240V, duplex

universal slots Outlet, 15A, 2P, 240V, single 1 grounding type, tandem Isolation Monitor 1.6m above floor 1 Ground terminal duplex 2 Calling Station 1 Fixed emergency light 2 Heat Detector 1 Door w/ vision panel 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-03A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) QUANTITY REMARKS QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY 613


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX DELIVERY ROOM 250B-DR-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-750 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000-20,000 Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) 10 View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 3 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff and patient Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET 614


615


Department: Room Title: DELIVERY ROOM COMPLEX CAESARIAN DELIVERY ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a stretcher trolley Aspirator 1 b. Patient is transferred from stretcher trolley to UV Light 1 operating table Oxygen Unit 1 c. Anesthesia is administered Sponge rack 1 d. Clinical handwashing Clock 1 e. Use of diagnostic equipment Double-film negatoscope 1 f. Patient is surgically operated People Involved: FURNITURE AND 2 x Resident Physicians FIXTURE CHECKLIST 1 x Nurse Operating table 1 1 x Nursing Attendant Operating lamp 1 1 x Patient Mayo table 1 1 x Utility Worker Footstool 2 Instrument table 2 Double basin stand 1 Single basin stand 1 Anesthetist's stool 1 Adjustable stool 2 Anesthetist's table 1 Anesthesia unit 1 Kick bucket 1 Irrigator stand 1 Floor clean-out 1 Shelving; adjustable, 500mm deep
1 Pack table 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Sub-Sterilizing Room ENGINEERING TERMINALS b. Adjacent to Scrub-Up Outlet, 10A,2P,240V, duplex 9 grounding type,

universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Outlet, telephone 1 Outlet, DATA 1 Heat Detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-04A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: QUANTITY REMARKS QUANTITY REMARKS REMARKS QUANTITY 616


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: CAESARIAN DELIVERY ROOM TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 750-1000 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 20,000-40,000 Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) 10 View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff and patient Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET April 2016 DELIVERY ROOM COMPLEX 250B-DR-RDS-04B 617


NA 618


Department: Room Title: DELIVERY ROOM COMPLEX RECOVERY ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient arrives on a stretcher trolley Oxygen outlet, mounted 1600mm 8 b. Patient is transferred from stretcher trolley to bed Suction outlet, mounted 1600mm 8 and vice versa Suction apparatus 8 c. Nurses monitor vital signs of patient at regular Standby BP apparatus 1 intervals Wall Clock 1 d. Use of monitoring and diagnostic equipment Emergency light 1 Oxygen unit 1 Waste bin w/ yellow lining 1 infectious 1 chemical 1 pharmaceutical Sharps container 1 People Involved: FURNITURE AND 1 x Physcian FIXTURE CHECKLIST Nurses Stretcher bed, adjustable 8 8 x Patients Cabinet, bedside 8 Chair, upright, stacking 8 Footstool 8 Work counter, 900mm high, 1 with cabinets below Sink, with gooseneck spout 1 and knee control Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Delivery Room ENGINEERING TERMINALS b. Adjacent to Sub-Sterilizing room Window curtain rail 1 c. Close to Caesarian Delivery room Cubicle curtain and rod 7 Outlet, 10A,2P,240V, duplex 20 grounding type,

universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Outlet, telephone 1 Outlet, DATA 1 Split type, ACU, 3 ton 1 preferably ceiling mounted FCU Smoke Detector 2 Bedlight 8 Nurse Call System 8 QUANTITY REMARKS QUANTITY REMARKS REMARKS QUANTITY DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-05A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: Updated Reference: 619


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX RECOVERY ROOM 250B-DR-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) 100 Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:DESIRABLE:unnecessary Cooling load (TR) 2 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit medical staff and patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 620


621 NA


Department: Room Title: DELIVERY ROOM COMPLEX HIGH-RISK PREGNANCY UNIT FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Nurse performs nursing care Cardiac monitor w/pulse oxymeter 5 b. Monitoring of vital signs Cardiotomography machine 5 c. Use of monitoring and daignostic equipment O2 unit w/ gauge & humidifier 5 O2 tank holder 5 Suction apparatus 5 Waste bin w/ yellow lining 1 infectious 1 chemical 1 pharmaceutical Sharps container People Involved: FURNITURE AND 1 x Physician FIXTURE CHECKLIST Nurses Hospital bed, adjustable 5 Midwives Cabinet, bedside 5 5 x Patients Chair, upright, stacking 6 Footstool 5 Desk 1 Counter, with cabinets above 1 and below Water closet w/ spray hose 1 Lavatory 1 Floor Drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Delivery Room Window curtain rail 2 b. Adjacent to Sub-Sterilizing Room Cubicle curtain rail and rod 4 c. Close to Caesarian Delivery Room Outlet, 10A,2P,240V, duplex 14 grounding type,

universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Nurse Call System 1 Smoke detector 1 Outlet, DATA 1 Outlet, Telephone 1 Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU QUANTITY REMARKS ROOM DATA SHEET 250B-DR-RDS-06A Department of Health HEALTH FACILITY QUANTITY REMARKS 622


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: HIGH-RISK PREGNANCY UNIT TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 35 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.5 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:UNNECESSARY Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: at scrub sink tolerated Maximum temperature (°C) 70 Access limit patient and medical staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET April 2016 DELIVERY ROOM COMPLEX 250B-DR-RDS-06B 623


NA 624


Department: Room Title: DELIVERY ROOM COMPLEX SCRUB-UP AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Physician and nurse rinse arms and hands with water Soap dispenser 3 and soap prior to and after surgical operation Hand dryer 1 Waste bin w/ yellow lining 1 infectious Clock 1 People Involved: FURNITURE AND 1 x Physician FIXTURE CHECKLIST 1 x Nurse or Nursing Attendant 3-Station Scrub sink, w/ gooseneck 1 spout & foot control, sensor type Shelves, overhead 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Caesarian Delivery Room ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 1 grounding type,

universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light 1 for hand dryer Smoke detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-07A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 625


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX SCRUB-UP AREA 250B-DR-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.35 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at scrub sink tolerated Maximum temperature (°C) 70 Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 626


627 NA


Department: Room Title: DELIVERY ROOM COMPLEX SUB-STERILIZING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Preparation of packed surgical instruments Sterilizer, instrument 1 b. Storing and retrieving of instruments from cabinets c. Minor sterilizing works d. Handwashing and other clean-up activities People Involved: FURNITURE AND 1 x Physician FIXTURE CHECKLIST 1 x Nurse or Nursing Attendant Counter, work 1 Sink, with drainboard 1 Counter, 900mm high, open below 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Operating Room Window curtain rail 1 b. Adjacent to Scrub-up Area Outlet, 10A,2P,240V, duplex 3 grounding type,

universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-08A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 628


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX SUB-STERILIZING ROOM 250B-DR-RDS-08B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.35 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 629


NA 630


Department: Room Title: DELIVERY ROOM COMPLEX STERILE INSTRUMENT & SUPPLY STORAGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Nurse checks the availability of supplies for issuance Waste bin w/ black or colorless 1 b. Nursing Attendants prepare needed supplies and articles lining listed in requisition form c. Nursing Attendants pack items individually, in bulk or wrap w/ clean paper before issuance d. Nurse performs physical inventory and update stock cards e. Nurse receives sterile supplies and instruments, puts entry into stock cards and stores supplies into shelves People Involved: FURNITURE AND 1 x Nurse FIXTURE CHECKLIST 1 x Nursing Attendant Counter, with 450mm deep shelving 1 Sink with drainboard 1 Cabinet, instrument 2 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Located at the Delivery Area ENGINEERING TERMINALS b. Adjacent to Nurse Supervisor's Area grounding type, 4 Outlet, 10A,2P,240V, duplex

parallel slots for emergency light 1 Outlet, 10A, 2P, 240V, single Smoke detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-09A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS above 631


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX STERILE INSTRUMENT & SUPPLY STORAGE 250B-DR-RDS-09B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:DESIRABLE:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 632


NA 633


Department: Room Title: DELIVERY ROOM COMPLEX DRESS, LOCKERS, T&B FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. DR staff change clothes in toilet and bathroom Waste bin w/ black lining 2 b. DR staff bathe in the bathroom Hamper, linen 2 c. Storing of clothing and personal effects People Involved: FURNITURE AND Resident Physicians FIXTURE CHECKLIST Locker, steel 12 Bench 2 Lavatory 2 Water closet 2 Shower 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Delivery Room Complex ENGINEERING TERMINALS b. Close to access door of Delivery Room Complex Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 2 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-10A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 634


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX DRESS, LOCKERS, T&B 250B-DR-RDS-10B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 85 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at toilet and bath tolerated Maximum temperature (°C) 70 Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 635


NA 636


Department: Room Title: DELIVERY ROOM COMPLEX LOUNGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Resident Physician to take rest in between surgeries Airconditioning unit 1 Waste bin w/ black lining 1 People Involved: FURNITURE AND Resident Physicians and Delivery Room Staff FIXTURE CHECKLIST Sofa, 1-seater with arms 1 Sofa, 2-seater with arms 1 Table, low corner 1 Table, 6-seater dining 1 Chair, dining 6 Counter, with cabinets below 1 Sink, kitchen 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Operating Room Suite ENGINEERING TERMINALS b. Close to access door of Operating Room Suite grounding type, 5 Outlet, 10A,2P,240V, duplex

universal slots for emergency light 1 Outlet, 10A, 2P, 240V, single Outlet, DATA 1 1 Outlet, Telephone Smoke detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-11A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 637


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX LOUNGE 250B-DR-RDS-11B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 35 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 638


NA 639


Department: Room Title: DELIVERY ROOM COMPLEX CLEAN-UP ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Nurse and Nursing Attendant perform post-delivery/ Hamper, linen 1 operation clean-up activities Waste bin, general 1 People Involved: FURNITURE AND 1 x Nurse FIXTURE CHECKLIST 1 x Nursing Attendant Counter, work; w/ cabinets above 1 and below Sink, double compartment; laundry; 1 350-400mm deep Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Delivery Room ENGINEERING TERMINALS grounding type, 1 Outlet, 10A,2P,240V, duplex

universal for emergency light 1 Outlet, 10A, 2P, 240V, single Smoke detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-12A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 640


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX CLEAN-UP ROOM 250B-DR-RDS-12B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.4 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 641


NA 642


Department: Room Title: DELIVERY ROOM COMPLEX JANITOR'S CLOSET FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of janitor's cleaning tools People Involved: FURNITURE AND 1 x Janitor FIXTURE CHECKLIST Slop sink w/ faucet 1 Shelf 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Operating Room ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 1 grounding type,

universal slots Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-13A Department of Health HEALTH FACILITY QUANTITY REMARKS Hospital: 250-Bed (Level 3) QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY 643


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX JANITOR'S CLOSET 250B-DR-RDS-13B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) NA Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff and patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 644


NA 645


Department: Room Title: DELIVERY ROOM COMPLEX WHEELED STRETCHER'S AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Patient scheduled for delivery is transferred from Delivery Room Complex stretcher 1 delivery suite use ward stretcher to delivery suite stretcher Ward stretcher 1 ward use People Involved: FURNITURE AND 2 x Nursing Attendants FIXTURE CHECKLIST 1 x Patient Planning Relationships: ADDITIONAL EQUIPMENT & a. Located at the entrance of Delivery Room Suite ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 1 grounding type,

universal Outlet, 10A, 2P, 240V, single 1 for emergency light Smoke detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-DR-RDS-14A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 646


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 DELIVERY ROOM COMPLEX WHEELED STRETCHER'S AREA 250B-DR-RDS-14B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) NA Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal Impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit patient and medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 647


NA 648


DN 2300 3100 7300 25200 13200 1500 5700 6000 5100 5100 NICU RECEIVING AREA ISOLATION ROOM LEVEL 1 GROWERS ON- CALL ROOM LEVEL III SICK LEVEL II INTERMEDIATE/ STEP-DOWN NURSE STATION STAFF LOUNGE DRESS BREAST FEEDING ROOM 6000 3000 3000 SUPPLY F DRESS/ T&B M DRESS/ T&B 2300 SCRUB SCALE 1:300 M 12000 649


Department: Room Title: NEONATAL INTENSIVE CARE UNIT NURSE STATION FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Nurse administers nursing care clinical procedures to Hot plate, single element 1 baby Instrument sterilizer 1 b. Nurse examines baby and records data gathered Glass board / white board 1 c. Nurse performs necessary monitoring activities to babies Clock 1 d. Nurse takes inventories of nursery supplies Waste bin w/ yellow lining infectious 1 pharmaceutical 1 Waste bin w/ black lining general waste 1 Sharps container 1 People Involved: FURNITURE AND 1 x Nurse FIXTURE CHECKLIST 2 x Nursing Attendants Counter 1 Chair; upright, stacking 1 Counter, with cabinets 1 above and below Sink 1 Concealed floor drain 1 Shelf 1 Lavatory 1 Water Closet 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Breastfeeding Room ENGINEERING TERMINALS grounding type, 4 Outlet, 10A,2P,240V, duplex b. Adjacent to Sub-Sterilizing Room universal slots c. Close to NICU for emergency light 1 Outlet, 10A, 2P, 240V, single Outlet, DATA 1 1 Outlet, Telephone Smoke detector 2 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-NICU-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 650


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: NEONATAL INTENSIVE CARE UNIT TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.35 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at lavatory and sink tolerated Maximum temperature (°C) 70 Access limit nursing staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 NURSE STATION 250B-NICU-RDS-01B 651


NA 652


Department: Room Title: NEONATAL INTENSIVE CARE UNIT LEVEL III SICK ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. A newborn premature baby is brought in from the Hot plate, single element 1 Delivery Room Instrument sterilizer 1 b. Nurse administers nursing care and clinical procedures Incubator 5 to baby Linen hamper 1 c. Nurse measures baby's height and head circumference Waste bin w/ yellow lining 1 infectious d. Nurse weighs baby Sharps container 1 e. Nurse records data gathered f. Nurse prepares baby, i.e. cleans and dresses baby g. Nurse places baby in the bassinet People Involved: FURNITURE AND 5 x Newborn infants FIXTURE CHECKLIST 1 x Nurse Counter, 900mm high with 1 1 x Nursing Attendant cabinets above and below Desk, 600 x 1000mm 1 Chair, stacking, upright 1 Stool, adjustable 1 Sink, with gooseneck spout and 1 foot or elbow control Cabinet, bedside 5 Partition, 1700mm high, clear 4 glass upper panel Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Nurse Station and Work Room ENGINEERING TERMINALS b. Close to Delivery Room and Caesarian Delivery Room Outlet, 10A,2P,240V, duplex 9 grounding type, c. Close to Labor Room

universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-NICU-RDS-02A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 653


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: NEONATAL INTENSIVE CARE UNIT TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.5 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: instrument sterilizer Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: at sink and lavatory tolerated Maximum temperature (°C) 70 Access limit newborn baby & nursing staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 250B-NICU-RDS-02B LEVEL III SICK ROOM 654


NA 655


Department: Room Title: NEONATAL INTENSIVE CARE UNIT BREASTFEEDING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Nurse brings in newborn infant to the waiting mother for Hand dryer 1 breastfeeding Waste bin w/ black lining 1 b. Nurse assists mothers in breastfeeding their babies People Involved: FURNITURE AND 1 x Nurse FIXTURE CHECKLIST Newborn Infant Sofa, 2-seater with arms 2 Mother Table, low corner 2 Counter, with cabinets below 1 Sink, kitchen 1 Lavatory with gooseneck spout 1 and knee control Floor drain, concealed 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Nurse Station and NICU ENGINEERING TERMINALS grounding type, 6 Outlet, 10A,2P,240V, duplex

universal slots for emergency light 1 Outlet, 10A, 2P, 240V, single Smoke detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-NICU-RDS-03A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 656


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: NEONATAL INTENSIVE CARE UNIT TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 25 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.5 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit mother, newborn infant & nurse Fire risk low:MEDIUM: high Other risks NA ROOM DATA SHEET April 2016 BREASTFEEDING ROOM 250B-NICU-RDS-03B 657


NA 658


Department: Room Title: NEONATAL INTENSIVE CARE UNIT LOUNGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Resident Physician to take rest in between surgeries Airconditioning unit 1 Waste bin w/ black lining 1 People Involved: FURNITURE AND Resident Physicians and Delivery Room Staff FIXTURE CHECKLIST Sofa, 1-seater with arms 1 Table, low corner 1 Table, 4-seater dining 1 Chair, dining 4 Counter, with cabinets above 1 and below Sink, kitchen 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Operating Room Suite ENGINEERING TERMINALS b. Close to access door of Operating Room Suite Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots Outlet, 10A, 2P, 240V, single 1 for emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-NICU-RDS-04A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 659


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: NEONATAL INTENSIVE CARE UNIT TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 35 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 LOUNGE 250B-NICU-RDS-04B 660


KEY SCALE 1:100 M 2300 5700 1 1 Sofa, 2-seater with arms 2 Table, low corner 3 Table, 4-seater dining 4 Chair, dining 5 Counter, with cabinets above and below 6 Sink, kitchen 7 Waste bin 8 Floor drain, concealed SD T D 2 3 4 4 4 4 5 6 7 8 CH 661


Department: Room Title: NEONATAL INTENSIVE CARE UNIT DRESS, LOCKERS, T&B FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. NICU staff change clothes in toilet and bathroom Waste bin w/ black lining 2 b. NICU staff bathe in the bathroom Hamper, linen 2 c. Storing of clothing and personal effects People Involved: FURNITURE AND Resident Physicians FIXTURE CHECKLIST Locker, steel 18 Shelf 1 Lavatory 2 Water closet 2 Shower 2 Slop sink, w/ faucet 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to NICU ENGINEERING TERMINALS b. Close to access door of NICU Outlet, 10A,2P,240V, duplex 2 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 2 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET 250B-NICU-RDS-05A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) April 2016 Reference Sheet Number: 662


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: NEONATAL INTENSIVE CARE UNIT TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 85 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at toilet and bath tolerated Maximum temperature (°C) 70 Access limit medical staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 DRESS, LOCKERS, T&B 250B-NICU-RDS-05B 663


NA 664


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. An infant is brought to Isolation Room to separate Hot plate, single element 1 him/her from other infants (suspected and Instrument sterilizer 1 confirmed infectious diseases) Incubator 1 b. Doctor/Nurse observes proper isolation Patient monitor 1 precautions and protocols: hand washing, gowning, Linen hamper 1 PPE, storage of clean supplies, among others Waste bin 1 w/ yellow lining c. Nurse administers nursing care and clinical Sharps container 1

procedures to infant

c. Nurse administers nursing care and clinical

procedures to infant FURNITURE AND d. Nurse measures infant's height and head FIXTURE CHECKLIST circumference Cabinet, for storage of gowns, 1 e. Nurse weighs infant PPEs, clean supplies, etc. f. Nurse records data gathered Counter, 900mm high with 1 g. Nurse prepared baby, i.e. cleans and dresses cabinets above and below baby, feeds baby, etc. Lavatory 1 h. Nurse places baby in incubator Sink, with gooseneck faucet 1 i. Nurse monitors infant's vital signs Cabinet, bedside 1

People Involved: 1 x Infant ADDITIONAL EQUIPMENT & 1 x Nurse ENGINEERING TERMINALS 1 x Nursing Attendant Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Outlet, data 1 Planning Relationships: Outlet, telephone 1 a. Near Nurse Station Smoke detector 1

Updated Reference: ROOM DATA SHEET NEONATAL INTENSIVE CARE UNIT Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: ISOLATION ROOM REMARKS QUANTITY REMARKS QUANTITY 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS April 2016 250B-NICU-RDS-06A 665


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-700 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 30 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (psi) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (psi) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.5 SOUND SAFETY Acceptable sound level (db) 30 Accessible hot surface: instrument sterilizer Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit infant and nursing staff Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET April 2016 250B-NICU-RDS-06B NEONATAL INTENSIVE CARE UNIT ISOLATION ROOM 666


KEY SCALE 1:100 M 3200 1300 4700 SD SD 1 3 4 2 6 5 7 8 13 14 9 12 11 10 16 17 7 15 1 Ante Room 2 Lavatory, with soap and paper towel dispenser 3 Cabinet, for clean linen/PPE 4 Hamper, soiled linen 5 Waste bin 6 Concealed floor drain 7 Window, view 8 Isolation Room 9 Counter, 900mm high with cabinets above and below 10 Sink, with gooseneck faucet 11 Hot plate, single element 12 Instrument sterilizer 13 Isolette 14 Cabinet, bedside 15 Monitor, patient 16 Sharps container 17 Waste bin, infectious D T 667


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. An infant is transferred from Level III Sick to Hot plate, single element 1 Level II Step Down/Intermediate Care upon Instrument sterilizer 1 observance of infant's progress/development Incubator 4 and/or growing stability Radiant warmer 1 b. Nurse administers nursing care and clinical Weighing scale 1 procedures to infant Linen hamper 1 c. Nurse measures infant's height and head Waste bin 2 w/ yellow lining circumference

w/ black lining d. Nurse weighs infant Sharps container 1 e. Nurse records data gathered f. Nurse prepared baby, i.e. cleans and dresses FURNITURE AND baby, feeds baby, etc. FIXTURE CHECKLIST g. Nurse places baby in incubator Counter, 900mm high with 1 h. Nurse monitors infant's vital signs cabinets above and below Desk, 600 x 1000mm 1 Chair, stacking, upright 1 People Involved: Stool, adjustable height 1 4 x Infants Sink, with gooseneck faucet 1 1 x Nurse Cabinet, bedside 4 1 x Nursing Attendant Partition, 1700mm high, clear 3

glass upper panel

ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Nurse Station Outlet, 10A,2P,240V, duplex 7 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Outlet, data 1 Outlet, telephone 1

Smoke detector 1

Updated Reference: ROOM DATA SHEET NEONATAL INTENSIVE CARE UNIT Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: LEVEL II STEP DOWN QUANTITY REMARKS REMARKS QUANTITY 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS APRIL 2016 250B-NICU-RDS-07A 668


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature(°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (psi) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (psi) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.5 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: instrument sterilizer Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit infant and nursing staff Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET APRIL 2016 250B-NICU-RDS-07B NEONATAL INTENSIVE CARE UNIT LEVEL II STEP DOWN 669


KEY SCALE 1:100 M T 2 3 4 5 6 7 8 11 12 5100 6000 SD CH 13 15 1416 8 12 8 17 17 8 D 1 1 Counter, 900mm high with cabinets above and below 2 Desk, 600 x 1000mm 3 Chair, stacking, upright 4 Stool, adjustable height 5 Sink, with gooseneck faucet 6 Hot plate, single element 7 Instrument sterilizer 8 Incubator 9 Radiant warmer 10 Weighing machine 11 Cabinet, bedside 12 Partition, 1700mm high, clear glass upper panel 13 Hamper, soiled linen 14 Waste bin, infectious 15 Waste bin, general 16 Sharps container 17 Window, view 11 11 10 9 12 CH 670


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. An infant is transferred from Level II Step Down/ Hot plate, single element 1 Intermediate Care to Level I Growers upon Instrument sterilizer 1 observance of infant's progress/development Incubator 5 and/or growing stability Linen hamper 1 b. Nurse administers nursing care and clinical Waste bin 2 w/ yellow lining procedures to infant

w/ black lining c. Nurse measures infant's height and head Sharps container 1 circumference

d. Nurse weighs infant

e. Nurse records data gathered FURNITURE AND f. Nurse prepared baby, i.e. cleans and dresses FIXTURE CHECKLIST baby, feeds baby, etc. Counter, 900mm high with 1 g. Nurse places baby in incubator cabinets above and below h. Nurse monitors infant's vital signs Desk, 600 x 1000mm 1 Chair, stacking, upright 1 Stool, adjustable height 1 People Involved: Sink, with gooseneck faucet 1 5 x Infants Cabinet, bedside 5 1 x Nurse Partition, 1700mm high, clear 4 1 x Nursing Attendant glass upper panel

ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Planning Relationships: Outlet, 10A,2P,240V, duplex 7 grounding type, a. Adjacent to Nurse Station

universal slots Outlet, 10A,2P,240V, single 1 for emergency light Outlet, data 1 Outlet, telephone 1 Smoke detector 1

HEALTH FACILITY Hospital: LEVEL I GROWERS 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS April 2016 250B-NICU-RDS-08A QUANTITY REMARKS QUANTITY REMARKS Updated Reference: ROOM DATA SHEET NEONATAL INTENSIVE CARE UNIT Department of Health DEVELOPMENT BUREAU 671


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature(°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m.hr.) 25 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (psi) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (psi) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% at 1 micron Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.5 SOUND SAFETY Acceptable sound level (db) 40 Accessible hot surface: instrument sterilizer Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit infant and nursing staff Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET April 2016 250B-NICU-RDS-08B NEONATAL INTENSIVE CARE UNIT LEVEL I GROWERS 672


KEY SCALE 1:100 M T 2 3 4 5 6 7 8 9 10 5100 6000 SD CH 11 12 13 14 8 9 10 8 9 15 15 8 9 10 D 1 1 Counter, 900mm high with cabinets above and below 2 Desk, 600 x 1000mm 3 Chair, stacking, upright 4 Stool, adjustable height 5 Sink, with gooseneck faucet 6 Hot plate, single element 7 Instrument sterilizer 8 Incubator 9 Cabinet, bedside 10 Partition, 1700mm high, clear glass upper panel 11 Hamper, soiled linen 12 Waste bin, infectious 13 Waste bin, general 14 Sharps container 15 Window, view 8 9 10 673


VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.9 NUTRITION & DIETETICS SERVICE FACILITIES

First Edition DEPARTMENT OF HEALTH Manila 2017 675


Hospital: 250-Bed (Level 3) Hospital Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER 609.00 216.00 250B-DIET-RDS-01 78.00 250B-DIET-RDS-02 37.00 250B-DIET-RDS-03 14.00 250B-DIET-RDS-04 3.00 250B-DIET-RDS-05 20.00 250B-DIET-RDS-06 Food Conveyor Parking 22.00 250B-DIET-RDS-07 Cold Storage 14.00 250B-DIET-RDS-08 Dry Storage 14.00 250B-DIET-RDS-09 7.00 250B-DIET-RDS-10 Delivery Receiving Area 18.00 250B-DIET-RDS-11 Dishwashing and Pots Washing Area 45.00 250B-DIET-RDS-12 Waste Holding Area 12.00 250B-DIET-RDS-13 Dietitian's Office/ Staff Office 41.00 250B-DIET-RDS-14 Nutrition Clinic 14.00 250B-DIET-RDS-15 Staff Dining Area 18.00 250B-DIET-RDS-16 36.00 250B-DIET-RDS-17 PAGE Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU NUTRITION AND DIETETICS 250B-DIET-SFSI-01 NUTRITION AND DIETETICS Reference Sheet Number: SERVICE FACILITY SHEET INDEX

Service Facility Title: ROOM TITLE Hospital Staff Dining Room Cooking and Baking Area Serving and Food Assembly Area Blenderized and Tube Feeding Area Therapeutic Diet Preparation Area

Food Preparation Area Storage for Utensils/ Silverware

Staff T&B/ Locker Room

677 685 679 250B-DIET-DDS-01 678 700 703 727 724 715 712 709 706 691 721 682 688 694 697 718


12000 9000 6000 3000 3000 57000 18000 3000 3000 3000 3000 3000 3000 9900 2050 3000 3000 H O S P I T A L S T A F F D I N I N G H A L L COOKING AREA FOOD ASSEMBLY AREA RELEASING AREA BAKING AREA NUTRITION CLINIC FOOD PREPARATION AREA STAFF OFFICE TUBE FEEDING ROOM DIETITIAN'S OFFICE COLD STORAGE CONFERENCE DRY STORAGE DELIVERY RECEIVING AREA RECEIVING AREA TRAYS IN FROM WARDS POTS WASHING DISH WASHING WASTE HOLDING AREA ANTE ROOM STORAGE FOR UTENSILS/ SILVERWARE FEMALE STAFF T&B/LOCKERS STAFF DINING FOOD OUT TO WARDS 3000 MALE STAFF T&B/LOCKERS THERAPEUTIC DIET PREP AREA SCALE 1:300 M FOOD CONVEYOR PARKING 678


Department: Room Title: HOSPITAL STAFF DINING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Authorized hospital staff diners take their Counter, food; with tray shelf 1 meals and bain marie Water station 1 Cash register / POS 1 Waste bin w/ black lining 3 People Involved: FURNITURE AND QUANTITY REMARKS 72 x Hospital Staff/ Personnel per sitting FIXTURE CHECKLIST Counter, work top; w/ cabinets 1 above and below Sink, stainless steel 1 Counter; with lavatory 1 Table, dining; 4-seater 12 Table, dining; 6-seater 4 Chair, dining 72 Stool, adjustable height 1 Shelf, stainless steel 1 for dirty dishes Trays/utensils station 1 Concealed floor drain 1 Lavatory 2 Water closet 2 Urinal 1 Planning Relationships: a. Close to Serving & Food Assembly Area ADDITIONAL EQUIPMENT & QUANTITY REMARKS b. Close to Dishwashing Area ENGINEERING TERMINALS Window curtain rail 10 Outlet, 10A,2P,240V, duplex 9 grounding type,

universal Split type ACU, 3 ton 2 optional Outlet, telephone 1 countertop grounding type, Outlet, ceiling fan 3 grounding type, universal Outlet, 15A, 2P, duplex 1 for food warmer grounding type Outlet, 15A, 2P, duplex 1 for countertop grounding type Outlet, 15A, 2P, duplex 1 for countertop grounding type Outlet, 10A, 240V, single 2 exhaust fan, t&b 1 emergency light Smoke Detector 6 Reference Sheet Number: April 2016 NUTRITION & DIETETICS 250B-DIET-RDS-01A REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) 679


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: HOSPITAL STAFF DINING ROOM TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:desirable:UNNECESSARY % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 4.8 SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: Baine Marie (food warmer) Speech privacy essential: DESIRABLE: unnecessary Maximum temperature (°C) 100 Quality which cannot be NA Domestic hot water: at lavatory tolerated Maximum temperature (°C) 70 Access limit hospital staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET April 2016 NUTRITION & DIETETICS 250B-DIET-RDS-01B 680 Negative Pressure (Pa)
NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa)
NA View out essential:DESIRABLE:unnecessary


681 NA


Department: Room Title: NUTRITION & DIETETICS COOKING AND BAKING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Cooking and baking of food Hood, exhaust 2 Range, with oven 4 Range, with broiler 8 Kettle, tilting 3 Heavy-duty frying pan 1 Cauldron (Kawa) 1 Griddle pan 1 Rice cooker 1 Pressure cooker 1 Drainage 1 Waste bin w/ black lining 3 People Involved: FURNITURE AND 1 x Dietitian FIXTURE CHECKLIST 2 x Cook Counter, 900mm high 1 4 x Food Service Workers Sink, single compartment with 2 drainboard; 350-400mm deep Sink, double compartment with 1 drainboard; 350-400mm deep 2 Shelves, overhead 3 Drain, trench grating 9 Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Staff Dining Room Window curtain rail 4 b. Close to Dietitian's Office Outlet, 10A,2P,240V, duplex 13 grounding type,

universal slots Outlet, 10A,2P,240V, single 2 exhaust fan 1 emergency light Smoke Detector 3 ionization type High Pressure Gas Piping System 1 250B-DIET-RDS-02A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 682


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: COOKING AND BAKING AREA TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight ESSENTIAL:desirable:unnecessary Positive Pressure (Pa) NA View out ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: heat-generating appliances Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) 100 Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit dietetics staff Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET April 2016 NUTRITION & DIETETICS 250B-DIET-RDS-02B 683


684 Others NA


Department: Room Title: NUTRITION & DIETETICS FOOD PREPARATION AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Food Service Workers prepare food (i.e. wash and peel) Vertical Cutter 1 vegetables, slice and cut meat and fish, segregate food Vegetable slicer 1 b. Food Service Workers set-up and assemble cooked food Mixing bowl 3 c. Dietitian puts tags on prepared trays for pay patients Basket strainer 1 d. Food Service Workers place food trays and containers on Heavy-duty knives 3 food converyors to be taken to the wards Waste bin w/ green lining 1 biodegradable e. Pre-preparation of food like embutido, relyeno, etc. Waste bin w/ black lining 1 non-biodegradable People Involved: FURNITURE AND 1 x Dietitian FIXTURE CHECKLIST 2 x Cook Counter, work; stainless steel 1 4 x Food Service Workers Sink, single compartment, with 1 drainboard; 350-400mm deep Sink, double compartment, with 1 drainboard; 350-400mm deep Counter, food preparation; 1 stainless steel Counter, tray set-up; stainless steel 1 Shelves, overhead
1 Drain, trench grating; stainless 4 steel ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Adjacent to Staff Dining Window curtain rail 2 b. Close to Dietitian's Office Outlet, 10A,2P,240V, duplex 7 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Outlet, DATA 1 local Outlet, Telephone 1 Smoke Detector 1 ionization type QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-DIET-RDS-03A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 685


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS FOOD PREPARATION AREA 250B-DIET-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight ESSENTIAL:desirable:unnecessary Positive Pressure (Pa) NA View out ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: heat-generating appliances Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) 100 Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit dietetics staff Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET 686


687 NA


Department: Room Title: BLENDERIZED & TUBE FEEDING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Preparation of food needed for blenderized and tube Food Blender 1 feeding Bottles b. Preparation of equipment needed for blenderized Measuring cups 1 set tube feeding Measuring spoons 1 set Waste bin w/ black lining 1 People Involved: FURNITURE AND QUANTITY REMARKS 1 x Nutritionist/ Dietitian FIXTURE CHECKLIST 2 x Food Service Workers Counter, work; stainless steel, 1 with cabinets above and shelves below Sink, single compartment, with 1 drainboard; 350-400mm deep Stool, adjustable height 1 Concealed floor drain 1 ADDITIONAL EQUIPMENT & QUANTITY REMARKS Planning Relationships: ENGINEERING TERMINALS a. Close to Therapeutic Diet Area Window curtain rail 1 b. Adjacent to Dietitian/ Nutritionist's Office Outlet, 10A,2P,240V, duplex 3 grounding type, universal Outlet, 15A, 240V, single 3 countertop Outlet, 10A,2P,240V, single 1 emergency light 1 exhaust Smoke Detector 1 ACU, window type 1 April 2016 NUTRITION & DIETETICS 250B-DIET-RDS-04A REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 688


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS BLENDERIZED & TUBE FEEDING AREA 250B-DIET-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit dietetics staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 689


690


Department: Room Title: NUTRITION & DIETETICS THERAPEUTIC DIET PREPARATION AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. The Nutritionist/ Dietitian prepare for the therapeutic Dietetic Scale 1 diet modified from regular diet Knives and chopping board 1 set b. The Nutritionist/ Dietitian measures and determines the Vegetable peeler 1 portion or size to be given to the patient Measuring cups 1 set Measuring spoons 1 set Food trays Food tags People Involved: FURNITURE AND 1 x Nutritionist/ Dietitian FIXTURE CHECKLIST 1 x Food Service Worker Counter, stainless steel, food 1 assembly Stool, adjustable height 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Blenderized and Tube Feeding Area ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 1 Outlet, 10A,2P,240V, single 3 emergency light Outlet, Electric Fan 1 wall-mounted REMARKS REMARKS QUANTITY QUANTITY QUANTITY REMARKS 250B-DIET-RDS-05A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 691


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS THERAPEUTIC DIET PREPARATION AREA 250B-DIET-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit dietetics staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 692


693 NA


Department: Room Title: NUTRITION & DIETETICS SERVING AND FOOD ASSEMBLY AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Food Service Workers set up and assemble cooked food Dietetic Scale 1 b. Food Service Workers place food trays and containers Diet tags on food conveyors to be taken to the wards People Involved: FURNITURE AND 1 x Nutritionist/ Dietitian FIXTURE CHECKLIST 2 x Food Service Workers Counter, work; stainless steel 1 Sink, single compartment, with 1 drainboard; 350-400mm deep Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Staff Dining Room ENGINEERING TERMINALS b. Close to Dietitian's Office Outlet, 10A,2P,240V, duplex 3 grounding type universal slot Outlet, 10A,2P,240V, single 1 for emergency light Smoke Detector 1 250B-DIET-RDS-06A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 694


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS SERVING AND FOOD ASSEMBLY AREA 250B-DIET-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering ESSENTIAL:desirable:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit dietetics staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 695


NA 696


Department: Room Title: NUTRITION & DIETETICS FOOD CONVEYOR PARKING FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Washing of food tray truck/ conveyor Tray truck, stainless steel, 4 b. Transit station for food tray truck/ conveyor 700 x 1800 People Involved: FURNITURE AND 2 x Food Service Workers FIXTURE CHECKLIST Faucet, with hose bibb 1 Floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Dishwashing Area ENGINEERING TERMINALS b. Adjacent to Food Assembly/ Tray Set-up Area Window curtain rail 1 Outlet, 10A,2P,240V, duplex 1 grounding type universal slot Outlet, 10A,2P,240V, duplex 1 GFCI Outlet, 10A,2P,240V, single 1 emergency light Smoke Detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 250B-DIET-RDS-07A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 697


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS FOOD CONVEYOR PARKING 250B-DIET-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering ESSENTIAL:desirable:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: at faucet tolerated Maximum temperature (°C) 70 Access limit dietetics staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 698


NA 699


Department: Room Title: NUTRITION & DIETETICS COLD STORAGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of poultry, meat and dairy products procured Refrigerator, 20 c.u. ft. 2 b. Storage of food that easily spoils (egg, vegetables, fruits) Freezer, 20 cu. Ft. 2 c. Storage of leftover cooked food that are still edible Chiller, 20 cu. Ft., reach-in 3 Exhaust fan 1 Weighing scale 1 Food cart 1 Plastic pallet 2 People Involved: FURNITURE AND 1 x Food Service Worker FIXTURE CHECKLIST Table, stainless steel;
1 750 x 1200mm Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Dry Storage Room ENGINEERING TERMINALS b. Close to Receiving Area Outlet, 10A,2P,240V, duplex 10 grounding type c. Adjacent to Dietitian's Office universal slots Outlet, 10A,2P,240V, single 1 emergency light 1 exhaust fan Smoke Detector 1 250B-DIET-RDS-08A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY REMARKS QUANTITY QUANTITY REMARKS 700


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS COLD STORAGE 250B-DIET-RDS-08B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit dietetics staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 701


702 NA


Department: Room Title: NUTRITION & DIETETICS DRY STORAGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of food procured Ladder, step 1 b. Storage of food intended for the next two meals Cart, push 1 c. Storage of excess supplies for future use Digital Weighing Scale 1 d. Storage of food that does not spoil easily Calculator 1 Ceiling Fan 1 People Involved: FURNITURE AND 1 x Food Service Worker FIXTURE CHECKLIST Counter, work 1 Shelves, 400mm deep 1 Cabinet, lockable 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Cold Storage Room ENGINEERING TERMINALS Outlet, 10A,2P,240V, single 3 grounding type, Smoke Detector parallel slots 1 emergency light 1 250B-DIET-RDS-09A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 703


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS DRY STORAGE 250B-DIET-RDS-09B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential: desirable: UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit dietetics staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 704 % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary


705 NA


Department: Room Title: NUTRITION & DIETETICS STORAGE FOR UTENSILS/ SILVERWARE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of kitchen utensils and silverware People Involved: FURNITURE AND QUANTITY REMARKS 2 x Food Service Workers FIXTURE CHECKLIST Shelves, open, 600mm deep Planning Relationships: ADDITIONAL EQUIPMENT & QUANTITY REMARKS a. Close to Dietitian's Office ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 2 groundng type, universal Outlet, 10A,2P,240V, single 1 REMARKS QUANTITY 250B-DIET-RDS-10A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 706


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS STORAGE FOR UTENSILS/ SILVERWARE 250B-DIET-RDS-10B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential: desirable: UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit dietetics staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 707


NA 708


Department: Room Title: NUTRITION & DIETETICS DELIVERY RECEIVING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Dietitian on duty and Auditor witness weighing of food Scale, platform, heavy duty 1 delivered by the supplier Hanging scale with pan 2 b. Auditor inspects and checks quality of food items purchasedPush cart 1 from the market and those delivered by the supplier Electric fan, ceiling type 1 Plastic Pallets People Involved: FURNITURE AND 1 x Nutritionist/ Dietitian FIXTURE CHECKLIST 1 x Food Service Worker Counter, stainless steel 1 1 x Auditor Sink, single compartment with 1 2 x Agency Inspectors drainboard; 350-400mm deep Counter, tiled 1 Shelves, open 1 Concealed floor drain 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Dietitian's Office ENGINEERING TERMINALS b. Close to Cold and Dry Storage Rooms Window curtain rail 1 Outlet, 10A,2P,240V, duplex 6 grounding type universal slot Outlet, 10A,2P,240V, single 1 for emergency light Exhaust fan 1 ionization type Smoke Detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 250B-DIET-RDS-11A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 709


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS DELIVERY RECEIVING AREA 250B-DIET-RDS-11B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering ESSENTIAL:desirable:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be Tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit chief dietitian & staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 710


NA 711


Department: Room Title: NUTRITION & DIETETICS DISHWASHING & POTS WASHING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Washing of pots, pans, trays, dishes and other kitchen Dishwashing machine, floor unit 1 utensils. Waste container, 380mm dia. 1 b. Food Service Workers perform other clean-up activities Waste bin w/ black lining 1 People Involved: FURNITURE AND 2 x Food Service Workers FIXTURE CHECKLIST Counter, stainless steel 1 Sink, double compartment with 2 drainboard Grease trap 1 Counter, with upturned edge 1 Shelves, open 2 Table, feeder, stainless steel 1 Table, work, stainless steel 2 700 x 1200mm 1 700 x 2400mm Concealed floor drain 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Food Preparation Area ENGINEERING TERMINALS b. Close to Dietitian's Office Window curtain rail 3 Outlet, 10A,2P,240V, duplex 6 grounding type parallel Outlet, 10A,2P,240V, single 1 emergency light Smoke Detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 250B-DIET-RDS-12A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 712


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS DISHWASHING & POTS WASHING AREA 250B-DIET-RDS-12B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit dietetics staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 713


714 NA


Department: Room Title: NUTRITION & DIETETICS WASTE HOLDING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Food Service Workers sort garbage accordingly Garbage bin/ container 4 b. Food Service Workers pack garbage and/or place sorted Faucet w/ hose bib 1 garbage into proper bins/ container c. Garbage generated for a day or two is temporarily stationed in this area prior to being collected for transfer to the waste management service People Involved: FURNITURE AND 1 x Food Service Worker FIXTURE CHECKLIST Floor Drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Located in the perimeter of the Dietetics Area ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 1 GFCI Outlet, 10A,2P,240V, single 1 emergency light 1 exhaust fan Smoke Detector 1 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS QUANTITY REMARKS REMARKS QUANTITY 250B-DIET-RDS-13A April 2016 715


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS WASTE HOLDING AREA 250B-DIET-RDS-13B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) NA Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential: desirable: UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit food service workers Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 716


717 NA


Department: Room Title: DIETITIAN'S OFFICE & STAFF OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Chief Dietitian calls meetings with staff for the preparation Computer 1 of monthly menu Calculating machine 2 b. Chief Dietitian and staff reads, writes and uses telephone FAX machine 1 in his work station Printer 1 c. Dietitian and staff receive visitors Telephone 1 d. Dietitian and staff store, file and retrieves records Waste bin w/ black lining 4 People Involved: FURNITURE AND 1 x Chief Dietitian FIXTURE CHECKLIST 3 x Staff Desk, 600 x 1200mm 1 Desk, 600 x 1500mm 3 Desk, extension; 400mm deep 1 Cabinet, steel; filing 2 Chair, junior executive 1 Chair, visitor 5 Chair, swivel 3 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Located in the kitchen where it shall give the Dietitian Window curtain rail 6 extensive view of work areas and control over possible Outlet, 10A, 2P, 240V, duplex 12 grounding type, pilferage of dietary supplies and equipment

universal slots Outlet, 15A, 2P, 240V, single 1 emergency light Outlet, DATA 4 Outlet, Telephone 2 Smoke Detector 2 ACU, window/ split-type 1 NUTRITION & DIETETICS April 2016 250B-DIET-RDS-14A Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 718


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS DIETITIAN'S OFFICE & STAFF OFFICE 250B-DIET-RDS-14B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 Micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.44 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit chief dietitian & staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 719


NA 720


Department: Room Title: NUTRITION & DIETETICS NUTRITION CLINIC FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Dietitian/ Nutritionist does individual food-related Scale, weighing 1 counselling Whiteboard 1 b. Dietitian/ Nutritionist does body fat testing Food Model c. Pamphlets on vegetarianism, exercise, cholesterol Food Pyramid Guide and weight reduction are given to patients Measuring cups 1 set d. Dietitian provides nutrition counselling to help treat and Measuring spoon 1 set prevent disease through dietary changes Waste bin w/ black lining 1 People Involved: FURNITURE AND 1 x Dietitian/ Nutritionist FIXTURE CHECKLIST 1 x Patient Desk, 600 x 1200mm 1 Desk, extension, 400 x 1200mm 1 Chair; upright, stacking 6 Counter, 900mm high, shelves 1 above and below Sink, stainless steel, with 1 drainboard Concealed floor drain 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Located within the Dietary Department Window curtain rail 1 b. Adjacent to the Dietitian's Office Outlet, 10A,2P,240V, duplex 6 grounding type, c. Must have an access outside the Dietary Department

universal slots ACU, window/ split-type 1 Outlet, Intercom 1 wall-mounted Outlet, Telephone 1 desktop Outlet, DATA 1 Smoke Detector 1 ionization type 250B-DIET-RDS-15A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 721


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS NUTRITION CLINIC 250B-DIET-RDS-15B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 Micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE: unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit dietitian/nutritionist and patient Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 722


NA 723


Department: Room Title: NUTRITION & DIETETICS STAFF DINING AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Dietetics staff take their meals Waste bin w/ black lining 1 People Involved: FURNITURE AND Dietetics Staff/ Personeel FIXTURE CHECKLIST Table, 1100 x 1800mm 1 Chair; upright, stacking 6 Counter, 900mm high, shelves 1 above and below Sink, stainless steel 1 Concealed Floor Drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Dietetics Service ENGINEERING TERMINALS Window curtain rail 2 Outlet, 10A,2P,240V, duplex 6 grounding type universal slot Outlet, 10A,2P,240V, single 1 emergency light Smoke Detector 1 250B-DIET-RDS-16A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 724


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 NUTRITION & DIETETICS STAFF DINING AREA 250B-DIET-RDS-16B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93% - 99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.53 SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit dietetics staff Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET 725


NA 726


Department: Room Title: STAFF T&B/ LOCKER ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Food Service Supervisor/ Workers/ Cooks change Exhaust fan 2 clothes in toilet and bathroom Waste bin w/ black lining 2 b. Food Service Supervisor/ Workers/ Cooks bathe and perform other personal hygiene activities c. Food Service Supervisor/ Workers/ Cooks store clothing and personal effects in the Locker Area People Involved: FURNITURE AND 8 x Food Service Workers FIXTURE CHECKLIST 2 x Cooks Lockers, steel 20 1 x Food Supervisor Water Closet 4 Lavatory 6 Urinal 2 Floor Drain 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Dishwashing Area ENGINEERING TERMINALS b. Adjacent to Food Assembly/ Tray Set-up area Window curtain rail 2 Outlet, 10A,2P,240V, duplex 2 grounding type,

universal slots Water Heater, 6kw 2 Male & Female T&B April 2016 NUTRITION & DIETETICS 250B-DIET-RDS-17A QUANTITY REMARKS QUANTITY REMARKS REMARKS QUANTITY Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 727


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: STAFF T&B/ LOCKER ROOM TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) NA Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy
ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit dietetics staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET NUTRITION & DIETETICS April 2016 250B-DIET-RDS-17B 728


NA 729


VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.10 ENGINEERING, MAINTENANCE and HOUSEKEEPING SERVICE FACILITIES

First Edition DEPARTMENT OF HEALTH Manila 2017 731


Hospital: 250-Bed (Level 3) Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER ENGINEERING, MAINTENANCE 429.00 & HOUSEKEEPING Garage, Work, and Parking Areas 135.00 250B-ENG-RDS-01 Drivers' Lounge 18.00 250B-ENG-RDS-02 Security Office 18.00 250B-ENG-RDS-03 Housekeeping Office 18.00 250B-ENG-RDS-04 Biomedical Engineering Workshop 36.00 250B-ENG-RDS-05 Carpentry Workshop 18.00 250B-ENG-RDS-06 Electrical and Mechanical Workshop 250B-ENG-RDS-07 Head's Office 18.00 250B-ENG-RDS-08 Staff Office 36.00 250B-ENG-RDS-09 Conference Room 18.00 250B-ENG-RDS-10 Staff Pantry 18.00 250B-ENG-RDS-11 Male Quarters & Lockers 23.00 250B-ENG-RDS-12 Male & Female Toilets, and Janitor's Closet 8.00 250B-ENG-RDS-13 Storage 18.00 250B-ENG-RDS-14

ENGINEERING, MAINTENANCE & HOUSEKEEPING 250B-ENG-SFSI-01 ROOM TITLE PAGE

SERVICE FACILITY SHEET INDEX Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU Service Facility Title: Reference Sheet Number: 250B-ENG-DDS-01 734 735 741 738 744 747 750 753 756 759 762 765 768 774 771 733 36.00 Plumbing Workshop 18.00 250B-ENG-RDS-15 777


POWER HOUSE PUMP ROOM MALE QUARTERS PANTRY STAFF OFFICE CARPENTRY WORKSHOP MECHANICAL & ELECTRICAL WORKSHOP PLUMBING WORKSHOP DRIVERS' LOUNGE BIOMEDICAL ENGINEERING WORKSHOP SECURITY OFFICE STORAGE ROOM HEAD'S OFFICE CONFERENCE ROOM FT MT MALE LOCKERS 9000 6000 6000 3000 6000 3000 3000 12000 6000 3000 6000 15000 S E R V I C E Y A R D GARAGE WORK AREA HOUSE- KEEPING OFFICE AMBULANCE PARKING SCALE 1:300 M 15000 6000 6000 3000 3000 3000 3000 3000 3000 3000 6000 6000 7400 1600 734 36000


Department: Room Title: ENGINEERING AND MAINTENANCE GARAGE, WORK & PARKING AREAS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Mechanic checks/ repairs vehicles Hydraulic lifter 1 b. Driver parks vehicles Oil interceptor pit 1 c. Driver cleans vehicles Whiteboard 1 Pressure washer 1 Vacuum pump 1 Air compressor 1 Waste bin 1 Fire Extinguisher 1 People Involved: FURNITURE AND 1 x Mechanic FIXTURE CHECKLIST 1 x Driver Shelf, 500mm deep 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Workship (Electrical and Mechanical) and ENGINEERING TERMINALS Drivers' Lounge Outlet, 10A,2P,240V, duplex 7 grounding type,

universal Outlet, 10A, 240V, single 1 emergency light Smoke Detector 4 QUANTITY REMARKS ROOM DATA SHEET 250B-ENG-RDS-01A Department of Health HEALTH FACILITY QUANTITY REMARKS Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: 735


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE GARAGE, WORK & PARKING AREAS 250B-ENG-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) NA Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) NA Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering and maintenance staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 736


NA 737


Department: Room Title: ENGINEERING AND MAINTENANCE DRIVERS' LOUNGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Driver rests, sleeps, stores clothings and other Refrigerator 1 belongings while waiting for transport service Whiteboard / bulletin board 1 b. Driver types trip tickets and requests for gasoline Water dispenser 1 c. Driver prepares and fills-up the endorsement Waste bin w/ black lining 1 checklist form Typewriter 1 d. Driver receives request for transport e. Driver stores, files and retrieves trip tickets and other documents f. Mechanic prepares and records in a log book the preventive maintenance of vehicles and records of registration renewal g. Mechanic receives spare parts for repair of vehicle People Involved: FURNITURE AND Driver FIXTURE CHECKLIST Mechanic Sofa, 2-seater 2 Table, side, 400 x 400mm 1 Counter, with cabinets 1 above & below Sink, kitchen 1 Closet, built-in 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Engineering and Maintenance ENGINEERING TERMINALS Building Window curtain rail 3 Outlet, 15A,2P,240V, duplex 7 grounding type universal Outlet, 10A, 240V, single 1 emergency light Smoke Detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 250B-ENG-RDS-02A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 738


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE DRIVERS' LOUNGE 250B-ENG-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering and maintenance staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 739


NA 740


Department: Room Title: ENGINEERING AND MAINTENANCE SECURITY OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Security staff reads, writes and uses telephone in Computer 1 work station Calculator 1 b. Security staff receives visitors CCTV monitor 1 c. Security staff stores, files and retrieves records Telephone 1 d. Security staff uses computer Hand Held Radio 1 e. Secuirty staff writes detailed reports on crime Fire Extinguisher 1 incidents within the hospital vicinity/ compound Metal Detector 1 f. Storage of firearms, handcuffs, and restraints ACU 1 g. If with CCTV's, the security staff watches/ monitors Whiteboard 1 video camera, alarm systems for signs of crime Waste bin w/ black lining 1 fire or disorder within the hospital compound h. Secuirty staff stores clothing and personal protective equipment in the storage room i. Secuirty staff stores confiscated materials People Involved: FURNITURE AND 1 x Chief Security FIXTURE CHECKLIST 2 x Security Guards Desk, 600 x 1200mm 1 Chair, swivel 1 Chair, upright, stacking 2 Shelves, 400 x 1500mm 1 Cabinet, side, 400 x 1200 1 Cabinet, steel filing 2 Shelves, open 1 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Within the Engineering and Maintenance Window curtain rail 1 Building Outlet, 15A,2P,240V, duplex 6 grounding type universal Outlet, 10A, 240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Outlet, ACU 1 Smoke Detector 1 250B-ENG-RDS-03A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 741


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE SECURITY OFFICE 250B-ENG-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit security staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 742


743 NA


Department: Room Title: ENGINEERING AND MAINTENANCE HOUSEKEEPING OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Janitorial staff reads, writes and uses telephone in Computer 1 work station Calculator 1 b. Janitorial staff receives visitors CCTV monitor 1 c. Janitorial staff stores, files and retrieves records Whiteboard 1 d. Supervisor uses computer Waste bin w/ black lining 1 e. Supervisor makes iventory of cleaning supplies/ paraphernalia and places orders for them or reports to the Supply Officer f. Storage of clothing and personal protective equipment g. Storage of cleaning tools and supplies People Involved: FURNITURE AND Janitorial staff FIXTURE CHECKLIST Supervisor Desk, 600 x 1200mm 1 Chair, swivel 1 Chair, upright, stacking 2 Shelves, 400 x 1500mm 1 Cabinet, side, 400 x 1200 1 Cabinet, steel filing 2 Counter, with cabinets above 1 and below Sink, stainless steel 1 Concealed floor drain 1 Shelves, open 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Engineering and Maintenance ENGINEERING TERMINALS Building Window curtain rail 1 Outlet, 15A,2P,240V, duplex 6 grounding type universal Outlet, 10A, 240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke Detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 250B-ENG-RDS-04A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 744


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE HOUSEKEEPING OFFICE 250B-ENG-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit janitorial staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 745


746 NA


Department: Room Title: BIOMEDICAL ENGINEERING WORKSHOP FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Repair of medical equipment such as suction Circular pan 1 apparatus, negatoscope, BP apparatus, etc. Biomedical tools 1 set b. Prepares the needed supplies and equipment for Whiteboard 1 the repair of medical apparatuses and units Waste bin w/ black lining 1 general People Involved: FURNITURE AND 1 x Biomed Technician FIXTURE CHECKLIST Table, work, 1 w/ 2" thk tabletop Counter, work, 900mm high 1 w/ 2" thk tabletop Cabinet, wall hung 1 Stool, adjustable 2 Bench 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Engineering and Maintenance ENGINEERING TERMINALS Building Window curtain rail 3 Outlet, 15A,2P,240V, duplex 8 grounding type universal Outlet, 10A, 240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke Detector 1 April 2016 ENGINEERING AND MAINTENANCE 250B-ENG-RDS-05A Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 747


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: BIOMEDICAL ENGINEERING WORKSHOP TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering and maintenance staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET April 2016 ENGINEERING AND MAINTENANCE 250B-ENG-RDS-05B 748


NA 749


Department: Room Title: ENGINEERING AND MAINTENANCE CARPENTRY WORKSHOP FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Repair of hospital furniture, cabinets, chairs and Circular pan 1 other woordworks Carpentry tools 1 set b. Assemble/ fabricate furniture and other woodworks Whiteboard 1 c. Painting, varnishing and refinishing of hospital Waste bin w/ black lining 1 furniture and other woodworks d. Prepares the needed supplies and tools for the repair of facilities People Involved: FURNITURE AND 1 x Carpenter FIXTURE CHECKLIST 1 x Painter Table, work 1 w/ 2" thk tabletop Counter, work, 900mm high 1 w/ 2" thk tabletop Counter, work, open below 1 Cabinet, wall hung 1 Cabinet, with shelves 1 Stool, adjustable 1 Bench 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Engineering and Maintenance ENGINEERING TERMINALS Building Outlet, 15A,2P,240V, duplex 6 grounding type universal Outlet, 10A, 240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke Detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 250B-ENG-RDS-06A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 750


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE CARPENTRY WORKSHOP 250B-ENG-RDS-06B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering and maintenance staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 751


NA 752


Department: Room Title: ENGINEERING AND MAINTENANCE ELECTRICAL & MECHANICAL WORKSHOP FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Repair of aircons and refrigerators Circular pan 1 b. Welding of trolleys, steel cabinets, cribs and other Electrical and mechanical tools 1 set steel works Whiteboard 1 c. Prepares the needed supplies and tools for the Waste bin w/ black lining 1 repair of facilities and building equipment d. Repair of telephone and other building apparatuses People Involved: FURNITURE AND 1 x Electrician FIXTURE CHECKLIST 1 x Aircon Technician Table, work 1 w/ 2" thk tabletop 1 x Electronic Technician Counter, work, 900mm high 2 w/ 2" thk tabletop Counter, work, open below 1 Cabinet, wall hung 1 Stool, adjustable 3 Bench 1 Shelving, open 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Engineering and Maintenance ENGINEERING TERMINALS Building Window curtain rail 1 Outlet, 15A,2P,240V, duplex 8 grounding type universal Outlet, 10A, 240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke Detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 250B-ENG-RDS-07A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 753


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE ELECTRICAL & MECHANICAL WORKSHOP 250B-ENG-RDS-07B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering and maintenance staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 754


NA 755


Department: Room Title: ENGINEERING AND MAINTENANCE HEAD'S OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Reads, writes and uses telephone in Computer 1 w/ printer work station Calculator 1 b. Receives visitors Drafting tools 1 set c. Uses toilet facilities ACU 1 d. Reviews and approves engineering and Whiteboard 1 architectural plans Waste bin w/ black lining 1 e. Approves documents and receives reports People Involved: FURNITURE AND 1 x Engineering Head FIXTURE CHECKLIST Visitors Desk, 600 x 1500mm 1 Engineering Staff Desk extension, 300 x 1500mm 1 Chair, swivel 1 Chair, upright, stacking 2 Sofa, 2-seater 1 Cabinet, steel filing 2 Water closet w/ spray hose 1 Lavatory 1 Floor Strainer 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Staff Office, Conference Room and ENGINEERING TERMINALS Storage Area Window curtain rail 1 Outlet, 10A,2P,240V, duplex 6 grounding type universal Outlet, 10A,2P,240V, duplex 1 GFCI Outlet, 10A, 240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke Detector 1 250B-ENG-RDS-08A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 756


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE HEAD'S OFFICE 250B-ENG-RDS-08B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering head & maintenance staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 757


NA 758


Department: Room Title: ENGINEERING AND MAINTENANCE STAFF OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Reads, writes and uses telephone in Computer 1 w/ printer work station Calculator 1 b. Receives visitors Drafting tools 1 set c. Stores, files and retrieves records ACU 1 d. Uses drafting tools Photocopy machine 1 e. Uses computer Low partition, 1800mm high 1 f. Requests, receives, and stores spare parts and Whiteboard / bulletin board 1 g. supplies Waste bin w/ black lining 3 h. Prepares documents for repair of vehicles i. Receives and records job order requests j. Prepares and records in a logbook the preventive maintenance of equipment and other facilities Reproduces copies of plans and documents People Involved: FURNITURE AND 1 x Maintenance Supervisor FIXTURE CHECKLIST 2 x Mechanics/ Carpenters Desk, 600 x 1200mm 7 Plumber Chair, upright; stacking 12 Carpenter/ Painter Cabinet, steel filing 3 Electrician Counter, with cabinets 1 Electronic Technician above & below Driver Sink, kitchen 1 Aircon Technician Table, 4-seater 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Engineering and Maintenance ENGINEERING TERMINALS Building Window curtain rail 2 Outlet, 10A,2P,240V, duplex 13 grounding type universal Outlet, 10A, 240V, single 2 emergency light Outlet, DATA 5 Outlet, Telephone 2 Smoke Detector 1 QUANTITY REMARKS REMARKS REMARKS QUANTITY QUANTITY 250B-ENG-RDS-09A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 759


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE STAFF OFFICE 250B-ENG-RDS-09B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:desirable:UNNECESSARY Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 2.4 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering & maintenance staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 760


761 NA


Department: Room Title: ENGINEERING AND MAINTENANCE CONFERENCE ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Engineering staff/ visitors hold meetings and/ or Computer 1 special lectures Projector 1 Sound System 1 ACU 1 Whiteboard/projection screen
1 Waste bin, general 1 People Involved: FURNITURE AND 1 x Maintenance Supervisor FIXTURE CHECKLIST Engineering Staff Table, conference, 8-seater 1 Visitors Chair, conference 8 Table, 900mm high, with
1 shelves/cabinets below Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Engingeering and Maintenance ENGINEERING TERMINALS Building Outlet, 10A,2P,240V, duplex 9 grounding type universal Outlet, 10A, 240V, single 1 emergency light Outlet, DATA 1 Outlet, Telephone 1 Smoke Detector 1 250B-ENG-RDS-10A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 762


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE CONFERENCE ROOM 250B-ENG-RDS-10B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500-700 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering & maintenance staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 763


NA 764


Department: Room Title: ENGINEERING AND MAINTENANCE STAFF PANTRY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Engineering Staff cook food for their meals Two-burner electric stove 1 b. Staff store their uncooked and cooked/ leftover food Exhaust fan 1 at the refrigerator Fire Extinguisher 1 c. Engineering Staff eat their meals at the party Refrigerator 1 d. Staff do clean-up activities Water dispenser 1 Waste bin w/ black lining 1 People Involved: FURNITURE AND 6 x Engineering Staff FIXTURE CHECKLIST Table, dining,6-seater 1 Chair, dining 6 Counter, with cabinets 1 above and below Sink, stainless steel 1 Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Withing the Engineering and Maintenance ENGINEERING TERMINALS Building Window curtain rail 1 Outlet, 10A,2P,240V, duplex 8 grounding type universal Outlet, 10A, 240V, single 1 emergency light Smoke Detector 1 250B-ENG-RDS-11A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 765


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE STAFF PANTRY 250B-ENG-RDS-11B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 1.2 SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering & maintenance staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 766


NA 767


Department: Room Title: ENGINEERING AND MAINTENANCE MALE QUARTERS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Maintenance staff rests, sleeps, and/ or store clothings ACU 1 and other personal belongings Waste bin w/ black lining 1 People Involved: FURNITURE AND 3 x Engineering Staff FIXTURE CHECKLIST Bed, single, with mattress 3 Table, side 4 Closet 1 Locker, 300 x 400mm 8 Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Engineering and Maintenance ENGINEERING TERMINALS Building Window curtain rail 1 Outlet, 10A,2P,240V, duplex 7 grounding type universal Outlet, 10A, 240V, single 1 emergency light Smoke Detector 1 250B-ENG-RDS-12A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 768


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE MALE QUARTERS 250B-ENG-RDS-12B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering & maintenance staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 769


NA 770


Department: Room Title: ENGINEERING AND MAINTENANCE T&B AND JAN. CLO. FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Engineering staff change clothes in T&B Exhaust fan 1 b. Engineering staff take a bath in T&B Waste bin w/ black lining 2 c. Engineering staff urinate and defecate People Involved: FURNITURE AND 4 x Engineering Staff FIXTURE CHECKLIST 1 x Janitor Water closet w/ spray hose 3 Urinal 2 Lavatory 3 Janitor's slop sink; with faucet 1 Shelf, open 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Conference Room and Male Quarters ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 2 GFCI Outlet, 10A, 240V, single 1 emergency light Smoke Detector 1 250B-ENG-RDS-13A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 771


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE T&B AND JAN. CLO. 250B-ENG-RDS-13B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering & maintenance staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 772


NA 773


Department: Room Title: ENGINEERING AND MAINTENANCE STORAGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of carpentry tools Exhaust fan 1 b. Storage of equipment used in the maintenance of Waste bin w/ black lining 1 vehicles and facilities c. Storage of spare parts for motor vehicles d. Storage of supplies and equipment for plumbing electrical, carpentry, welding, and painting works People Involved: FURNITURE AND Maintenance/ Engineering Staff FIXTURE CHECKLIST Shelving, open 2 Cabinet 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Biomedical Engineering Workship, ENGINEERING TERMINALS Carpentry Workshop and Head Office Window curtain rail 1 Outlet, 10A,2P,240V, duplex 2 grounding type universal Outlet, 10A, 240V, single 1 emergency light Smoke Detector 1 250B-ENG-RDS-14A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY QUANTITY REMARKS REMARKS QUANTITY 774


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 ENGINEERING AND MAINTENANCE STORAGE 250B-ENG-RDS-14B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:desirable:UNNECESSARY Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit engineering & maintenance staff Fire risk low:MEDIUM: high Other risks NA ROOM DATA SHEET 775


NA 776


777


778


KEY SCALE 1:100 M SD 1 Table, work; with 2" thick tabletop 2 Counter, work; 900mm high, with 2" thick tabletop 3 Counter, 750mm high, with deep work sink 4 Stool, adjustable 5 Bench 6 Floor drain 7 Whiteboard/ bulletin board 8 Waste bin 9 Window 3000 6000 1 2 D T 3 6 5 4 7 9 8 CH 779


VOLUME 3 DEPARTMENTAL PLANS and
TECHNICAL REQUIREMENTS
of a 250-BED HOSPITAL (LEVEL 3)

3.11 SUPPORT SERVICE FACILITIES

3.11.1 LINEN and LAUNDRY 3.11.2 PROPERTY and SUPPLY 3.11.3 MORGUE 3.11.4. CENTRAL WASTE STORAGE

First Edition DEPARTMENT OF HEALTH Manila 2017 781


Hospital: 250-Bed (Level 3) Updated Reference: April 2016 SPACE DEMAND TOTAL AREA REFERENCE SHEET (SQ. MTS.) (SQ. MTS.) NUMBER LINEN AND LAUNDRY 172.00 250B-LL-DDS-01 784 Issuing, Office, Work Room, and Storage 68.00 250B-LL-RDS-01 785 Pressing and Ironing Room 41.00 250B-LL-RDS-02 788 Washing/ Drying Room 8.00 250B-LL-RDS-03 791 Receiving/ Sorting/ Disinfection Area 8.00 250B-LL-RDS-04 794 Staff Lockers and T&B 16.00 250B-LL-RDS-05 797 Sewing & Sorting Room 31.00 250B-LL-RDS-06 800 PROPERTY AND SUPPLY 246.00 250B-PS-DDS-01 803 Storage/ Warehouse 144.00 250B-PS-RDS-01 804 Work Area 42.00 250B-PS-RDS-02 807 Head's Office 24.00 250B-PS-RDS-03 810 Staff Pantry 9.00 250B-PS-RDS-04 813 Staff Lockers, T&B, & Janitor's Closet 27.00 250B-PS-RDS-05 816 MORGUE 157.00 250B-MOR-DDS-01 819 Autopsy and Tissue Processing Room 54.00 250B-MOR-RDS-01 820 Morgue 90.00 250B-MOR-RDS-02 823 Staff Lockers, T&B, & Janitor's Closet 13.00 250B-MOR-RDS-03 826 CENTRAL WASTE STORAGE 60.00 250B-CWS-DDS-01 829 Work Area 12.00 250B-CWS-RDS-01 830 Hazardous Waste Room 12.00 250B-CWS-RDS-02 833 Mercury-Containing Devices/ Lamps 12.00 250B-CWS-RDS-03 836 Biodegradables 12.00 250B-CWS-RDS-04 839 Non-Biodegradables 12.00 250B-CWS-RDS-05 842

Reference Sheet Number:

SERVICE FACILITY SHEET INDEX Service Facility Title: ROOM TITLE PAGE Department of Health

HEALTH FACILITY DEVELOPMENT BUREAU 250B-SUP-SFSI-01 SUPPORT SERVICE FACILITY 783


784


Department: Room Title: LINEN AND LAUNDRY ISSUING, OFFICE, WORK ROOM & STORAGE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Laundry workers classify, count and record clean linen in Trolley/pushcart, linen 1 the log book Sewing machine 2 b. Seamstress repairs or mends torn linen and Marking machine 1 records it in the log book Step ladder, adjustable 2 c. Head of unit receives linen issue slip and prepares linen Waste bin w/ black lining 2 items for issuance d. Laundry workers pack linen and deliver to wards e. Head of linen/ laundry unit prepares forms for purchase of materials f. Linen unit receive materials and do the sewing of linen and other necessary preparations g. Head of linen/ laundry unit prepares memo receipt to the head of unit and notifies the requsitioning unit when materials are ready h. Head of linen unit retrieves and stores original copies of forms in file and keeps an updated inventory of linens i. Marking and remarking of linen for tap sheet, marking FURNITURE AND of name of hospital and inventory number at the center FIXTURE CHECKLIST Counter, 900mm high, w/ 1 cabinets below Counter, pass-through 1 People Involved: Counter, w/ cabinets above & below 1 1 x Laundry Unit Head Desk, 750 x 1200mm 2 2 x Laundry Workers Cabinet, steel; filing 2 2 x Seamstresses Chair, upright, stacking
4 Table, work
2 Stool, adjustable
3 Shelving, for linen, w/ glass doors 3 ADDITIONAL EQUIPMENT & Planning Relationships: ENGINEERING TERMINALS a. Close to Receiving Area Window curtain rail 1 b. Adjacent to Central Linen Storage Outlet, 10A,2P,240V, duplex 11 universal c. Close to Pressing and Ironing Area Outlet, 10A, 240V, single 1 emergency light Outlet, DATA 1 wall-mounted Outlet, Telephone 1 desktop Computer 1 for coverting, reports/ changing of extra linen Smoke Detector 3 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: QUANTITY REMARKS REMARKS QUANTITY 250B-LL-RDS-01A April 2016 QUANTITY REMARKS 785


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LINEN AND LAUNDRY ISSUING, OFFICE, WORK ROOM & STORAGE 250B-LL-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 1000 Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit linen and laundry staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 786


KEY SCALE 1:150 M A ISSUING AREA 1 Counter, 900mm high, w/ cabinets below 2 Trolley/pushcart, linen B WORK AREA 3 Counter, pass-through 4 Counter, w/ cabinets above & below 5 Desk, 750 x 1200mm 6 Cabinet, steel; filing 7 Chair, upright, stacking 5200 8 Table, work 9 Stool, adjustable 10 Sewing machine 11 Marking machine 12 Waste bin C STORAGE AREA 13 Shelving, for linen, w/ glass doors 14 Step ladder, adjustable D SUPPLY ROOM 6000 6000 3000 3000 SD SD SD 3000 SD 1 2 12 7 A B 3 4 5 7 T D 9 9 9 8 8 5 7 10 10 11 6 6 12 13 13 13 14 14 C D 7 4000 2000 787


Department: Room Title: PRESSING AND IRONING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Laundry Worker inspects linen brought in from the drying Flatwork ironer, 2-roll 1 area and segregates torn linen to be mended Mushroom laundry press 2 b. Laundry Worker shakes out, presses and irons clean linen Ironing board 1 brought in from the drying area Compressor 1 Ironing board 1 People Involved: FURNITURE AND 3 x Laundry Workers FIXTURE CHECKLIST Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Washing Area ENGINEERING TERMINALS b. Adjacent to Issuing, Office, Work Room and Storage Window curtain rail 2 Outlet, 15A,2P,240V, duplex 8 universal Outlet, 10A, 240V, single 2 emergency light exhaust fan Smoke Detector 1 Equipment specific outlet as required preferably GFU April 2016 LINEN AND LAUNDRY 250B-LL-RDS-02A REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 788


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: PRESSING AND IRONING ROOM TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) 100 Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit linen and laundry staff Fire risk low: medium: HIGH Other risks NA ROOM DATA SHEET April 2016 LINEN AND LAUNDRY 250B-LL-RDS-02B 789


                                                             NA

790


Department: Room Title: LINEN AND LAUNDRY WASHING/ DRYING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Linens are washed by Laundry Workers Laundry tub, double compartment 1 Washing machine, industrial 5 Dryer, industrial 5 People Involved: FURNITURE AND 3 x Laundry Workers FIXTURE CHECKLIST Table, shakeout 1 Stool, adjustable 1 Cabinet, supply storage 1 Concealed floor drain 5 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Sorting Area ENGINEERING TERMINALS b. Adjacent to Pressing and Ironing Area Window curtain rail 2 c. Adjacent to Linen Office and Work room Outlet, 15A,2P,240V, duplex 13 universal Outlet, 10A, 240V, single 1 emergency light Smoke Detector 1 REMARKS QUANTITY QUANTITY REMARKS QUANTITY REMARKS 250B-LL-RDS-03A April 2016 Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 791


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LINEN AND LAUNDRY WASHING/ DRYING ROOM 250B-LL-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit linen and laundry staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 792


793 NA


Department: Room Title: LINEN AND LAUNDRY RECEIVING/ SORTING/ DISINFECTION AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Laundry worker counts soiled linen with Nursing Bins, sorting 1 for condemned attendant and tallies the number with the linen list. 1 for infectious b. Laundry worker inspects soiled linen and segregate those 1 for slightly that need repair or those to be condemned, and used-white linens to be washed 1 for heavily c. Temporary transit area for soiled linen soiled-white d. Soiled linen are sorted according to grouping system 1 for slightly being adapted prior to washing used-colored Trolley, dirty linen 3 Basin, big 2 for soaking of heavily soiled colored linen People Involved: FURNITURE AND 3 x Laundry Workers FIXTURE CHECKLIST Table, pre-sorting 1 Stool, adjustable 2 Washing trough, tiled 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Washing/Drying Room ENGINEERING TERMINALS b. Close to Issuing, Office, Work Room and Storage Window curtain rail 3 Outlet, 10A,2P,240V, duplex 7 grounding type,

universal Outlet, 10A, 240V, single 2 exhaust fan, emergency light Smoke Detector 2 QUANTITY REMARKS QUANTITY REMARKS April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: ROOM DATA SHEET 250B-LL-RDS-04A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU 794


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LINEN AND LAUNDRY RECEIVING/ SORTING/ DISINFECTION AREA 250B-LL-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
250-500 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Exhaust (Pa) NA Daylight essential:DESIRABLE:unnecessary Inlet (Pa) NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit linen and laundry staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 795


                                                             NA

796


Department: Room Title: LINEN AND LAUNDRY STAFF LOCKERS AND T&B FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Laundry Unit Employees change from street clothes to Waste bin w/ black lining 2 work clothes and personal protective equipment (PPE) b. Laundry Unit Employees perform personal hygiene activities c. Use of toilet facilities d. Laundry Unit Employees store clothing and personal effects in the Locker Area People Involved: FURNITURE AND Laundry Unit Workers FIXTURE CHECKLIST Lockers, steel 9 Water Closet w/ spray hose 2 Lavatory 2 Urinal 1 Floor Strainer 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Located within or adjacent to the Laundy Department ENGINEERING TERMINALS near the Linen Office to keep the area always clean Window curtain rail 2 and dry Outlet, 10A,2P,240V, duplex 1 universal Outlet, 10A, 240V, single 1 emergency light Smoke Detector 1 QUANTITY REMARKS Updated Reference: DEVELOPMENT BUREAU ROOM DATA SHEET Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: REMARKS QUANTITY 250B-LL-RDS-05A April 2016 QUANTITY REMARKS 797


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 LINEN AND LAUNDRY STAFF LOCKERS AND T&B 250B-LL-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit linen and laundry staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 798


5300 KEY SCALE 1:100 M 3000 1 LOCKER AREA 2 Lockers, steel 3 TOILET & BATH 4 Waste bin 1 SD 3 2 2 2 2 4 2600 2700 2 2 2 2 2 3 4 1500 2000 3300 1500 799


Department: Room Title: FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Laundry worker examines linen for repair and Trolley, linen 1 tallies number on linen list/inventory Sewing Machine 1 b. Laundry worker repairs torn/damaged linen

by hand and/or using sewing machine

c. Laundry worker folds repaired linen on work

table d. Repaired linen is transferred to trolley
for transport to Pressing/Ironing Room People Involved: FURNITURE AND 2 x Laundry Workers FIXTURE CHECKLIST

Table, sorting 1

Table, work 1

Stool, adjustable 3

ADDITIONAL EQUIPMENT & ENGINEERING TERMINALS Planning Relationships: Outlet, 10A,2P,240V, duplex 4 grounding type, a. Adjacent to Washing/Drying Room

universal slots b. Adjacent to Pressing/Ironing Room Outlet, 10A,2P,240V, single 1 for emergency light

Smoke detector 1

250B-LL-RDS-06A Updated Reference: REMARKS QUANTITY REMARKS Department of Health DEVELOPMENT BUREAU HEALTH FACILITY LINEN AND LAUNDRY QUANTITY Hospital: SEWING & SORTING RM 250-Bed (Level 3) ROOM DATA SHEET Reference Sheet Number: QUANTITY REMARKS April 2016 800


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 250-500 Room temperature atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity (%RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit linen and laundry staff Fire risk LOW: medium : high Other risks NA ROOM DATA SHEET April 2016 250B-LL-RDS-06B LINEN AND LAUNDRY SEWING & SORTING RM 801


KEY SCALE 1:100 M SD 1 Table, sorting 2 Table, work 3 Stool, adjustable 4 Machine, sewing 5 Trolley, linen 5100 6000 1 3 4 3 2 3 5 802


12000 6000 6000 STORAGE/ WAREHOUSE STAFF LOCKERS & T&B WORK AREA HEAD'S OFFICE STAFF PANTRY JAN CLO 6000 6000 27000 TEMPERATURE- CONTROLLED STORAGE ROOM HAZARDOUS ITEMS STORAGE ROOM ISSUING MEETING ROOM LOADING/ UNLOADING BAY SCALE 1:300 M 12000 3000 3000 3000 3000 3000 3000 803


Department: Room Title: PROPERTY AND SUPPLY STORAGE/ WAREHOUSE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of tools, equipment, instruments, materials, and Fire Extinguisher 4 other supplies needed by the different departments of Exhaust fan 4 the hospital People Involved: FURNITURE AND Property and Supply Staff FIXTURE CHECKLIST Plastic Pallets, 1000mmX1200mm 6 Shelving, railing, adjustable 25 Door, Roll-up, Aluminum 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. With a good view from the Staff and Head's Office ENGINEERING TERMINALS b. With direct access from the service road for easier Outlet, 10A,2P,240V, duplex 11 grounding type, delivery/ loading and distribution of supplies

universal and equipment Outlet, 10A, 240V, single 1 emergency light Smoke Detector 4 REMARKS QUANTITY Updated Reference: QUANTITY REMARKS QUANTITY REMARKS ROOM DATA SHEET 250B-PS-RDS-01A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU April 2016 Reference Sheet Number: 804


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PROPERTY AND SUPPLY STORAGE/ WAREHOUSE 250B-PS-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
150 Room temperature (°C) atmospheric Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary Negative Pressure (Pa) NA Daylight essential:DESIRABLE:unnecessary Positive Pressure (Pa) NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Property and Supply Staff Fire risk low: MEDIUM: high Other risks NA ROOM DATA SHEET 805


                                                             NA

806


Department: Room Title: PROPERTY AND SUPPLY WORK AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Staff reads, writes and uses computer in work station Computer 10 w/ internet access b. Staff receives visitors/ vendors Calculator 10 c. Stores, files and retrieves records ACU 1 d. Staff assists the Property Supply Officer in locating vendors Whiteboard 3 of materials, equipment and supplies Waste bin w/ black lining 10 e. Staff checks on delayed orders and expedite delivery People Involved: FURNITURE AND 10 x Clerks FIXTURE CHECKLIST Visitors/ Vendors Desk, 600 x 1200mm 10 Desk extension, 400 x 800mm 10 Chair, clerical 10 Chair, visitor 5 Cabinet, steel filing 3 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to PSO's Office and Storage / Warehouse Area ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 3 grounding type,

universal Outlet, 10A, 240V, single 1 emergency light Outlet, telephone 2 Outlet, DATA 6 Smoke Detector 2 QUANTITY REMARKS ROOM DATA SHEET 250B-PS-RDS-02A Department of Health HEALTH FACILITY QUANTITY REMARKS Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: 807


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PROPERTY AND SUPPLY WORK AREA 250B-PS-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 500 Volume (cu.m./hr.-person) 25 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary NA Daylight essential:DESIRABLE:unnecessary NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.9 SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Property & Supply Officer and Vendors/ Visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 808 Negative Pressure (Pa) Positive Pressure (Pa)


5 NA 809


Department: Room Title: PROPERTY AND SUPPLY HEAD'S OFFICE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Property Supply Officer makes requisition, inventory, Computer 1 w/ printer distribution, and control of tools, equipment, materials, and supplies for a department or division Whiteboard 1 b. PSO controls purchasing department budgets Waste bin w/ black lining 1 d. PSO develops and implements purchasing and contract supplies and interviews them to determine product availability and terms of sales e. Property Supply Officer analyzes market and delivery systems to assess present and future material availability People Involved: FURNITURE AND 1 x Property Supply Officer FIXTURE CHECKLIST Visitors/ Vendors Desk, 750 x 1500mm 1 Desk, extension, 400 x 1200mm 1 Chair, junior executive 1 Chair, visitor 2 Cabinet, steel filing 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Work Area and Storage / Warehouse ENGINEERING TERMINALS Window curtain rail 1 Outlet, 10A,2P,240V, duplex 5 grounding type,

universal Outlet, 10A, 240V, single 1 emergency light Outlet, telephone 1 Outlet, DATA 1 Smoke Detector 1 Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: QUANTITY REMARKS ROOM DATA SHEET 250B-PS-RDS-03A Department of Health HEALTH FACILITY QUANTITY REMARKS 810 ACU 1


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PROPERTY AND SUPPLY HEAD'S OFFICE 250B-PS-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
250-500 Room temperature (°C) 23 Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) Whiteboard Volume (cu.m./hr.-person) 25 Color rendering Waste bin w/ black lining Velocity (m./min.) 30 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

NA Daylight essential:DESIRABLE:unnecessary

NA View out essential:DESIRABLE:unnecessary % Dust filtration 93%-99% @ 1 micron Privacy essential:DESIRABLE:unnecessary Humidity (% RH) 50 Black out essential:desirable:UNNECESSARY Cooling load (TR) 0.6 Desk, 750 x 1500mm Desk, extension, 400 x 1200mm SOUND SAFETY Chair, junior executive Acceptable sound level (db) 60 Accessible hot surface: Chair, visitor Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) Cabinet, steel filing Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Property & Supply Officer and Vendors/ Visitors Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 811 Negative Pressure (Pa) Positive Pressure (Pa)


                                                             NA

812


Department: Room Title: PROPERTY AND SUPPLY STAFF PANTRY FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Property and Supply Staff eat their meals Exhaust fan 1 b. Staff do clean-up activities Fire extinguisher 1 Refrigerator 1 Water dispenser 1 Waste bin 1 People Involved: FURNITURE AND 4 x Property and Supply Staff FIXTURE CHECKLIST Table, dining, 4-seater 1 Chair, dining 4 Counter, w/ cabinets above & below 1 Sink, single basin, w/ drainboard 1 and below Concealed floor drain 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Within the Property and Supply Building ENGINEERING TERMINALS Window curtain rail 1 Outlet, 10A,2P,240V, duplex 6 grounding type,

universal Outlet, 10A, 240V, single 1 emergency light Smoke Detector 1 QUANTITY REMARKS QUANTITY REMARKS ROOM DATA SHEET 250B-PS-RDS-04A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: 813


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PROPERTY AND SUPPLY STAFF PANTRY 250B-PS-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:DESIRABLE:unnecessary Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light essential:DESIRABLE:unnecessary NA Daylight essential:DESIRABLE:unnecessary NA View out essential:DESIRABLE:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Property and Supply Staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET Negative Pressure (Pa) Positive Pressure (Pa) 814


                                                             NA

815


Department: Room Title: PROPERTY AND SUPPLY STAFF LOCKERS, T&B, AND JAN. CLO. FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Property and Supply Staff change clothes in the T&B Waste bin w/ black lining 2 b. Property and Supply Staff store clothing and other Exhaust fan 1 personal belongings c. Property and Supply Staff take a bath in the T&B d. Property and Supply Staff urinate and defecate e. Janitor stores cleaning supplies and tools People Involved: FURNITURE AND 4 x Property and Supply Staff FIXTURE CHECKLIST 1 x Janitor Locker, steel, 300 x 500mm 5 Lavatory 4 Water closet 3 Urinal 1 Shower room 2 Slop sink, with floor strainer 1 Shelves, open 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Staff Pantry ENGINEERING TERMINALS b. Close to Head Office and Work Area Window curtain rail 1 Outlet, 10A,2P,240V, duplex 1 grounding type,

universal Outlet, 10A,2P,240V, duplex 2 GFCI Outlet, 10A, 240V, single 1 emergency light Smoke Detector 1 ROOM DATA SHEET 250B-PS-RDS-05A Department of Health HEALTH FACILITY Hospital: 250-Bed (Level 3) DEVELOPMENT BUREAU April 2016 Reference Sheet Number: REMARKS QUANTITY Updated Reference: QUANTITY REMARKS QUANTITY REMARKS 816


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 PROPERTY AND SUPPLY STAFF LOCKERS, T&B, AND JAN. CLO. 250B-PS-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX)
150 Room temperature (°C) ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m./min.) 45 Standby light essential:DESIRABLE:unnecessary Pressure Differential: Emergency light ESSENTIAL:desirable:unnecessary

NA Daylight essential:DESIRABLE:unnecessary

NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity (% RH) NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be NA Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit Property and Supply Staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 817 Negative Pressure (Pa) Positive Pressure (Pa)


KEY SCALE 1:150 M 3000 3000 1 LOCKER AREA 2 Locker, steel, 300 x 500mm 3 TOILET & BATH 4 Waste bin 3000 5 JANITOR'S CLOSET 6 Slop sink, with floor strainer 7 Shelves, open GFCI 3000 1 2 3 3 4 4 5 6 7 SD GFCI 1725 2775 2400 2100 2925 1575 1400 1600 818 1150 1850 1600 1400 1950 1050


15000 9000 6000 MORGUE 10000 AUTOPSY AREA TISSUE PROCESSING AREA LOCKER & T&B SCALE 1:300 M FAMILY GRIEVING ROOM J.C. 819


Department: Room Title: MORGUE AUTOPSY & TISSUE PROCESSING ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Pathologist performs autopsy procedure on Table, mayo 1 deceased patients b. Pathologist performs toileting activites after Suction apparatus 1 procedure Scale 1

Kick bucket 1

Instrument sterilizer, with stand 1 Autotechnicon tissue processor 1 Waste bin w/ yellow lining 1 infectious Waste bin w/ yellow lining 2 pathological People Involved: FURNITURE AND 1 x Pathologist FIXTURE CHECKLIST 1 x Medical Technologist Counter, tiled, with cabinets 2 above & below Sink, instrument & scrub, with 2 gooseneck spout & spray, foot

 control - sensor type

Stool, adjustable 2 Table, autopsy, with sink 1 Concealed floor drain 2 Planning Relationships: ADDITIONAL EQUIPMENT & a. Close to Ante Room/Lobby ENGINEERING TERMINALS b. Adjacent to Locker Room and T&B Window curtain rail 4 c. Adjacent to Morgue Outlet, 10A,2P,240V, duplex 9 grounding type,

universal slots Outlet, 15A,2P,240V, duplex 1 suction apparatus Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 2 QUANTITY REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) Reference Sheet Number: 250B-MOR-RDS-01A QUANTITY REMARKS QUANTITY REMARKS Footstool 1 820


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 MORGUE AUTOPSY & TISSUE PROCESSING ROOM 250B-MOR-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) 10,000 Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary NA Daylight essential:DESIRABLE:unnecessary NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy ESSENTIAL:desirable:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: at sink tolerated Maximum temperature (°C) 70 Access limit morgue staff Fire risk LOW: medium: high Other risks exposure to hazardous chemicals ROOM DATA SHEET 821 Negative Pressure (Pa) Positive Pressure (Pa)


KEY SCALE 1:150 M 1 Counter, tiled, with cabinets above & below 2 Sink, instrument & scrub, with gooseneck spout & spray, foot control - sensor type 3 Stool, adjustable 4 Table, autopsy, with sink 5 Table, mayo 6 Footstool 7 Suction apparatus 8 Scale 9 Kick bucket 10 Instrument sterilizer, with stand 11 Autotechnicon tissue processor 12 Waste bin, infectious 13 Waste bin, pathological 14 Concealed floor drain 10000 6000 1 SD SD 1 2 2 3 3 4 7 8 5 6 9 11 10 14 12 14 13 13 CH CH CH 1500 1500 3000 1500 5700 2800 822


Department: Room Title: MORGUE MORGUE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of deceased bodies awaiting claim by relatives Partition, foldable 2

Waste bin w/ black lining 1 general

People Involved: FURNITURE AND 1 x Pathologist FIXTURE CHECKLIST 1 x Medical Technologist Sofa, 2-seater 2 Relatives Table, 400 x 400mm 1

Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Autopsy Room ENGINEERING TERMINALS Window curtain rail 4 Outlet, 10A,2P,240V, duplex 11 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 2 QUANTITY REMARKS QUANTITY Reference Sheet Number: 250B-MOR-RDS-02A QUANTITY REMARKS REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) Refrigerator, mortuary 7 823


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 MORGUE MORGUE 250B-MOR-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 500 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light ESSENTIAL:desirable:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary NA Daylight essential:desirable:UNNECESSARY NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 50 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit morgue staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 824 Negative Pressure (Pa) Positive Pressure (Pa)


KEY SCALE 1:150 M 1 MORGUE 2 Refrigerator, mortuary 3 Partition, foldable 4 FAMILY GRIEVING ROOM 5 Sofa, 2-seater 6 Table, 400 x 400mm 7 Waste bin, general 3 SD SD SD 2 2 2 2 2 2 2 3 1 4 5 5 7 6 3450 2950 2600 2600 7400 10000 9000 825


Department: Room Title: STAFF LOCKERS, T&B AND JAN. CLO. FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Morgue staff change clothes in Locker Room Waste bin w/ black lining 1 b. Storing of clothes and personal effects

c. Morgue staff perform toiletting activities in T&B

FURNITURE AND People Involved: FIXTURE CHECKLIST 1 x Morgue Technician Locker, steel 1 1 x Pathologist Slop sink, with hose bibb faucet 1 1 x Medical Technologist Shelving, open 1 Lavatory 1 Water Closet 1

Shower 1 Planning Relationships: ADDITIONAL EQUIPMENT & a. Adjacent to Autopsy Room ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 1 grounding type,

universal slots Outlet, 10A,2P,240V, duplex 1 GFCI Outlet, 10A,2P,240V, single 1 emergency light Window curtain rail 2 Smoke detector 1 April 2016 MORGUE 250B-MOR-RDS-03A QUANTITY REMARKS QUANTITY Reference Sheet Number: QUANTITY REMARKS REMARKS Updated Reference: ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) 826


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: Jan-00 MORGUE STAFF LOCKERS, T&B AND JAN. CLO. 250B-MOR-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light essential:DESIRABLE:unnecessary Pressure: Emergency light ESSENTIAL:desirable:unnecessary % Dust filtration NA Privacy ESSENTIAL:desirable:unnecessary Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 60 Accessible hot surface: NA Speech privacy essential:DESIRABLE:unnecessary Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit morgue staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 827 Negative Pressure (Pa) Positive Pressure (Pa) NA Daylight essential:desirable:UNNECESSARY NA View out essential:desirable:UNNECESSARY


828 NA


829


Department: Room Title: CENTRAL WASTE STORAGE WORK AREA FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Janitor places waste bins carts/trolleys Weighing scale 1 b. Janitor stores cleaning tools, supplies and PPEs Washer, high pressure 1 c. Janitor cleans/washes the waste bins and Waste bins / carts / trolleys 3 trolleys Fire extinguisher 1 d. Janitor weighs volume of waste e. Janitor records volume of waste f. Janitors performs hand washing

People Involved: FURNITURE AND 8 x Janitors FIXTURE CHECKLIST

Shelving, 400mm deep 1 Floor strainer 1

Planning Relationships: ADDITIONAL EQUIPMENT & a. Within Central Waste Storage Facility ENGINEERING TERMINALS Window curtain rail 1 Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1 QUANTITY REMARKS QUANTITY Reference Sheet Number: 250B-CWS-RDS-01A QUANTITY REMARKS REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) 830


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 CENTRAL WASTE STORAGE WORK AREA 250B-CWS-RDS-01B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light essential:desirable:UNNECESSARY Pressure: Emergency light essential:desirable:UNNECESSARY NA Daylight essential:DESIRABLE:unnecessary NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit waste management staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 831 Negative Pressure (Pa) Positive Pressure (Pa)


                                                             NA

832


Department: Room Title: CENTRAL WASTE STORAGE HAZARDOUS WASTE ROOM FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST Storage of the following hazardous waste before Waste bins / carts / trolleys 5 yellow treatment : Exhaust fan 1 above door a. Infectious Refrigerator 1 b. Sharps c. Chemical d. Pharmaceutical e. Pathological / Anatomical

People Involved: FURNITURE AND 2 x Janitors FIXTURE CHECKLIST

Planning Relationships: ADDITIONAL EQUIPMENT & a. Within Central Waste Storage Facility ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 5 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1 QUANTITY REMARKS QUANTITY Reference Sheet Number: 250B-CWS-RDS-02A QUANTITY REMARKS REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) 833


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 CENTRAL WASTE STORAGE HAZARDOUS WASTE ROOM 250B-CWS-RDS-02B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light essential:desirable:UNNECESSARY Pressure: Emergency light essential:desirable:UNNECESSARY NA Daylight essential:DESIRABLE:unnecessary NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit waste management staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 834 Negative Pressure (Pa) Positive Pressure (Pa)


                                                             NA

835


Department: Room Title: CENTRAL WASTE STORAGE MERCURY-CONTAINING DEVICES/LAMPS FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of mercury-containing devices/lamps Exhaust fan 1 above door

before being collected by DENR-accredited TSD

(Treatment/Storage/Disposal) Facility

People Involved: FURNITURE AND 2 x Janitors FIXTURE CHECKLIST

Cabinet with shelves 2

Planning Relationships: ADDITIONAL EQUIPMENT & a. Within Central Waste Storage Facility ENGINEERING TERMINALS Window curtain rail 1 Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1 Window curtain rail 1 QUANTITY REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) QUANTITY Reference Sheet Number: 250B-CWS-RDS-03A QUANTITY REMARKS REMARKS 836


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 CENTRAL WASTE STORAGE MERCURY-CONTAINING DEVICES/LAMPS 250B-CWS-RDS-03B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light essential:desirable:UNNECESSARY Pressure: Emergency light essential:desirable:UNNECESSARY NA Daylight essential:DESIRABLE:unnecessary NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit waste management staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET 837 Negative Pressure (Pa) Positive Pressure (Pa)


838 NA


Department: Room Title: CENTRAL WASTE STORAGE BIODEGRADABLE WASTE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of biodegradable waste before being Waste bins / carts / trolleys 3 black

picked up by the local waste transporter Exhaust fan 1 above door

People Involved: FURNITURE AND 2 x Janitors FIXTURE CHECKLIST

Planning Relationships: ADDITIONAL EQUIPMENT & a. Within Central Waste Storage Facility ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1 QUANTITY REMARKS QUANTITY Reference Sheet Number: 250B-CWS-RDS-04A QUANTITY REMARKS REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) 839


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 CENTRAL WASTE STORAGE BIODEGRADABLE WASTE 250B-CWS-RDS-04B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light essential:desirable:UNNECESSARY Pressure: Emergency light essential:desirable:UNNECESSARY NA Daylight essential:DESIRABLE:unnecessary NA View out essential:desirable:UNNECESSARY % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit waste management staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET Negative Pressure (Pa) Positive Pressure (Pa) 840


                                                             NA

841


Department: Room Title: CENTRAL WASTE STORAGE NON-BIODEGRADABLE/ RECYLABLE WASTE FUNCTIONAL DESIGN REQUIREMENTS:

This activity space provides facilities needed EQUIPMENT AND for the following activities: ACCESSORY CHECKLIST a. Storage of non-biodegradable/recyclable waste Waste bins / carts / trolleys 3 yellow

before being transfered to Material Recovery Facility or before being subjected for recycling

People Involved: FURNITURE AND 2 x Janitors FIXTURE CHECKLIST

Planning Relationships: ADDITIONAL EQUIPMENT & a. Within Central Waste Storage Facility ENGINEERING TERMINALS Outlet, 10A,2P,240V, duplex 4 grounding type,

universal slots Outlet, 10A,2P,240V, single 1 emergency light Smoke detector 1 QUANTITY REMARKS Updated Reference: April 2016 ROOM DATA SHEET Department of Health DEVELOPMENT BUREAU HEALTH FACILITY Hospital: 250-Bed (Level 3) QUANTITY Reference Sheet Number: 250B-CWS-RDS-05A QUANTITY REMARKS REMARKS Exhaust fan 1 above door 842


Hospital: Department of Health 250-Bed (Level 3) HEALTH FACILITY DEVELOPMENT BUREAU Updated Reference: Department: Room Title: Reference Sheet Number: April 2016 CENTRAL WASTE STORAGE NON-BIODEGRADABLE/ RECYLABLE WASTE 250B-CWS-RDS-05B TECHNICAL DESIGN DATA:

ENVIRONMENTAL CONDITIONS DESIGN DATA ENVIRONMENTAL CONDITIONS DESIGN DATA AIR

LIGHTING AND VISUAL Outdoor air temperature (°C) ave. local station temp. reading General illumination (LUX) 150 Room temperature ambient Night illumination (LUX) NA Mechanical ventilation Task illumination (LUX) NA Volume (cu.m./hr.-person) 35 Color rendering essential:desirable:UNNECESSARY Velocity (m.hr.) 45 Standby light essential:desirable:UNNECESSARY Pressure: Emergency light essential:desirable:UNNECESSARY Negative Pressure (Pa) Positive Pressure (Pa) % Dust filtration NA Privacy essential:desirable:UNNECESSARY Humidity NA Black out essential:desirable:UNNECESSARY Cooling load (TR) NA SOUND SAFETY Acceptable sound level (db) 70 Accessible hot surface: NA Speech privacy essential:desirable:UNNECESSARY Maximum temperature (°C) NA Quality which cannot be tonal impact Domestic hot water: NA tolerated Maximum temperature (°C) NA Access limit waste management staff Fire risk LOW: medium: high Other risks NA ROOM DATA SHEET

NA Daylight essential:DESIRABLE:unnecessary

NA View out essential:desirable:UNNECESSARY 843


                                                             NA

844


MANUAL on TECHNICAL GUIDELINES for HOSPITAL PLANNING and DESIGN 250-BED HOSPITAL
(LEVEL 3)

APPENDICES

First Edition DEPARTMENT OF HEALTH Manila 2017 VOLUME 4 845


VOLUME 4 APPENDICES

TABLE OF CONTENTS

PAGE APPENDIX A

EXISTING HOSPITALS

APPENDIX B

NEW CLASSIFICATION of

HOSPITALS

APPENDIX C

PATIENT CARE AREAS

APPENDIX D

CATEGORIES and SOURCES of

HOSPITAL HEALTHCARE

WASTE

847 849 850 854 855


APPENDIX A

EXISTING HOSPITALS

The devolution of health services to local government units (LGUs), brought about by the Local Government Code of 1991, transferred among others, the provision, management and maintenance of government health facilities (provincial hospitals, district and municipal hospitals, RHUs, BHS) at different levels of LGUs. Currently, the total number of hospitals is 729 of various types such as special, specialty, medical centers, regional, provincial, district, municipal and medicare community hospitals, totalling 49,538 hospital beds. Majority of these existing hospitals are in Region 4-A (CALABARZON) but the total number of beds are concentrated in the National Capital Region / Metro Manila area. However, private hospitals make up for this inequity of health resource distribution with 1,202 hospitals, functional and provided with the latest medical equipment, totalling about 43,645 beds scattered all over the country.

(sources : DOH – Health Facility Development Bureau, formerly NCHFD; and DOH – Health Services and Facilities Regulatory Bureau, formerly BHFS) 849


APPENDIX B

NEW CLASSIFICATION OF HOSPITALS

Department of Health Administrative Order No. 2012-0012 “Rules and Regulations Governing the New Classification of Hospitals and Other Health Facilities in the Philippines”

and

R.A. 4226 “Hospital Licensure Act”

Based on the above, hospitals shall be classified as follows :

a. ACCORDING TO OWNERSHIP

  1. Government Hospital – created by law. A government health facility may be under the national government, DOH, Local Government Unit (LGU), Department of National Defense (DND), Philippine National Police (PNP), Department of Justice (DOJ), State Universities and Colleges (SUCs), Government Owned and Controlled Corporations (GOCC) and others.
  2. Private Hospital – owned, established and operated with funds through donation, principal, investment or other means by any individual, corporation, association or organization. A private health facility may be a single proprietorship, partnership, corporation, cooperative, foundation, religious, non-government organization and others.
    b. ACCORDING TO SCOPE OF SERVICES
  3. General – a hospital that provides services for all kinds of illnesses, diseases, injuries or deformities. A general hospital shall provide medical and surgical care to the sick and injured, maternity, newborn and childcare. It shall be equipped with the service capabilities needed to support board certified / eligible medical specialties and other licensed physicians rendering services in, but not limited to, the following : a) Clinical Services

Family Medicine 2) Pediatrics 3) Internal Medicine 850


Obstetrics and Gynecology 5) Surgery b) Emergency Services c) Outpatient Services d) Ancillary and Support Services such as, Clinical Laboratory, Imaging Facility and Pharmacy 2. Specialty – a hospital that specializes in a particular disease or condition or in one type of patient. A specialized hospital may be devoted to treatment of any of the following : a) Treatment of a particular type of illness or for a particular condition requiring a range of treatment Examples : Philippine Orthopedic Center, National Center for Mental Health, San Lazaro Hospital, a hospital dedicated to the treatment of cancer
b) Treatment of patients suffering from diseases of a particular organ or group of organs Examples : Lung Center of the Philippines, Philippine Heart Center, National Kidney and Transplant Institute, a hospital dedicated to the treatment of eye disorders
c) Treatment of patients belonging to a particular group such as children, women, elderly, and others.
Examples : Philippine Children’s Hospital, Dr. Jose Fabella Memorial Hospital
c. ACCORDING TO FUNCTIONAL CAPACITY

  1. General Hospital
    a) Level 1 A Level 1 hospital shall have as a minimum the services stipulated under Rule V.B.1.b.1. of this Order, including, but not limited to, the following:

A staff of qualified medical, allied medical and administrative personnel headed by a physician duly licensed by the Professional Regulatory Commission (PRC); 851


Bed space for its authorized bed capacity in accordance with DOH Guidelines in the Planning and Design of Hospitals; 3) An Operating Room with standard equipment and provision for sterilization of equipment and supplies in accordance with: a. DOH Reference Plan in the Planning and Design of an Operating Room/Theater (Annex A) b. DOH Guidelines on Cleaning, Disinfection and Sterilization of Reusable Medical Devices in Hospital Facilities in the Philippines (Annex B)
4) A Post-Operative Recovery Room; 5) Maternity facilities, consisting of ward(s), room(s), a Delivery Room, exclusively for maternity patients and newborns; 6) Isolation facilities with proper procedures for the care and control of infectious and communicable diseases as well as for the prevention of cross infections; 7) A separate dental section/clinic; 8) Provision for blood station; 9) A DOH licensed Secondary Clinical Laboratory with the services of a consulting Pathologist; 10) A DOH licensed Level 1 Imaging Facility with the services of a consulting Radiologist; and
11) A DOH licensed Pharmacy.
b) Level 2
A Level 2 hospital shall have as a minimum, all of Level 1 capacity, including, but not limited to, the following: 1) An organized staff of qualified and competent personnel with Chief of Hospital/Medical Director and appropriate board certified Clinical Department Heads; 2) Departmentalized and equipped with the service capabilities needed to support board certified/eligible medical specialists and other licensed physicians rendering services in the specialties of Medicine, Pediatrics, Obstetrics and Gynecology, Surgery, their subspecialties and ancillary services; 852


Provision for general ICU (Intensive Care Unit) for critically ill patients; 4) Provision for NICU (Neonatal Intensive Care Unit); 5) Provision for HRPU (High-Risk Pregnancy Unit); 6) Provision for respiratory therapy services; 7) A DOH licensed Tertiary Clinical Laboratory; 8) A DOH licensed Level 2 Imaging Facility with Mobile X-Ray inside the institution and with capability for contrast examinations.
c) Level 3 A Level 3 hospital shall have as a minimum, all of Level 2 capacity, including, but not limited to, the following: 1) Teaching and/or training hospital with accredited residency training program for physicians in the four (4) major specialties namely: Medicine, Pediatrics, Obstetrics and Gynecology, and Surgery; 2) Provision for Physical Medicine and Rehabilitation Unit; 3) Provision for Ambulatory Surgical Unit; 4) Provision for Dialysis facility; 5) Provision for Blood Bank; 6) A DOH licensed Tertiary Clinical Laboratory with standard equipment/reagents/supplies necessary for the performance of histopathology examinations; 7) A DOH licensed Level 3 Imaging facility with interventional Radiology.
2. Specialty Hospital (refer to Rule V.B.1.b.2. of this Order) 3. Trauma Capability of Hospitals The trauma capability of hospitals shall be assessed in accordance with the guidelines formulated by the Philippine College of Surgeons (PCS). a) Trauma-Capable Facility – a DOH licensed hospital designated as a Trauma Center.
b) Trauma-Receiving Facility – a DOH licensed hospital within the trauma service area which received trauma patients for transport to the point of care or a trauma center.
853


APPENDIX C

PATIENT CARE AREAS

Patient care areas, classified as follows, shall be those areas designated by the governing body of the health care facility in accordance with the type of patient care anticipated:

  1. General Care Areas are patient bedrooms, examining rooms, treatment rooms, clinics and similar areas in which it is intended that the patient shall come in contact with ordinary appliances such as a nurse call system, electrical beds, examining lamps, telephone and entertainment devices. In such areas, it may also be intended that patients be connected to electromedical devices (such as heating pads, electrocardiographs, drainage pumps, monitors, otoscope, opthalmoscopes, peripheral intravenous lines).
  2. Critical Care Areas are those special care units, intensive care units, coronary care units, angiography, laboratories, cardiac catheterization laboratories, delivery rooms, operating rooms and similar areas in which patients are intended to be subjected to invasive procedures and connected to line-operated, electromedical devices.
  3. Wet Locations are patient care areas that are normally subject to wet conditions while patients are present. These include standing fluids on the floor or drenching of the work area, either of which condition is intimate to the patient or staff. Routing housekeeping procedures and incidental spillage on liquids do not define a wet location.

(source : Philippine Electrical Code, Article 5.17.1.2.) 854


APPENDIX D

CATEGORIES and SOURCES of HOSPITAL HEALTHCARE WASTE

“Health care Waste” (HCW) includes all the solid and liquid waste generated as a result of any of the following :

 Diagnosis, treatment or immunization of human beings;  Research pertaining to the above activities;  Research using laboratory animals for the improvement of human health;  Production or testing of biologicals; and
 Other activities performed by the health care facility

“Healthcare Facilities” (HCF), for this purpose, are public, private and non- governmental institutions/facilities that contribute to the improvement of the health status of an individual.

Categories of Healthcare Waste

A. Infectious

  • All waste suspected to contain pathogens (or their toxins) in sufficient concentration to cause diseases to a potential host.
  • Discarded materials or equipment used for diagnosis, treatment and prevention of disease of patients with infectious disease.
  • Highly infectious waste include microbial cultures and stocks of highly infectious agents from Medical Analysis Laboratories and biofluids from patients with highly infectious diseases (these require disinfection at source) Examples : Solid wastes from patients with infectious disease (e.g., dressings, swabs, blood bag, urine bag, sputum cup); Liquid wastes from patients with infectious disease (e.g., feces, urine, blood or other body secretions); Food wastes (liquid or solid) of patients with highly infectious disease.
    B. Sharps
  • Items that can cause cuts or puncture wounds.
    Examples : Used or expired sharps (e.g., hypodermic, intravenous or other needles, auto-disable syringes, syringes with attached needles, infusion sets, scalpels, pipettes, knives, blades, broken glass, wet ampoules); Except syringes and needles used for antineoplastic purposes
    855

C. Pathological and Anatomical

  • Refers to tissue sections and body material derived from biopsies or surgical procedures that are then examined in the laboratory.
  • Anatomical waste is a subgroup of pathological waste. This type of waste refers to recognizable human body parts such as amputated limbs, etc.
    Examples : Placenta, internal organs, tissues used for diagnostic procedures such as biopsy, blood, fetus; Amputated body parts like legs.
    D. Pharmaceutical
  • Refers to expired, spilt and contaminated pharmaceutical products, drugs and vaccines. Also refers to discarded items used in handling pharmaceuticals.
  • Pharmaceuticals wastes include antineoplastic, cytotoxic, and genotoxic waste. Drugs usually used in oncology (antineoplastic drugs) or radiotherapy units have a high hazardous mutagenic or cytotoxic effect.
    Examples : Empty vials, bottles, connective tubing; Medical supplies and containers of cytotoxic drugs or chemicals E. Chemical
  • Discarded chemicals (solid, liquid, or gaseous) generated during disinfecting and sterilizing procedures
  • Chemical wastes can be further classified into corrosive, reactive, toxic and flammable
  • Chemical wastes also include wastes with high content of heavy metals and their derivatives Examples : Laboratory reagents, film developer, disinfectants and soaking solutions, solvents; Concentrated ammonia solutions, concentrated hydrogen peroxide chlorine, silver nitrate; Cadmium, mercury from broken thermometers, sphygmomanometers
    F. Radioactive
  • Wastes exposed to radionuclide. Residues from shipment of radioactive materials and unwanted solution of radionuclide intended for diagnostic or therapeutic use.
    856

  • Liquids, gas and solids contaminated with radionuclide whose ionizing radiations have genotoxic effects. Examples : Cobalt (60 Co), Technetium (99 Tc), Iodine (131 I)), and Iridium (192 Ir); Contaminated waste, patient’s excretion and all materials used by patients exposed with radionuclide within 48 hours
    G. Non-Hazardous or General
  • Waste that has not been in contact with communicable or infectious agents, hazardous chemicals or radioactive substances, and does not pose a hazard.
    Examples : Paper, cardboard, empty bottle, tetra pack, scrap material, pressurized containers, office waste, food waste and other materials of patients with non-communicable disease, X-Ray plates.

(source : DOH Manual on Healthcare Waste Management – Third Edition)
857


REFERENCES

 Manual on Technical Guidelines for Hospitals and Health Facilities Planning and Design 100-Bed Hospital. Department of Health, Manila. 1994.  Signage Systems Manual for Hospitals and Offices. Department of Health, Manila. 1994.
 Healthcare Waste Management Manual 3rd Edition. Department of Health, Manila. 2011.  The Fire Code of the Philippines and its Implementing Rules and Regulations RA 9514. Bureau of Fire Protection, Manila. 2009.  National Building Code of the Philippines and its Implementing Rules and Regulations PD 1096. Department of Public Works and Highways. 2005.  The Law to Enhance Mobility of Disabled Persons BP 344. 1983.  DOH Administrative Order 2010-0036 : Universal Health Care for All Filipinos “Kalusugang Pangkalahatan”  DOH Administrative Order No. 2012-0012 : Rules and Regulations Governing the New Classification of Hospitals and Other Health Facilities in the Philippines
 PhilHealth Benchbook for Quality Assurance in Healthcare. 2006.  Safe Hospitals in Emergencies and Disasters, Philippine Indicators. Department of Health, Manila. 2011.

CROSS-REFERENCES

 Manual for Medical Social Workers 5th Edition. Department of Health, Manila. 2010.  Manual of Standards and Guidelines on the Management of Hospital Emergency. Department of Health, Manila. 2010.  Hospital Nursing Service Administration Manual. Department of Health, Manila. 2010.  Hospital Nutrition and Dietetics Service Management Manual. Department of Health, Manila. 2010.  Hospital Information Management Systems Manual. Department of Health, Manila. 2010.  Hospital Property and Supply Management Manual. Department of Health, Manila. 2010.  National Standards Infection Control for Healthcare Facilities Revised Edition. Department of Health, Manila. 2010.  Manual on Standards on Quality Management of the Administrative and Finance Service for Hospitals. Department of Health, Manila. 2008. 859